AQUA24TF/D

Tel  +46 (0)31 720 02 00    Fax  +46 (0)31 720 02 50

Box 116   428 22  KÅLLERED    SWEDEN

1612G APR 02

INSTRUCTIONS

INSTRUCTIONS

Start up

1. Check that all wiring is correct.
2. Check that switch 2 is in the correct positions for the installa-

tion on hand.

3. If everything seems to be OK, connect supply voltage and do

those of the following tests that apply to the installation.

Function test: Cascade control.

1. Set function switch 3 and 5 to position A and switches 1 and

4 to position B.

2. Twist the setpoint knob to the clockwise endposition. LED Y1

should light up and the actuator should open the valve.

3. Twist the setpoint knob to the counter clockwise endposition.

LED Y2 should light up and the actuator should close the
valve.

4. Set function switch 4 to position A and switches 1,3 and 5 to

position B.

5. Twist MIN to the clockwise endposition. LED Y1 should light

up and the actuator should open the valve.

6. Twist MIN to the counter clockwise endposition. LED Y2

should light up and the actuator should close the valve.

Function test: Single sensor control.

1. Set function switch 3 and 5 to position A and switches 1 and

4 toposition B.

2. Twist the setpoint knob to the clockwise endposition. LED Y1

should light up and the actuator should open the valve.

3. Twist the setpoint knob to the counter clockwise endposition.

LED Y2 should light up and the actuator should close the
valve.

After completing the test:

Set the function switches in the correct positions for the installa-
tion on hand.
When running cascade control, set the potentiometer MIN to the
desired minimum limiting value for the supply air temperature
and set the cascade factor on potentiometer CF.

17
18

TG-A130
TG-D130

Fig 5

AQUA

19
20

TG-K330

Fig 4

AQUA

Settings

AQUA24TF/D is on delivery set to values suitable as starting values
for balancing the system.
Final settings must be tried out when the system is comissioned.
Factory settings FS in brackets.

Setpoint

0 - 30°C. Setpoint for the main controller.
(FS = 20°C).

CF

1 - 15. Cascade factor. (FS = 1). The value signifies
the immediate change in the duct controller setpoint
for a 1K step change in room temperature.
(Cascade control only).

Min

0 - 30°C. Minimum duct temperature. (FS = 15°C).
(Cascade control only).

N.B. When running single sensor room temperature control (not

cascade control) CF and Min are inactive.

Function switches

1 and 4 in position B
3 and 5 in position A

1 and 4 in position A
3 and 5 in position B

2 in pos. A = Internal
2 in pos. B = External

Wiring diagrams

Fig 1: Main sensor when using the built-in setpoint.
Fig 2: Main sensor and external setpoint TBI-30.
Fig 3: Main sensor and external setpoint when running room

temperature control with room sensor TG-R430.

Fig 4: Limiting sensor when running cascade control.
Fig 5: Frost sensor.

EMC emissions & immunity standards:

This product conforms with the requirements of European EMC
standards CENELEC EN 50081-1 and EN 50082-1 and carries the
CE mark.

LVD

This product conforms with the requirements of European LVD
standards IEC 669-1 and IEC669-2-1.

Single sensor control

Cascade control

Setpoint

1
2
3
4
5
6
7
8
9

10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

Neutral
24V AC in
Not connected

Output common

Output decrease
Output increase

Not connected

SPC 0-10V DC in
Signal neutral
+10V DC out
0-10V DC in
Frost sensor
Signal neutral
Limit sensor
Signal neutral
Fan supervision
Signal neutral
Main sensor
Signal neutral

Alarm relay

24V AC, 2A

Alarm relay

230V AC, 2A

Supply-
voltage

Содержание AQUA24TF/D

Страница 1: ...reglering minbegr nsas Koppla in begr nsningsgivaren i enligt fig 4 Frysskyddsgivare Frysskyddsgivaren placeras antingen som anliggningsgivare TG A130 p returvattenledningen efter batteriet eller som...

Страница 2: ...telefon 031 720 02 30 Inst llningar AQUA24TF D r vid leverans inst lld p v rden som r l mpliga startv rden vid injustering Slutgiltiga v rden provas ut i samband med uppstart av anl gg ningen FI Fabri...

Страница 3: ...or as an immersion sensor TG D130 in the heater or the return water pipe Should the temperature at the frost protection sensor fall below 10 C the frost protection controller will force the valve to...

Страница 4: ...et the cascade factor on potentiometer CF 17 18 TG A130 TG D130 Fig 5 AQUA 19 20 TG K330 Fig 4 AQUA Settings AQUA24TF D is on delivery set to values suitable as starting values for balancing the syste...

Страница 5: ...chiebung wird durch den Kaskadenfaktor CF bestimmt Bei Raumtem peraturregelung kann die Kanaltemperatur minimalbegrenzt werden Schlie en Sie den Begrenzungsf hler lt fig 4 an Frost protection sensor D...

Страница 6: ...1 Stellen Sie die Schalter 3 und 5 auf Position A und die Schalter 1 und 4 auf Position B 2 Drehen Sie das Sollwertpoti im Uhrzeigersinn in die Endposition Die LED Y1 sollte aufleuchten und der Venti...

Страница 7: ...oit utiliser une sonde antigel plac e sur la canalisation de retour d eau TGA 130 ou une sonde d immersion TGD 130 dans la batterie ou sur la canalisation de retour d eau Lorsque la sonde antigel d te...

Страница 8: ...lectriques 2 V rifier les positions des s lecteurs pour obtenir la fonction d sir e 3 Si tout para t OK alimenter le r gulateur et r aliser les tests ci dessous Test fonction mode cascade 1 Placer le...

Отзывы: