Potter Program #7
Double Interlock Programming Instructions (Single
Hazard - Cross-Zoned, 2 Alarm Zones, 1 Water
fl
ow
Zone and 2 Supervisory Zones)
1. Apply power to panel.
2. Slide the program switch down.
3. Press the FUNCTION button until the display reads
“PASSWORD = 000.”
4. To enter a password, press the SELECT button until
the proper number is displayed above the “^” sym-
bol; then press the SET button to move to the next
digit. After entering the third number the display will
change. (All panels are shipped with a “000” pass-
word).
5. Press the FUNCTION button until the display reads
“PROGRAM ##.” (the second “#” character refers to
the current program number between “0” and “24”).
6. Press the SELECT button until the display reads
“PROGRAM #7.”
7. Press the SET button.
8. The panel is completely programmed except for the
custom banner and zone messages. Slide the pro-
gram switch back up.
POTTER PROGRAM #7
OUTPUTS
ZONES
*Supervisory 2
#1
Conventional
#2
Conventional
#3
Water
fl
ow
#4
Low Air
Supervisory
#1 ALARM
X
X
#2 ALARM
X
#3 SUPERVISORY
X
X
#4 RELEASE
X
X
INPUTS:
2 conventional zones (cross-zoned), 1 waterflow zone, 1 low air zone, 1 supervisory zone.
OUTPUTS:
1 general alarm bell, 1 waterflow bell, 1 supervisory bell, 1 solenoid release circuit.
OPERATION: Activation of both conventional zones at the same time will operate the solenoid release circuit and
thegeneral alarm bell.Activation of either conventional zone will operate the general alarm bell.Acti-
vation of the waterflow zone will operate the waterflow bell.Activation of either the low air zone or the
supervisory zone will operate the supervisory bell.When either Zone #1 or #2 is in alarm, Output #1
(general alarm) will operate.When Zones #1 and #2 are in alarm at the same time, Output #4 (solenoid
release) and Output #1(general alarm) will operate.When Zone #3 is in alarm, Output #2 (waterflow
bell) will operate.When either Zone #4 or the supervisory zone is activated, Output #3 (supervisory
bell) will operate.
* The Butter
fl
y valve in the PrePaK assembly is connected to Supervisory 2 input of the Potter PFC-4410RC
Releasing/Control panel
Refer to the “Installation, Operation and Instruction Manual” for the PFC-4410-RC Releas-
ing Control Panel for Additional Information.
Содержание DDX PrePaK
Страница 3: ...3 Fig 1 ...
Страница 11: ...11 Fig 3 ...
Страница 12: ...12 Fig 4 ...
Страница 13: ...13 Fig 5 ...
Страница 14: ...14 Fig 6 ...
Страница 15: ...15 Fig 7 ...
Страница 16: ...16 Fig 8 ...
Страница 17: ...17 Fig 9 ...
Страница 18: ...18 Fig 10 ...
Страница 19: ...19 ...
Страница 20: ...20 Fig 11 ...
Страница 21: ...21 ...
Страница 22: ...22 Fig 12 ...
Страница 23: ...23 ...
Страница 25: ...25 Fig 13 ...
Страница 27: ...27 Fig 14 ...
Страница 28: ...28 Fig 15 ...
Страница 29: ...29 Fig 16 ...