Parameter 76
Activation lock time closing time 1
0 – normal mode
1 – closing time mode
Parameter 77
Activation lock time closing time 2
0 – normal mode
1 – closing time mode
Parameter 78
Activation lock time closing time 3
0 – normal mode
1 – closing time mode
Example : The motion sensor Outside is locked from 6 pm until 8 am
==>> 1. Start 1: (P70) = 06:00:00 pm, 2. End 1: (P71) = 08:00:00 am, 3. Closing time mode: (76) = 1
Parameter 80:
New safety check interval, internal counters are reset
Parameter 81:
Maintenance interval in months
Parameter 82:
Accumulator operation in case of power failure
0 – normal operation for approx. one hour at 50 cycles
1 – door OPENS in case of power failure and remains in this position until power returns
2 – all holding functions are deactivated; the door
always
closes immediately after an opening run
Parameter 83:
Pull and Go Function
0 – door
can
not
be operated manually. The door is kept closed by motor operation and an acoustic
signal warns the user in case of manual opening.
1 – door can be manually operated. The door is opened by motor operation. The CompletelyOpen1
function is carried out.
2 – door can be manually operated. The door is opened by motor operation. The PartlyOpen function
is carried out.
3 – door can be manually operated. The door is opened by motor operation. The PermanentlyOpen
function is carried out..
4 – door can be manually operated. The door opens automatically until the set opening width (para-
meter 15) is reached. The PermanentlyPartlyOpen function is carried out.
Parameter 84:
Safety elements:
0 – deactivated
1 – active (safeguarding main closure-edge)
2 – active (safeguarding main and side closure-edge)
Parameter 85:
Number of safety elements:
1 – Operation with one safety element
2 – Operation with two safety elements
Parameter 86:
Self-monitoring function for safety element 1:
0 - deactivated
1 – active
Parameter 87:
Self-monitoring function for safety element 2:
0 – deactivated
1 – active
Parameter 88
Key lock time start – time when all operating elements are locked.
Parameter 89
Key lock time end – time when all operating elements are reactivated.
Example : The operating elements are locked from 4 pm until 6 am
==>> 1. Start: (P88) = 04:00:00 pm,
2. End: (P89) = 06:00:00 am
Parameter 91
Erection right / left:
0 – right
1 – left
Parameter 95
Enable program modules (5-digit);
1 – motion sensor
2 – safety elements
3 – interlocking function
4 – self-monitoring function for safety elements
5 – battery / accumulator operation (emergency power)
V
EN
– 13 –
Содержание s4000
Страница 1: ...Operating Manual Sliding Door Drive Engine V EN ...
Страница 16: ...11 0 Terminal connection diagrams 11 1 Wiring diagram maximum total cable length 10m 16 ...
Страница 17: ...11 2 Terminal assignment V EN 17 ...
Страница 18: ...12 0 Dimensions 12 1 Sectional drawing one wing drive 18 ...
Страница 19: ...12 2 Sectional drawing telescopic and two wing drive V EN 19 ...