![Regulus 18239 Скачать руководство пользователя страница 62](http://html1.mh-extra.com/html/regulus/18239/18239_instruction-manual_1434392062.webp)
62
It is obvious from the picture that the Delay function can delay signal from thermostat and diff. thermostat
functions, the Overrun function can hold disconnection (switching off) from thermostat, diff. thermostat
and delay functions. The Timer function is superior over all the preceding functions.
Basic settings
UNI function active (on/off)
Switching on the universal function.
sens. 1
........................ Selection of sensor 1 for universal function.
sens. 2
........................ Selection of sensor 2 for universal function.
Thermostat 1, Thermostat 2
Thermostat 1 is related to sensor 1, thermostat 2 to sensor 2.
demand (°C)
...............
Thermostat 1 (2) demand (set) temperature
d. ON/OFF (°C)
........... Thermostat 1 (2) switch-on and switch-off temperature difference.
Thermostat 1 (2) is used for cooling (yes/no)
.................................... If the
yes
option (cooling mode) is selected then the Thermostat 1 (2) function will
be switched on when the temperature reaches demand (+ switch-on difference)
and will be switched off again if the temperature drops below demand (- switch-off
difference). If the no option (heating mode) is selected then the Thermostat 1 (2)
function will be switched on when the temperature drops below demand (- switch-
on difference) and will be switched off again if the temperature reaches demand
(+ switch-off difference).
Call for heat from Thermostat 1 (2) (on/off)
.................................... Switch-off temperature for Thermostat 1 (2) will be taken over as the desired
temperature for heat sources. Valid only if Thermostat 1 (2) is set in “heating”
mode. When
Timer
function is also On, the request will be taken over during active
time period only.
Differential thermostat
Differential thermostat between sensors 1 and 2.
diff. on (°C)
.................
Switch-on difference between temperatures.
diff. off (°C)
.................
Switch-off difference between temperatures.
Delay
Output switch-on delay function.
period (minutes)
........
Delay time in case when all the preceding functions are switched on.
Overrun
Output switch-off delay function.
overrun (minutes)
......
Output overrun time after the preceding functions are switched off.