22 English
Parameters for
heating
circuit:
Para-
meter
Function
Parameter description
Setting range
Default
value
S2.1
MIN. SETPOINT
TEMPERATURE IN
HEATING MODE
Setting of minimal allowed setpoint temperature in
heating mode. Setpoint temperature cannot be adjusted
lower
than
this parameter.
5 ÷ 70 °C
50 °C
S2.2
MAX. SETPOINT
TEMPERATURE IN
HEATING MODE
Setting of maximal allowed setpoint temperature in
heating mode. Setpoint temperature cannot be adjusted
higher
than
this parameter.
10 ÷ 95 °C
70 °C
S2.3
MIN. SETPOINT
TEMPERATURE IN
COOLING MODE
Setting of minimal allowed setpoint temperature in
cooling mode. Setpoint temperature cannot be adjusted
lower
than
this parameter.
10 ÷ 25 °C
15 °C
S2.4
MAX. SETPOINT
TEMPERATURE IN
COOLING MODE
Setting of maximal allowed setpoint temperature in
cooling mode. Setpoint temperature cannot be adjusted
higher
than
this parameter.
15 ÷ 35 °C
30 °C
S2.7
BACKLASH OF
MIXING VALVE
Setting of mixing valve running time to compensate the
backlash of actuator and mixing valve assembly,
which
occurs by change of rotation direction.
0 ÷ 5 s
1
S2.8
MIXING VALVE P -
CONSTANT
Setting of mixing valve position correction intensity.
Smaller value means shorter movements, higher value
means longer movements,
0,5 ÷ 2,0
1
S2.9
MIXING VALVE I -
CONSTANT
Setting of mixing valve control frequency - how often
mixing valve position is being controlled. Smaller value
means low frequency, higher value means higher
frequency.
0,4 ÷ 2,5
1
S2.10
MIXING VALVE D -
CONSTANT
Sensitivity of mixing valve for
heating circuit
temperature
changes. Smaller value means low sensitivity, higher
value means high sensitivity.
0,4 ÷ 2,5
1
S2.13
BOILER CIRCULATI-
ON PUMP - TIME OF
BOILER TEMPERA-
TURE INCREASE
(SECONDS)
This function is used in
control
of return in solid fuel
boiler. In the set time, the
actuator
determines
temperatu
re increase of the boiler by 2
°C. If an increase
in the boiler
is determined, the
actuator
activates the
circulation
pump.
30 ÷ 900
seconds
300
S2.14
BOILER CIRCU-
LATION PUMP
OPERATION
1. STANDARD
2. PERMANENT
The setting informs about the operation of the
circulation
pump of the boiler:
1-
STANDARD
means
that the pump is operating accor-
ding to the minimum set temperature of the system, and
when the difference between the boiler and return l
line is
exceeded.
2-
PERMANENT means that the pump is operating
continuously when boiler temperature is higher than the
set minimum set temperature of the boiler. This mode is
used for pellet boilers when there is no sensor available
in the thermal
store.
1- STANDARD
2- PERMANENT
1
S2.1
5
BOILER CIRCU-
LATION PUMP -
SWITCH-OFF DELAY
(SECONDS)
Setting of delayed circulation pump switch-off when there
is no requirement for heating.
30 ÷ 900 seconds
300
S2.16
BOILER CIRCULA-
TION PUMP
-
SWITCH
- OFF
DIFFERENCE
T2-T1 (°C)
This setting determines the difference between sensors
T2 and T1 which
switches off
circulation
pump of the
boiler.
2.0 ÷ 8.0 °C
3.0
Содержание ACC30
Страница 2: ......
Страница 29: ...DIAGRAM 02 DIAGRAM 03 English 29...
Страница 31: ...DIAGRAM 06 DIAGRAM 05 English 31...
Страница 34: ...34 English...
Страница 64: ...SCH MA02 230 V AC 50 Hz b r ra SCH MA03 230 V AC 50 Hz b r oo 64 esky...
Страница 66: ...SCH MAOS 230 V AC 50 Hz c r 1 f SCH MA06 _ T2 T1 i 230 V AC 50 Hz c l l8J1 66 esky...
Страница 67: ......