Installation 

Reliable Attic sprinklers are intended to be installed in ac-
cordance with NFPA 13 and the requirements of other ap-
plicable authorities having jurisdiction. In addition, Reliable 
Attic sprinklers must also be installed in accordance with 
the requirements contained in this Bulletin. 

Installation Reliable Attic Sprinklers only in the orientation 
specified in Figure 23. 

 

Installation Orientation

 

Figure 23 

 

jçÇÉä=aa=pÉêáÉë=

 

Install Model DD Series sprinklers with the deflector 
parallel to the floor and arrows on deflector pointing 
down the roof slope in both directions. 

=

=

jçÇÉä=apRS=

 

Install Model DS56 sprinklers with the frame arms per-
pendicular to the roof deck and the arrow on the de-
flector pointing down the roof slope. 

 

=

jçÇÉä=dmRS=

 

Install Model GP56 sprinklers with the deflector parallel 
to the roof deck and the arrow on the deflector pointing 
down the roof slope. 

 

Follow installation requirements specified in the individual 
sprinkler data sheets in this bulletin. Figure 24 illustrates 
select installation criteria for each sprinkler. 

 

Installation Dimensions

 

Figure 24 

 

jçÇÉä=aa=pÉêáÉë=

 

=

=

jçÇÉä=apRS=

 

=

jçÇÉä=dmRS=

 

 

Where Reliable Attic Sprinklers are installed on wet-pipe 
sprinkler systems with CPVC pipe, the CPVC pipe must be 
protection in accordance with the pipe manufacturer’s in-
stallation instruction as well as the requirements in Figure 
25.  

 

 

Содержание DD56-27

Страница 1: ...8 12 Re liable Attic Sprinklers are upright sprinklers listed for use on wet pipe or dry pipe sprinkler systems All Reliable Attic sprinklers use a 212 F 100 C temperature rated fusible link operatin...

Страница 2: ...slope measured parallel to the roof deck Horizontal Distance from Face of Truss Min 6 inches 150 mm Vertical Distance of Deflector Above Scis sor Truss Min 18 inches 450 mm Horizontal Distance from Ce...

Страница 3: ...he roof slope measured parallel to the roof deck Horizontal Distance from Face of Truss Min 6 inches 150 mm Vertical Distance of Deflector Above Scis sor Truss Min 18 inches 450 mm Horizontal Distance...

Страница 4: ...mm Horizontal Distance from Centerline of Ridge Max 6 inches 150 mm Vertical Distance of Deflector Below Peak Ridge or Deck Min 17 inches 430 mm Max 21 inches 530 mm Material Specifications Thermal S...

Страница 5: ...hes 450 mm Horizontal Distance from Centerline of Ridge Max 6 inches 150 mm Vertical Distance of Deflector Below Peak Ridge or Deck Min 17 inches 430 mm Max 21 inches 530 mm Material Specifications Th...

Страница 6: ...mm Max 38 inches 970 mm Vertical Distance of Top of Deflector Above Bottom of Draft Curtain Min 8 inches 200 mm Model DS56 sprinklers may be installed back to back on opposite sides of a ridge where a...

Страница 7: ...t 3 0 m across roof slope measured along the floor Max 15 ft 4 6 m up and down roof slope measured along the floor Min 6 ft 1 8 m measured parallel to the roof deck Distance from Top of Deflector to R...

Страница 8: ...vidual sprinkler data sheets in this Bulletin Example sprinkler layouts are illustrated in Figures 7 through 21 Design criteria for Reliable Attic Sprinklers must be in accordance with Table H based o...

Страница 9: ...are in the design area Calculate design area per NFPA 13 and include all sprinkler types that are in the design area DD Series at ridge with DD Series in dormer Fig 15 5 at ridge and up to 2 in dorme...

Страница 10: ...Bulletin 056 Page 10 of 24 December 2016 www reliablesprinkler com Model DD Series Sprinkler Example Layout Not to Scale Figure 7 Model DS56 Sprinkler Example Layout Not to Scale Figure 8...

Страница 11: ...blesprinkler com Model DD Series Sprinklers at Ridge with Model DS56 Sprinklers Beyond Obstruction Example Layout Not to Scale Figure 9 Model DS56 Sprinklers at Ridge with Model DS56 Sprinklers Beyond...

Страница 12: ...lesprinkler com Model DD Series Sprinklers at Ridge with Model GP56 Sprinklers Beyond Obstruction Example Layout Not to Scale Figure 11 Model DS56 Sprinklers at Ridge with Model GP56 Sprinklers Beyond...

Страница 13: ...Bulletin 056 Page 13 of 24 December 2016 www reliablesprinkler com Model DD Series Sprinklers at Ridge with Model GP56 Sprinklers at Dormer or Cross Example Layout Not to Scale Figure 13...

Страница 14: ...Bulletin 056 Page 14 of 24 December 2016 www reliablesprinkler com Model DD Series Sprinklers at Ridge with Standard Spray Sprinklers at Dormer or Cross Example Layout Not to Scale Figure 14...

Страница 15: ...eliablesprinkler com Model DD Series Sprinklers at Ridge with Model DD Series Sprinklers in Dormers Example Layout Not to Scale Figure 15 Model DD Series Sprinklers at Ridge with Model GP56 Sprinklers...

Страница 16: ...www reliablesprinkler com Model DS56 Sprinklers at Ridge with Model GP56 Sprinklers at Eave Example Layout Not to Scale Figure 17 Model DD Series Sprinklers at Ridge with DS56 Sprinklers at Hip or El...

Страница 17: ...reliablesprinkler com Model DS56 Sprinklers at Ridge with DS56 Sprinklers at Hip or Ell Example Layout Not to Scale Figure 19 Model DD Series Sprinklers at Ridge with Standard Spray Sprinklers at Hip...

Страница 18: ...Bulletin 056 Page 18 of 24 December 2016 www reliablesprinkler com Model DS56 Sprinklers at Ridge with Standard Spray Sprinklers at Hip or Ell Example Layout Not to Scale Figure 21...

Страница 19: ...ot provided between the top of the obstruction and the roof deck Additional sprinklers not required below horizontal obstruction 4 0 1 2 m or less in width Additional sprinklers required below horizon...

Страница 20: ...pace less than 1 0 300 mm from roof deck Additional sprinkler not required below stiffeners meeting all of the following criteria 1 min 1 0 300 mm below Reliable Attic sprin klers 2 max 7 1 2 190 mm w...

Страница 21: ...rs with the deflector parallel to the floor and arrows on deflector pointing down the roof slope in both directions j apRS Install Model DS56 sprinklers with the frame arms per pendicular to the roof...

Страница 22: ...ig Max 1 0 300 mm CPVCRiser Locate a sprinkler within 1 0 300 mm horizontally of CPVC risers Max 3 0 900 mm Min 1 0 300 mm Min 1 0 300 mm Min 6 150 mm Joist Noncombustible insulation e g fiberglass An...

Страница 23: ...rig may extend above the insulation to supply Model GP56 sprinklers Model GP56 sprinkler Joist Noncombustible insulation e g fiberglass Min 6 150 mm Max 10 0 3 m Model GP56 sprinkler Joist Noncombusti...

Страница 24: ...j dmRS j apRS t c j apRS Maintenance Reliable Attic sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25 as well as the requirements of any Authorities Having...

Отзывы: