background image

7.

Note:

In order for the solenoid valve to maintain Reliable’s war-
ranty it must remain sealed as it came from the factory. If 
there are concerns about the valve’s internal components, 
immediate replacement is recommended.

System Operation (Double Interlock) 

To fully activate (water delivery to a fire) the Reliable Model 

DDX Type F PrePaK in a double interlock application, a fire 
detection device (smoke, heat, etc.) (two different detectors 
with cross-zoned detection) must activate and the sprinkler 
system’s piping must be purged of its supervisory air pres-
sure (i.e. from a discharged sprinkler head). 

When the system is properly set for service, the water sup-

ply pressure  simultaneously acts on both the underside of 
the deluge valve’s clapper and on the valve’s push rod by 
means of the pressurized push rod chamber. The resultant 
pressure force acting on the push rod, in unison with the me-
chanical advantage of the deluge valve’s lever, is more than 
sufficient to hold the valve’s clapper in the closed position 
against the water supply pressure. 

Energizing the releasing solenoid valve is only one of the 

events required towards opening the deluge valve.  Air 
pressure in the sprinkler system must also be reduced to a 
level low enough to activate the Model LP Dry Valve Actua-
tor.  

Both

 of these events allows the deluge valve’s push-

rod chamber to be vented to drain through its outlet. Since 
the push-rod chamber’s pressure cannot be replenished 
through its inlet restriction as rapidly as it is vented though 
its outlet, the pressure falls rapidly. When the push-rod 
chamber pressure drops below one-third of the water sup-
ply pressure, the opening force acting beneath the valve’s 
clapper becomes greater than the push-rod force acting on 
the lever. This causes the clapper to open. Refer to Reliable 
Technical Bulletin 751 for further details. 

Once the clapper has opened, the lever acts as a latch, 

preventing the clapper from returning to the closed position. 
Water from the supply flows through the deluge valve into 
the system piping. Water also flows through the deluge valve 
alarm outlet to activate any water flow alarm devices. Note 
that the solenoid valve will be maintained open by the Pot-
ter Model PFC-4410-RC Releasing/Control Panel’s latching 
feature until it is reset for operation. 

After system shutdown and draining, the Model DDX Del-

uge Valve is easily reset without special tools (see Figs. 10, 
11 or 12 depending on system size). Restore detection de-
vices by resetting or replacing any operated device. Once 
detection devices are restored and the Potter Model PFC-
4410-RC Releasing/Control Panel is reset, water supply 
pressure may be re-applied to the deluge valve.

Maintenance

The Model DDX Type F PrePaK and associated equip-

ment shall periodically be given a thorough inspection and 
test. NFPA 25, Inspection, Testing and Maintenance of water 
Based Fire Protection Systems, provides minimum mainte-
nance requirements. Systems should be tested, operated, 
cleaned and inspected at least annually, and parts replaced 
as required. Periodically open the air/condensate drain valve 
(see Figs. 10, 11 or 12 depending on system size) beneath 

the air tank to drain any condensate accumulation. Reliable 
Technical Bulletin 751 provide information for maintaining 
the Model DDX Deluge Valve. Potter Manual #5403550 pro-
vides information for maintaining the PFC-4410-RC Releas-
ing/Control Panel.

System Reset Procedure (All Sizes)

Refer to Figs. 10, 11 or 12 (depending on system size)
1.  Close the main valve controlling water supply to the 

Model DDX deluge valve.  Also, close the two ¼” valves, 
valves M (Rapid-Air Fill Shutoff Valve) and K (Regulated 
Air Shutoff Valve). 

2.  Close the pushrod chamber supply valve, valve A. 
3.  Open the main drain valve, valve B, and drain the sys-

tem.  

4.  Open all drain valves and vents at low points through-

out the system, closing them when flow of water has 
stopped. Open valve D. 

Note:

 The above steps accom-

plish the relieving of pressure in the pushrod chamber 
of the deluge valve. 

5.  Open valve N.  Push in the plunger of ball drip valve, 

valve F, to force the ball from its seat, and drain any wa-
ter in the alarm line.  Close valve N.

6.  With the Model B Manual Emergency Station, valve D, 

open, push in and rotate the deluge valve’s external 
reset knob clockwise until you hear a distinct clicking 
noise, indicating that the clapper has closed. 

Note:

 

The reset knob can be rotated only after pressure in the 
pushrod chamber is reduced to atmospheric conditions 
(0 psig). 

7.  Inspect and replace any portion of the sprinkler system 

subjected to fire conditions.  Press the system reset but-
ton on the Potter PFC-4410-RC Panel to place the sys-
tem in the ready condition. 

Note:

 All detection devices 

must be reset before the panel can be reset.

8.  Verify that the following valves are in their respective po-

sitions prior to continuing: 
Valve A – closed, Valve B – open, Valve C – open, Valve 
D – open, Valve E – closed, Valve G – open (if optional 
air compressor is installed), Valve H – closed, Valve 
J – open (if optional Nitrogen Kit is installed), Valve K 
– closed, Valve M – closed, Valve N – closed, Valve 
P – closed (if optional Model B1 Accelerator Kit is in-
stalled).

9.  Open valve A and allow water to fill the deluge valve’s 

pushrod chamber. Close valve D after any trapped air 
has had a chance to escape from the deluge valve’s 
pushrod chamber. Close the main drain, valve B.

10.  Bleed any residual air that may be located between the 

solenoid valve and the Model LP Dry Valve Actuator pip-
ing by energizing the solenoid valve. This is done by 
opening the factory-installed manual pull station that is 
assembled to the exterior of the PrePaK’s 24VDC Termi-
nal Box.   Water should now be flowing freely through 
the solenoid valve as well as the Model LP Dry Valve Ac-
tuator into the drip cup. 

