Description

The Series TY-B, 5.6 and 8.0 K-factor,
Upright and Pendent Sprinklers de-
scribed in this data sheet are standard
response - standard coverage, deco-
rative 5 mm glass bulb

type spray

sprinklers designed for use in light,
ordinary, or extra hazard, commercial
occupancies such as banks, hotels,
shopping malls, factories, refineries,
chemical plants, etc.

The recessed version of  the Series
TY-B Pendent Sprinkler, where appli-
cable, is intended for use in areas with
a finished ceiling. It uses a two-piece
Style 10 (1/2 inch NPT) or Style 40 (3/4
inch NPT) Recessed Escutcheon. The
Recessed Escutcheon provides 1/2
inch (12,7 mm) of recessed adjust-
ment or up to 3/4 inch (19,1 mm) of
total adjustment from the flush pen-
dent position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.

Corrosion resistant  coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these corrosion resistant coatings
for any given corrosive environment.
The effects of ambient temperature,
concentration of chemicals, and
gas/chemical velocity, should be con-
sidered, as a minimum, along with the
corrosive nature of the chemical to
which the sprinklers will be exposed.

An intermediate level version of the
Series TY-B Pendent Sprinkler can be

obtained by utilizing the Series TY-B
Pendent Sprinkler in combination with
the Model S2 Shield.

WARNINGS

The Series TY-B Sprinklers described
herein must be  installed and  main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the integrity of these devices.

The owner is responsible for maintain-
ing their fire protection system and de-
vices in  proper operating  condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.

Model/Sprinkler
Identification
Numbers

TY3151 -

Upright 5.6K, 1/2"NPT

TY3251 -

Pendent 5.6K, 1/2"NPT

TY4151 -

Upright 8.0K, 3/4"NPT

TY4251 -

Pendent 8.0K, 3/4"NPT

TY4851 -

Upright 8.0K, 1/2"NPT

TY4951 -

Pendent 8.0K, 1/2"NPT

Technical
Data

Approvals

UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)

Maximum Working Pressure

175 psi (12,1 bar)

Discharge Coefficient

K = 5.6 GPM/psi

1/2

(80,6 LPM/bar

1/2

)

K = 8.0 GPM/psi

1/2

(115,2 LPM/bar

1/2

)

Temperature Ratings

Refer to Table A

Finishes

Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated,
Chrome Plated, (Other colors are
available on request.)

Physical Characteristics

Frame

. . . . . . . . . . . . Bronze

Button

. . . . . . . .

Brass/Copper

Sealing Assembly . . . . . . . . . .

. . . . . . Beryllium Nickel w/Teflon†

Bulb

. . . . . . . . . . . . . . Glass

Compression Screw . . . . . Bronze
Deflector . . . . . . . . . . . Copper

D

uP

on

t

R

eg

is

tere

d

T

rad

ema

rk

Series TY-B — 5.6 and 8.0 K-factor
Upright and Pendent Sprinklers
Standard Response, Standard Coverage

Technical Services:

Tel: (800) 381-9312 / Fax: (800) 791-5500

Page 1 of 8

TFP151

FEBRUARY, 2002

Customer Service/Sales:

Tel: (414) 570-5000 / (800) 558-5236

Fax: (414) 570-5010 / (800) 877-1295

TFP151 (TD515A)

OBSOLETE

Summary of Contents for Gem TY-B

Page 1: ...te level version of the Series TY B Pendent Sprinkler can be obtained by utilizing the Series TY B Pendent Sprinkler in combination with the Model S2 Shield WARNINGS The Series TY B Sprinklers described herein must be installed and main tained in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association in addition to the standards of any ...

Page 2: ... orifice seat on frame Pipe thread connections per ISO 7 1 can be provided on special request 2 4 5 6 PENDENT CROSS SECTION 58 7 mm 2 5 16 39 7 mm 1 9 16 PLATE SEATING ESCUTCHEON 1 2 12 7 mm NOMINAL MAKE IN SURFACE 1 3 NPT 3 4 RECESSED PENDENT UPRIGHT 12 7 mm NOMINAL MAKE IN 1 2 RECESSED STYLE 40 ESCUTCHEON 57 2 mm 2 1 4 3 4 NPT DEFLECTOR SSU SSP DEFLECTOR 7 FLATS WRENCH 2 7 8 73 0 mm DIA FIGURE 2...

Page 3: ...position of the sprinkler fitting to suit The Series TY B Pendent and Up right Sprinklers must be installed in accordance with the following instruc tions Step 1 Pendent sprinklers are to be installed in the pendent position and upright sprinklers are to be installed in the upright position Step 2 With pipe thread sealant ap plied to the pipe threads hand tighten the sprinkler into the sprinkler f...

Page 4: ...orrosion Resistant Sprinklers Installed with Style 10 1 2 NPT or Style 40 3 4 NPT 3 4 Total Adjustment Recessed Escutcheon as applicable 150 F 66 C Maximum Ceiling Temperature White or Any Color Frame and Deflector only N A Not Available TABLE A LABORATORY LISTINGS AND APPROVALS 1 2 5 WAX OVER LEAD COATED LEAD COATED WAX COATED N A 1 2 3 5 1 2 3 5 1 2 3 5 1 2 3 5 1 2 3 5 N A 5 6 1 2 NPT PENDENT TY...

Page 5: ...gled downward and then touch the wax stick to the rod approximately one half inch away from the area re quiring retouching The wax will melt and run down onto the sprinkler The Series TY B Recessed Pendent Sprinklers must be installed in ac cordance with the following instruc tions Step A After installing the Style 10 or 40 Mounting Plate as applicable over the sprinkler threads and with pipe TFP1...

Page 6: ...pec tions should be made so as to better determine the exact sprinkler condi tion and the long term integrity of the corrosion resistant coating as it may be affected by the corrosive conditions present The owner is responsible for the in spection testing and maintenance of their fire protection system and de vices in compliance with this docu ment as well as with the applicable standards of the N...

Page 7: ...ify Specify color color coded Wax Stick for retouching specify tem perature rating temperature rated Se ries TY B Sprinklers P N specify Black for 135 F P N 56 065 1 135 Red for 155 F P N 56 065 1 155 Yellow for 175 F P N 56 065 1 175 Blue for 200 F and 286 F P N 56 065 1 286 NOTES Each wax stick is suitable for retouch ing up to twenty five sprinklers The wax used for 286 F sprinklers is the same...

Page 8: ...Page 8 of 8 TFP151 TYCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale Pennsylvania 19446 O B S O L E T E ...

Reviews: