22 |
Regency Ultimate™ U900E Gas Fireplace
installation
VENTING
DIRECT VENT SYSTEM (FLEX)
HORIZONTAL TERMINATIONS ONLY
These venting systems, in combination with the U900E Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by
Warnock Hersey/ITS. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in the "Exterior
Vent Termination Locations" section.
Regency Direct Vent (Flex) System Termination Kit (Part # 946-515) includes all the parts needed to install the U900E with a maximum
run of 4 feet.
1)
6-7/8" dia. flexible liner (4 ft. length)
2)
4" dia. flexible liner (4 ft. length)
3)
spring spacers (4)
4)
thimble (2)
5)
AstroCap
termination cap (1)
6)
screws (12)
7)
tube of Mill Pac (1)
8)
plated screws (8)
9)
screws #8 x 1-1/2" Drill Point, Stainless
Steel (4)
1)
6-7/8" dia. flexible liner (10 ft. length)
2)
4" dia. flexible liner (10 ft. length)
3)
spring spacers (7)
4)
thimble (2)
5)
AstroCap
termination cap (1)
6)
screws (12)
7)
tube of Mill Pac (1)
8)
plated screws (8)
9)
screws #8 x 1-1/2" Drill Point, Stainless
Steel (4)
If longer runs are needed, the Regency Direct
Vent system (Flex) # 946-516 includes all
the parts needed to install the U900E with a
maximum 10' run.
Notes:
1) Liner sections must be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency may be used for Flex installations.