Note:

 This venting of all trapped 

air from this small location in the trim is very important to 
ensure proper system operation and avoidance of false-
ly tripping the valve during an isolated electrical alarm.

Содержание DDX PrePaK

Страница 1: ...visory Pressure Double Interlock Electric Pneumatic Release Contents Page General Description 2 Listings and Approvals 2 Technical Data 4 Installation Requirements 5 System Operation 7 System Reset Procedure 7 Inspection Testing and Maintenance 8 Diagrams Assembly Dimensions 3 Potter PFC 4410 RC Releasing Control Panel 10 Terminal Box Wiring 11 Factory Installed Electrical Devices 12 14 Detector C...

Страница 2: ...urged of its su pervisory air sufficiently enough for the Model LP Dry Valve Actuator to operate This purging is usually caused by the operation of an automatic sprinkler In the event that the system piping is ruptured or a sprin kler head is accidentally opened the Model LP Dry Valve Actuator will open and a low system air pressure alarm will sound The Model DDX Deluge Valve however will not be r...

Страница 3: ...3 Fig 1 ...

Страница 4: ...ote controlled Releasing Control Panels used with these units are Listed Approved and programmed to handle the required sequence of operation necessary to operate the automatic sprinkler system Any unauthorized modification or addition made on site to a factory built Listed Approved unit will void the Listing Approval Such modifications or additions may void the unit s warranty as well Consult Re ...

Страница 5: ...ditional low pressure air test In some cases hydrostatic testing in accordance with the NFPA 13 requirements noted above will result in pressures that exceed the working pressure of the valve and trim kit for the two hour test period The valve and applicable trim kit have been tested approved and listed under these conditions and as such hydrostatic testing in accordance with NFPA 13 is ac ceptabl...

Страница 6: ...y fill the sprinkler system with air the steel enclosure s door should remain open to provide maximum intake air flow to the air compressor The air compressor is connected to a storage tank This tank functions as a reser voir providing make up air to compensate for small inter mittent leaks in the sprinkler system It should be noted that significant leaks may overburden this storage tank thereby c...

Страница 7: ...ion Systems provides minimum mainte nance requirements Systems should be tested operated cleaned and inspected at least annually and parts replaced as required Periodically open the air condensate drain valve see Figs 10 11 or 12 depending on system size beneath the air tank to drain any condensate accumulation Reliable Technical Bulletin 751 provide information for maintaining the Model DDX Delug...

Страница 8: ...l Emergency Station valve D in the OFF position with a nylon tie supplied with the assembly 18 Press the system reset button on the Potter PFC 4410 RC Panel to place the system in the ready condition Note All detection devices must be reset before the panel can be reset Inspection And Testing Refer to Figs 10 11 or 12 depending on system size 1 Water supply Verify that the valve controlling water ...

Страница 9: ...ve B If system contains pressur ized air allow air pressure to come back up to specifica tion Open valve A first and then open the main valve controlling the water supply to the deluge valve 9 SOLENOID VALVE INSPECTIONS TESTS AND MAINTENANCE WARNING THE OWNER IS RESPONSIBLE FOR MAIN TAINING THE FIRE PROTECTION SYSTEM IN PROP ER OPERATING CONDITION ANY SYSTEM MAINTE NANCE OR TESTING THAT INVOLVES P...

Страница 10: ...POWER TBL SYSTEM TBL SUP TBL GROUND FAULT SUP 1 ABORT SUPERVISORY 2 COMMON ALARM ALARM SILENCE STEADY DISCHARGED FLASHING PRE DISCHARGE RUN PROGRAM SET SELECT FUNCTION SCROLL DOWN BUZZER SILENCE SIGNAL SILENCE SYSTEM RESET SCROLL UP BUZZER SILENCE VIEWING ANGLE RED OUTPUT LED STEADY ABORT LAMP TEST 10 ...

Страница 11: ...11 Fig 3 ...

Страница 12: ...12 Fig 4 ...

Страница 13: ...13 Fig 5 ...

Страница 14: ...14 Fig 6 ...

Страница 15: ...15 Fig 7 ...

Страница 16: ...16 Fig 8 ...

Страница 17: ...17 Fig 9 ...

Страница 18: ...18 Fig 10 ...

Страница 19: ...19 ...

Страница 20: ...20 Fig 11 ...

Страница 21: ...21 ...

Страница 22: ...22 Fig 12 ...

Страница 23: ...23 ...

Страница 24: ...Release 3 Waterflow 4 Low Air Supervisory 1 ALARM X X 2 ALARM X 3 SUPERVISORY X X 4 RELEASE X X INPUTS 1 conventional zone 1 manual release zone 1 waterflow zone 1 low air zone 1 supervisory zone OUTPUTS 1 general alarm bell 1 waterflow bell 1 supervisory bell 1 solenoid release circuit OPERATION Activation of either the conventional zone or the manual release will operate the solenoid release cir...

Страница 25: ...25 Fig 13 ...

Страница 26: ... SUPERVISORY X X 4 RELEASE X X INPUTS 2 conventional zones cross zoned 1 waterflow zone 1 low air zone 1 supervisory zone OUTPUTS 1 general alarm bell 1 waterflow bell 1 supervisory bell 1 solenoid release circuit OPERATION Activation of both conventional zones at the same time will operate the solenoid release circuit and thegeneral alarm bell Activation of either conventional zone will operate t...

Страница 27: ...27 Fig 14 ...

Страница 28: ...28 Fig 15 ...

Страница 29: ...29 Fig 16 ...

Страница 30: ...nted in U S A 10 16 P N 9999970383 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association Factory Mutual Research Corporation or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable Products manufactured and distributed by Reliable have been...

Отзывы: