background image

2.

General Description 

The Reliable Type F Model DDX  PrePaK (Sizes 2” (50 

mm), 2½” (65 mm), 3” (80 mm), 4” (100 mm), 6” (150 mm) 
and 8” (200 mm) is a completely self-contained, supervised 
preaction system that can be readily installed within a floor 
space of less than 7.5  square feet ( 0.70 square meters) 
(not including door swing). Refer to Fig. 1 for cabinet dimen-
sions. Installation of the PrePaK (not including exterior devic-
es, i.e., detectors and alarm bells), requires just three piping 
connections.  These connections are the water supply, the 
sprinkler system and the drain.  Reference locations of these 
piping connections are shown in Fig. 1. Also, two 120 / 220 
VAC electrical power connections are required. 

Note:

 The 

Type F Model DDX PrePaK is available with its air compres-
sor and releasing/control panel wired for a 120 VAC / 60Hz 
or for a 220 VAC / 50 Hz power supply.

Figures 15, 16, and 17 in this Bulletin identify standard and 

optional equipment available in Reliable DDX PrePak, Type 
F, Preaction Systems.

The Reliable Type F PrePaK utilizes an optional Potter 

Model PFC-4410-RC Releasing/Control Panel.  This fully 
programmable, microprocessor-based releasing panel is 
Underwriters Laboratories, Inc. Listed and is in compliance 
with NFPA 13 and NFPA 72. Because the PFC-4410-RC is 
totally zone and output programmable, the Reliable Type 
F PrePaK can be utilized in many different preaction appli-
cations without having to rewire any of the factory installed 
devices. Once the previously described connections are 
completed, the 24 VDC detectors, output devices, and relay 
contacts may be connected to achieve the desired system 
implementation. 

The Type F PrePaK is designed specifically for double 

interlock applications. Reliable double interlock preaction 
systems are designed for water sensitive areas that require 
protection from inadvertent water flow into the sprinkler sys-
tem piping. 

The major benefits of a double interlock preaction System, 

when compared with a wet pipe system, are as follows:

A.  A fire alarm sounds prior to the flow of water from 

a sprinkler, which may enable extinguishment of 
the fire by handheld means before the operation 
of any sprinkler occurs. 

B.  An annunciator signals whenever the integrity of 

piping or sprinklers is accidentally or intentionally 
disturbed; however, no water flow occurs at that 
time. 

C.  Detection and notification of a fire condition are 

provided by fire detectors, without the delay as-
sociated with water delivery time in the event of 
a fire. Note that with a wet pipe system, the fire 
alarm is delayed until after water has begun flow-
ing from and operated sprinkler.

To flow water into the system piping of a Type F double 

interlock preaction system, two events must take place:
1)  A fire detection device must detect heat and/or 

smoke thereby causing the releasing/control panel 
to energize the normally-closed solenoid valve.

2)  The sprinkler system piping must be purged of its su-

pervisory air sufficiently enough for the Model LP Dry 
Valve Actuator to operate.  This purging is usually 

caused by the operation of an automatic sprinkler.  

In the event that the system piping is ruptured, or a sprin-

kler head is accidentally opened, the Model LP Dry Valve 
Actuator will open and a low system air pressure alarm will 
sound. The Model DDX Deluge Valve, however, will not be 
released to flow water since the solenoid valve still remains 
closed. The same end result would occur if a fire detection 
device was falsely operated. The releasing/control panel will 
activate an alarm, but the Model DDX Deluge Valve will not 
flow water due to the fact that the Model LP Dry Valve Actua-
tor still remains closed. 

When using the Reliable Type F PrePaK, in double inter-

lock applications, the sprinkler system is pressurized (su-
pervised) with air provided by the optional factory-installed 
air compressor (or on-site Nitrogen supply) and is monitored 
by a system pressure switch.  If Nitrogen is used as the su-
pervisory gas, an optional Nitrogen Kit is available.  This kit 
contains a regulator and an additional pressure switch that is 
used to monitor any low pressure conditions that may arise 
due to having a limited Nitrogen supply.  Also, a “Low Nitro-
gen” LED is mounted onto the door of the releasing/control 
panel for visual confirmation.  When using Nitrogen, the pri-
mary supervisory gas should be the Nitrogen (not standard 
air) due to dryness concerns (i.e. freezing conditions).  The 
optional factory-installed air compressor should be utilized 
merely for make-up air until the Nitrogen supply can be re-
plenished.  

Note:

 This compressor supplied make-up air is 

not to be considered as dry air and may create ice plugs or 
freezing conditions in the sprinkler system piping.

A Model B Hydraulic Manual Emergency Releasing station 

is standard equipment in the Type F PrePaK. It consists of an 
aluminum nameplate mechanically attached to a ball valve. 
The valve handle in its OFF position is guarded against ac-
cidental turning to the ON position (and system discharge) 
by a nylon cable tie provided with the PrePaK assembly. 
The cable tie is designed to allow, in case of an emergency, 
forceful turning of the valve handle to the ON position. 

Listings and Approvals 

1.  Underwriters Laboratories, Inc. Listed and Certified 

for Canada* (cULus) as an assembled unit in the 
“Special System Water Control Valves Assembled 
Units” category, (VKYL).
*The system’s pressure switches must be specified 
to meet Canadian requirements. This option is avail-
able.

2.  Factory Mutual Approved as a Refrigerated Area 

Sprinkler System for use in refrigerated rooms or 
buildings. Refrigerated area sprinkler systems are 
FM Approved as complete systems. Systems are FM 
approved for use with thermal detectors and Class A 
detector wiring only. 

3.  Approved for use in New York City based on UL List-

ing.

