English 23
Para-
meter
Function
Parameter description
Setting range
Default
value
S2.19
INITIAL VALVE
MOVEMENT FROM
OPEN POSITION
(SECONDS)
Setting of initial valve movement duration when moving
from open position. With this setting the valve is moved
to its control range
(with immediate response)
at
startup of system.
0 ÷ 30 seconds
15
S2.20
INITIAL VALVE
MOVEMENT FROM
CLOSED POSITION
(SECONDS)
Setting of initial valve movement duration when moving
from closed position. With this setting the valve is
moved to its control range
(with immediate response)
at
startup of system.
0 ÷ 30 seconds
15
Parameters for heat source:
Para-
meter
Function
Parameter description
Setting range
Default
value
S3.1
SYSTEM PROTEC-
TION IN HEATING
MODE - SENSOR
T2
Setting of
actuator
response
in case if T2 sensor is
installed. If T2 temperature is lower
than
paremeter
S3.2, the
actuator
fully closes the valve. If T2 is higher
than
parameter
S3.3, the
actuator
fully opens the valve.
0 - Sensor T2 is not used for system protection.
1- Only minimal temperature is respected for system
protection (parameter S3.2).
2- Only maximal temperature is respected for system
protection (parameter S3.3).
3- Minimal and maximal temperature is respected for
system protection (parameter S3.2 in S3.3).
0- WITHOUT
1- TMIN
2- TMAX
3- TMIN IN TMAX
0
S3.2
MIN. SYSTEM
TEMPERATURE IN
HEATING MODE
Setting of minimal temperature at which the
actuator
fully
closes the valve.
10
÷
70 °C
55 °C
S3.3
MAX. SYSTEM
TEMPERATURE IN
HEATING MODE
Setting of maximal temperature at which the
actuator
fully
opens the valve.
30
÷
95 °C
90 °C
S3.4
SYSTEM PROTEC-
TION IN COOLING
MODE - SENSOR
T2
Setting of
actuator
response
in case if T2 sensor is
installed. If T2 temperature is lower
than
parameter
S3.5, the
actuator
fully closes the valve. If T2 is higher
than
parameter
S3.6, the
actuator
fully opens the valve.
0 - Sensor T2 is not used for system protection.
1- Only minimal temperature is respected for system
protection (parameter S3.5).
2- Only maximal temperature is respected for system
protection (parameter S3.6).
3- Minimal and maximal temperature is respected for
system protection (parameter S3.5 in S3.6).
0- WITHOUT
1- TMIN
2- TMAX
3- TMIN IN TMAX
0
S3.5
MIN.SYSTEM
TEMPERATURE IN
COOLING MODE
Setting of minimal temperature at which the
actuator
fully
closes the valve.
1
0 ÷
3
0 °C
15
S3.6
MAX. SYSTEM
TEMPERATURE IN
COOLING MODE
Setting of maximal temperature at which the
actuator
fully
opens the valve.
2
0 ÷
4
0 °C
30
Содержание ACC30
Страница 2: ......
Страница 29: ...DIAGRAM 02 DIAGRAM 03 English 29...
Страница 31: ...DIAGRAM 06 DIAGRAM 05 English 31...
Страница 34: ...34 English...
Страница 64: ...SCH MA02 230 V AC 50 Hz b r ra SCH MA03 230 V AC 50 Hz b r oo 64 esky...
Страница 66: ...SCH MAOS 230 V AC 50 Hz c r 1 f SCH MA06 _ T2 T1 i 230 V AC 50 Hz c l l8J1 66 esky...
Страница 67: ......