56
external blocking input (sensor list)
.................................... Setting the terminal to which an input used for blocking the heat pump externally
can be connected. It is possible to select any free sensor input to IR or inputs from
the add-on digital input module (if present).
Heat pump 1 settings
It is necessary to use the web interface to set other heat pumps in the cascade.
State (off/on)
.............. Switching off/on the specific heat pump.
Max.flow. t. (°C)
......... Max. heat pump flow temperature. When this temperature is exceeded, the heat
pump is switched off. The heat pump will also switch off when the flow temperature
exceeds a certain value, established by the manufacturer depending on the heat
pump type (see the heat pump service manual).
Max.return t. (°C)
....... Max. heat pump return temperature. When this temperature is exceeded, the heat
pump is switched off. The heat pump will also switch off when the return
temperature exceeds a certain value, established by the manufacturer depending
on the heat pump type (see the heat pump service manual).
Min.outd.t. (°C)
.......... Min. outdoor temperature for heat pump operation. When the temperature drops
below this value, the heat pump is switched off. The heat pump will also switch off
when the outdoor temperature drops below a certain value, established by the
manufacturer depending on the heat pump type (see the heat pump service
manual).
Max.outd.t (°C)
.......... Max. outdoor temperature. When the outdoor temperature exceeds this value, the
heat pump is switched off.
Restart time (min)
...... Min. delay between two heat pump starts.
Min.run.time (min)
.................................... Minimum time of HP operation. It is activated either after compressor start, or after
DHW heating is finished (if the heating circuit demand is higher than 10°C), or
after a defrosting cycle is finished.
5.6.
Heat pump 1 operating data
In this menu, detailed information about heat pump number 1 is displayed. For data on other pumps in
the cascade, it is necessary to use the web interface.
Flow temp. (°C)
.......... HP flow temperature
Return t. (°C)
.............. HP return temperature
Hot gas (°C)
................ HP compressor hot gas temp.
Flow temp. (°C)
.......... HP flow temperature
Cond.temp. (°C)
......... HP condensing temp.
Cond.press. (bar)
...... HP condensation pressure