uREG User Manual
31
7.4.
CT-0 MODULE (SLOT 1)
In the
CT-0
module (
c
urrent
t
ransformers module), there are 3 current transformers for
direct measurements of phase currents within the range (In: 5 A, 1 A) = 0 ÷ 192 A.
Phase current input circuits
Rated current In
5 A or 1A
Measurement range
0 ÷ 192 A
Measurement error within ranges:
0.05 ÷ 0.35 A <5 %
0.35 ÷ 50 A <1.5 %
50 ÷ 192 A
<5 %
Power input at I=In
<0.5 VA
Rated frequency fn
50 Hz
Continuous current-carrying capacity
3 * In
1-second thermal endurance
100 * In
Dynamic withstand value
250 * In
Terminals of the
CT-0
module are grouped into three Wieland-Wiecon 4-pin symmetric
ports (screwed, type 8313S/4 WF OB; pitch: 7.50 mm, max continuous capacity 12 A, 400 V,
cable cross-section 2.5 mm2). Each pin k, l on the transformers is connected to two connector
terminals.
Fig. 7.4. Terminals of the CT-0 module.
The
CT-0
module is required for fulfillment of the following protective criteria, e.g.:
Overcurrent I>
Tripped overcurrent I>T
Overcurrent dependent I>
Undercurrent
I0> (vector sum of currents Ir, Is, It)
Current asymmetry aI>
I>tilt (polygonal characteristic curve)
I1>, I2>, I3> for MSK.
Содержание uREG
Страница 2: ...uREG User Manual 2 LogCZIP and uREG are registered trademarks of REGULUS Zygmunt Liszy ski...
Страница 4: ...uREG User Manual 4...
Страница 8: ...uREG User Manual 8 21 GUIDELINES FOR THE PURCHASER 107 22 WARRANTY 107...
Страница 21: ...uREG User Manual 21 Drilling diagram for 10 slot enclosure installation...
Страница 22: ...uREG User Manual 22 Drilling diagram for 14 slot enclosure installation...