Installation

Model GXLO sprinklers must be installed according to appropriate 
NFPA Standards, FM Global Loss Prevention Data Sheets, and/or 
the requirements of the authority having jurisdiction.

Use only the Model H sprinkler wrench for sprinkler installation 
or use the Model JV wrench to install the sprinkler/guard 
assembly (Figure 3). Any other type of wrench may damage 
the sprinkler.  Damaged sprinklers must be replaced 
immediately.

A leak tight joint should be obtained with a torque of 14 to 20 
lb-ft (19 to 27 N

.

m) for 3/4 inch NPT and ISO 7-R3/4 thread 

sprinklers. For 1/2 inch NPT and ISO 7-R1/2 thread sprinklers the 
recommended installation torque is 8 to 18 lb-ft (11 to 24 N

.

m). 

Exceeding the maximum recommended torque may cause leakage 
or impairment of the sprinklers.

Maintenance

Reliable Model GXLO sprinklers should be inspected and the 
sprinkler system maintained in accordance with NFPA
25, as well as the requirements of any Authorities Having
Jurisdiction.

Prior to installation, sprinklers should remain in the original 
cartons and packaging until used. This will minimize the 
potential for damage to sprinklers that could cause improper 
operation or non-operation.

Do not clean sprinklers with soap and water, ammonia liquid or 
any other cleaning fluids. Remove dust by gentle vacuuming 
without touching the sprinkler.

Replace any sprinkler which has been painted (other than 
factory applied). A stock of spare sprinklers should be 
maintained to allow quick replacement of damaged or 
operated sprinklers.

Failure to properly maintain sprinklers may result in inadvertent 
operation or non-operation during a fire event.

Guarantee

For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms, 
and conditions, visit www.reliablesprinkler.com.

Ordering Information

Specify the following when ordering.

       

 Model GXLO Sprinkler

 

•  [Upright] [3/4” NPT] [ISO 7-R3/4]
•  [Pendent] [3/4” NPT] [ISO 7-R3/4]
•  [Upright Retrofit] [1/2” NPT] [ISO 7-R1/2]
•  [Upright with factory installed shield]

        Temperature Rating

 

• [165°F (74°C)] [212°F (100°C)] [286°F (141°C)]

        

Finish

 

•  See Table C

        

Guard/Shield

 

•  See Technical Specifications

      

  Sprinkler Wrench

 

•  [Model H] [Model JV (required with pre-installed 

                    guards)]

Standard 

Finishes

Special Application 

Finishes

Bronze

Lead Plated 

(1)

 165°F (74°C), 212°F (100°C) and   

286°F (141°C) Temp. Ratings

Chrome

 (1)

Wax 

(1) (2) 

165°F (74°C) Clear Wax, 

212°F    (100°C) Brown Wax

Wax/Lead 

(1) (2)

165°F (74°C) Clear Wax, 

212°F (100°C) Brown Wax

(1)

 cULus, upright (without shield) only.

(2)

 212°F (100°C) Brown wax may be used on 286°F (141°C) Sprinklers 

    when maximum ambient temperatures do not exceed 150°F (66°C).

Sprinkler Finishes

Table C

Wrenches

Figure 3

Model H Wrench (sprinkler)

Model JV Wrench (with guard installed)

Classification

Sprinkler

Rating

Maximum 

Ambient 

Temperature

Frame Color

°F

°C

°F

°C

Ordinary

Intermediate

High

165
212
286

74

100
141

100
150
225

38
66

107

Uncolored

White

Blue

Temperature Ratings

Table D

Bulletin 129
August 2020

Page 5 of 5

www.reliablesprinkler.com