V
11/2014
Temperature Control Unit 90smart/150smart
Operating Instructions
7
ing so, you will avoid unnecessary expense and problems during start-up
as well as production downtime.
Inspection of Consumers
Before installing the connecting lines between consumer and tempera-
ture control unit, the consumer must be subjected to the following inspec-
tions:
Verify that channels are unobstructed
Remove residual fluid and dirt with compressed air (foreign ob-
jects such as shavings etc. can damage the pump)
Rust and scale deposits must be removed because they greatly
interfere with the heat exchange between consumer and heat
transfer medium and increase the pressure drop in the consum-
er. Descaling can be carried out using the Regloplas REG de-
scaling unit (see the "Regloplas Temperature Control Technolo-
gy" brochure, REG data sheet)
Water Quality
The water used must meet the following requirements to avoid damage
to the cooler of the temperature control unit:
Criterion
Requirement
Appearance
clear/without sediment
Cloud
< 0.5 NTU (very light cloud)
Total hardness
< 10 °dH
pH-value
6.5-8.5
Conductivity
max. 500 µS/cm
Carbonate hard-
ness
< 5 °dH
Addition of RK93 corrosion inhibitor is urgently recommended (see the
"Regloplas Temperature Control Technology" brochure, RK93 data sheet).
Connecting Lines
The connecting lines must consist only of pressure-resistant and temper-
ature-resistant hoses and screw fittings. The cross-section of the con-
necting lines may not be reduced (see Maintenance section).
The connecting lines must be routed so that they are protected
against unintentional contact. Thermal expansion must be taken
into account in pipe joints
When connecting to public water mains, the applicable laws and
safety regulations must be observed (e.g., connection of the unit
via backflow preventer). The water mains pressure must be with-
in the range of 2-6 bar
Cooling water outlet - must prevent reverse flow and must be al-
ways open. The hose must be fastened so that any escaping
steam at the start of the cooling procedure does not pose a haz-
ard
Содержание 150smart
Страница 1: ...En 90smart 150smart Operating Instructions...
Страница 26: ...V 11 2014 22 Operating Instructions Temperature Control Unit 90smart 150smart...
Страница 37: ...V 11 2014 Temperature Control Unit 90smart 150smart Maintenance 33 Y2 Y13 69 41 68 T5 V21 F5 M10 Y6 Y13 S3 B1...
Страница 41: ...V 11 2014 Temperature Control Unit 90smart 150smart Maintenance 37...