Note:

 Although PrePak units are UL Listed, custom built 

units are sometimes supplied upon request. The compo-
nents within these special units maintain their individual 
Listings/Approvals, whereas the assembled units do not.

Содержание DDX PrePaK

Страница 1: ...visory Pressure Double Interlock Electric Pneumatic Release Contents Page General Description 2 Listings and Approvals 2 Technical Data 4 Installation Requirements 5 System Operation 7 System Reset Procedure 7 Inspection Testing and Maintenance 8 Diagrams Assembly Dimensions 3 Potter PFC 4410 RC Releasing Control Panel 10 Terminal Box Wiring 11 Factory Installed Electrical Devices 12 14 Detector C...

Страница 2: ...urged of its su pervisory air sufficiently enough for the Model LP Dry Valve Actuator to operate This purging is usually caused by the operation of an automatic sprinkler In the event that the system piping is ruptured or a sprin kler head is accidentally opened the Model LP Dry Valve Actuator will open and a low system air pressure alarm will sound The Model DDX Deluge Valve however will not be r...

Страница 3: ...3 Fig 1 ...

Страница 4: ...ote controlled Releasing Control Panels used with these units are Listed Approved and programmed to handle the required sequence of operation necessary to operate the automatic sprinkler system Any unauthorized modification or addition made on site to a factory built Listed Approved unit will void the Listing Approval Such modifications or additions may void the unit s warranty as well Consult Re ...

Страница 5: ...ditional low pressure air test In some cases hydrostatic testing in accordance with the NFPA 13 requirements noted above will result in pressures that exceed the working pressure of the valve and trim kit for the two hour test period The valve and applicable trim kit have been tested approved and listed under these conditions and as such hydrostatic testing in accordance with NFPA 13 is ac ceptabl...

Страница 6: ...y fill the sprinkler system with air the steel enclosure s door should remain open to provide maximum intake air flow to the air compressor The air compressor is connected to a storage tank This tank functions as a reser voir providing make up air to compensate for small inter mittent leaks in the sprinkler system It should be noted that significant leaks may overburden this storage tank thereby c...

Страница 7: ...ion Systems provides minimum mainte nance requirements Systems should be tested operated cleaned and inspected at least annually and parts replaced as required Periodically open the air condensate drain valve see Figs 10 11 or 12 depending on system size beneath the air tank to drain any condensate accumulation Reliable Technical Bulletin 751 provide information for maintaining the Model DDX Delug...

Страница 8: ...l Emergency Station valve D in the OFF position with a nylon tie supplied with the assembly 18 Press the system reset button on the Potter PFC 4410 RC Panel to place the system in the ready condition Note All detection devices must be reset before the panel can be reset Inspection And Testing Refer to Figs 10 11 or 12 depending on system size 1 Water supply Verify that the valve controlling water ...

Страница 9: ...ve B If system contains pressur ized air allow air pressure to come back up to specifica tion Open valve A first and then open the main valve controlling the water supply to the deluge valve 9 SOLENOID VALVE INSPECTIONS TESTS AND MAINTENANCE WARNING THE OWNER IS RESPONSIBLE FOR MAIN TAINING THE FIRE PROTECTION SYSTEM IN PROP ER OPERATING CONDITION ANY SYSTEM MAINTE NANCE OR TESTING THAT INVOLVES P...

Страница 10: ...POWER TBL SYSTEM TBL SUP TBL GROUND FAULT SUP 1 ABORT SUPERVISORY 2 COMMON ALARM ALARM SILENCE STEADY DISCHARGED FLASHING PRE DISCHARGE RUN PROGRAM SET SELECT FUNCTION SCROLL DOWN BUZZER SILENCE SIGNAL SILENCE SYSTEM RESET SCROLL UP BUZZER SILENCE VIEWING ANGLE RED OUTPUT LED STEADY ABORT LAMP TEST 10 ...

Страница 11: ...11 Fig 3 ...

Страница 12: ...12 Fig 4 ...

Страница 13: ...13 Fig 5 ...

Страница 14: ...14 Fig 6 ...

Страница 15: ...15 Fig 7 ...

Страница 16: ...16 Fig 8 ...

Страница 17: ...17 Fig 9 ...

Страница 18: ...18 Fig 10 ...

Страница 19: ...19 ...

Страница 20: ...20 Fig 11 ...

Страница 21: ...21 ...

Страница 22: ...22 Fig 12 ...

Страница 23: ...23 ...

Страница 24: ...Release 3 Waterflow 4 Low Air Supervisory 1 ALARM X X 2 ALARM X 3 SUPERVISORY X X 4 RELEASE X X INPUTS 1 conventional zone 1 manual release zone 1 waterflow zone 1 low air zone 1 supervisory zone OUTPUTS 1 general alarm bell 1 waterflow bell 1 supervisory bell 1 solenoid release circuit OPERATION Activation of either the conventional zone or the manual release will operate the solenoid release cir...

Страница 25: ...25 Fig 13 ...

Страница 26: ... SUPERVISORY X X 4 RELEASE X X INPUTS 2 conventional zones cross zoned 1 waterflow zone 1 low air zone 1 supervisory zone OUTPUTS 1 general alarm bell 1 waterflow bell 1 supervisory bell 1 solenoid release circuit OPERATION Activation of both conventional zones at the same time will operate the solenoid release circuit and thegeneral alarm bell Activation of either conventional zone will operate t...

Страница 27: ...27 Fig 14 ...

Страница 28: ...28 Fig 15 ...

Страница 29: ...29 Fig 16 ...

Страница 30: ...nted in U S A 10 16 P N 9999970383 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association Factory Mutual Research Corporation or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable Products manufactured and distributed by Reliable have been...

Отзывы: