Adjust Menu
(5 of 6)
Cooling Cycle
Determines the number of cycles per hour for the cooling equipment.
This item is only available in the Installer access level.
Auto, 2 to 12
Cooling Interlock
Selects the time delay between the heating and cooling relays.
This item is only available in the Installer access level.
10 to 180 min.
Cooling Minimum On
Sets the minimum on time of the cooling contact.
This is to prevent short cycling. This item is only available in the Installer
access level.
0:30 to 5:00 min.
Cooling Minimum Off
Sets the minimum off time of the cooling contact. This is to prevent short
cycling. This item is only available in the Installer access level.
0:30 to 10:00 min.
Early Start
Selects whether or not the Early Start (anticipation) feature is active. This
item is only available in the Installer access level.
OFF, ON