52
Solar (active/off)
........ Switching on solar zone.
sol.cons. 1,2 (active/off)
.................................... Switching on separate tanks in solar circuit.
Solar consumer 1, 2
sensor (sensor list)
... Choice of temperature sensor in a solar tank.
diff. on (°C)
................. Difference to switch on heating from solar circuit. Difference between solar
collector and temperature sensor set in parameter
sensor
.
diff. off (°C)
................. Difference to switch off heating from solar circuit.
desired t. (°C)
............. The desired temperature. Under the normal solar circuit mode, the tank is heated
up to this temperature. As soon as all switched-on tanks are heated up to the
demand temperature
, the Controller continues heating up to max. temperature.
max. temp. (°C)
.......... Max. temperature. Maximum temperature the solar tank is heated to in normal
mode (the function of solar collectors cooling is turned off).
bore regen. (yes/no)
.................................... Set if this tank is used for ground-source heat pump’s deep bore regeneration.
Selecting “yes” will start a ground loop circulation pump together with the given
consumer.
Oscillating loading
t. increase (°C)
........... Temperature increase during oscillating loading. If a solar tank of a higher priority
cannot be loaded, the Controller waits for the time set in parameter
idle
time
. If the
temperature rises after this time by the value set in parameter
t.
increase
, the
Controller keeps idling. This repeats until the consumer switch-on difference is
reached. If this condition is not reached, the tank of lower priority is loaded,
supposed the condition of switching difference is met – cf. more details in the
description of
Oscillating loading
function
.
idle time (min)
............ Time period the Controller idles, waiting if the solar collector temperature rises.
For description see parameter
t. increase.
sol.cons.2 (min)
......... If a tank of higher priority cannot be loaded, a tank of lower priority is loaded for
the time period set in this parameter.
Collector cooling
When this function is on, solar collector is cooled. As soon as the max. temperature is reached (in all
active tanks), tank loading is stopped. When the solar collector temperature exceeds the preset max.
collector temperature, the circulation pump starts and the collector is cooled by heating that tank which