Operating Instructions
Temperature Control Unit 90smart/150smart
NOTE
Important - When switching between the operating modes Pressure and Leak
stop mode, the temperature control unit must be switched off at the I/O switch!
Displays
Display
Remark
OUT 1
The heating is switched on when the LED is on
ALM
The cooler is switched on when the LED is on
Level
The light is on if there is insufficient heat carrier
Motor
The light is on if the thermal relay has been triggered
Setting the set-point value
Press
SET
,
Sv
flashes
Set the set-point value using the
or
button
Press
SET
, the new value is activated
Changing the parameter
Press
SET
for a few seconds until
Pv
appears
Pv
value flashes
Tap
SET
until
Lkv
appears
Set
Lkv
to 1 (clearance)
Tap
SET
until the desired parameter appears
Set the value using the
or
button
Press
SET
for a few seconds - End (set-point value/actual value
is displayed)
Switch off
Cool down device or temperature control circuit to a minimum of
80 °C
Switch off the device/pump with the I/O switch
WARNING
Danger of injury from escaping hot cooling water!
Before detaching connecting lines from the temperature control circuit, first al-
low the temperature control unit to cool down, as a function of the outlet tem-
perature, and then switch it off!
Check that the pump is no longer running!
Содержание 150smart
Страница 1: ...En 90smart 150smart Operating Instructions...
Страница 26: ...V 11 2014 22 Operating Instructions Temperature Control Unit 90smart 150smart...
Страница 37: ...V 11 2014 Temperature Control Unit 90smart 150smart Maintenance 33 Y2 Y13 69 41 68 T5 V21 F5 M10 Y6 Y13 S3 B1...
Страница 41: ...V 11 2014 Temperature Control Unit 90smart 150smart Maintenance 37...