Regency U31-10 Gas Fireplace Insert

  |     

7

 

 

|

 

7

requirements

5.08: 

Modifications to NFPA-54, Chapter 10

(2) Revise 10.8.3 by adding the following additional requirements: 

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for 

residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than 

seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall 

be satisfied:  

1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled 

equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is 

installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery 

operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure 

served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of 

qualified licensed professionals for the installation of hard wired carbon monoxide detectors 

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon 

monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. 

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of 

thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon 

monoxide detector with an alarm shall be installed. 

2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions 

shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.  

3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 

(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The 

sign shall read, in print size no less than one-half (1/2) inch in size, 

"GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL 

OBSTRUCTIONS". 

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation 

unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 

5.08(2)(a)1 through 4.  

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:  

1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by 

the Board; and  

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or 

structure used in whole or in part for residential purposes.  

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product 

Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the 

instructions provided by the manufacturer for installation of the equipment and the venting system shall include: 

1. Detailed instructions for the installation of the venting system design or the venting system components; and 

2. A complete parts list for the venting system design or venting system.  

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a 

Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies 

"special venting systems", the following requirements shall be satisfied by the manufacturer: 

1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and  

2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and 

detailed installation instructions.  

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, 

all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of 

the installation.  

MA Code - CO Detector

(for the State of Massachusetts only)

Содержание U31-LP10

Страница 1: ...ble vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Leave the building immediately Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department In...

Страница 2: ...armth and charm of a fireplace at the flick of a switch The models U31 NG10 and U31 LP10 of this series have been approved by Warnock Hersey Intertek for both safety and efficiency As it also bears our own mark it promises to provide you with economy comfort and security for many trouble free years to follow Please take a moment now to acquaint yourself with these instructions and the many feature...

Страница 3: ...ion 13 High elevation 13 Draft hood connection 13 Venting 13 Gas pressure test 13 Gas insert aeration system 14 Test for flue spillage 14 Optional brick panel 14 Log set installation 15 Wiring diagram 18 Standard faceplate hearth trim install 19 Flush louver installation 20 Low profile faceplate installation 21 Safety screen installation removal 23 Optional wall thermostat 24 Final check 24 Operat...

Страница 4: ...4 Regency U31 10 Gas Fireplace Insert 4 dimensions UNIT DIMENSIONS WITH STANDARD FACE PLATE ...

Страница 5: ...Regency U31 10 Gas Fireplace Insert 5 5 dimensions UNIT DIMENSIONS WITH LOW PROFILE FACE PLATE ...

Страница 6: ...ssachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed This is a copy of the labels that accompany each U31 10 Gas Insert We have printed a copy of the contents here for your review The safety label is located on a plate inside the base of the unit visible when the bottom...

Страница 7: ...tly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspecti...

Страница 8: ...LDREN SHOULD BE CARE FULLY SUPERVISED WHEN THEY ARE IN THE SAME AREA AS THE APPLI ANCE TODDLERS YOUNG CHILDREN AND OTHERS MAY BE SUSCEPTIBLE TO ACCIDENTAL CONTACT BURNS A PHYSICAL BARRIERS IS RECOMMEND ED IF THERE ARE AT RISK INDIVIDUAL IN THE HOUSE TO RESTRICT ACCESS TO A FIREPLACE OR STOVE INSTALL AN ADJUSTABLE SAFETY GATE TO KEEP TODDLERS YOUNG CHILDREN AND OTHER AT RISK INDIVIDUALS OUT OF THE ...

Страница 9: ...nd assembly instruc tions This appliance may only be installed in a vented noncombustible fireplace 5 This appliance is Listed for bedroom installa tions In Canada room heaters must be installed with a Listed Millivolt Thermostat Some areas may have further requirements check local codes before installation 6 This unit is not approved for installation into a mobile home 7 Always connect this inser...

Страница 10: ... firing correctly This includes a Clocking the appliance to ensure the correct firing rate b Adjusting the primary air if required to ensure that the flame does not carbon c Ensuring that the appliance is venting correctly MATERIALS REQUIRED No electrical power supply is required for the gas control to operate A 120 Volt AC power cord is hooked up to the fan Plug the 3 wire cord into a suitable re...

Страница 11: ...31 10 Gas Fireplace Insert 11 11 installation COMBUSTIBLE MANTEL CLEARANCES IN MASONRY INSTALLATION Clearances for Low Profile Faceplate with Safety Screen Clearances for Standard Faceplate Low Profile Faceplate ...

Страница 12: ...ff the pilot cap to expose the pilot orifice 18 Unscrew the pilot orifice with the allen key and replace with the LP pilot orifice in the kit 19 Replace Burner Tray and reverse steps 5 to 1 20 Adjust the burner aeration setting to 3 8 to 3 8 as required for the best flame picture Fig 1 9 R e m o v e t h e b l a c k protection cap by hand fromthehi lowknob Fig 1 Fig 2 12 Flip the screw Fig 3 Fig 4 ...

Страница 13: ...t of the unit therefore the front of the unit must be kept clear of any obstructions GAS PRESSURE TEST The unit is preset to give the correct gas input at the specified manifold pressures shown on the label The maximum gas manifold pressure is Natural Gas 3 5 w c Propane 10 w c The manifold pressure is controlled by a regulator built into the gas control and should be checked at the pressure test ...

Страница 14: ...ONNECT THIS SWITCH OPTIONAL BRICK PANEL 1 Unwrap the brick pattern panels from the pro tective wrapping 2 Remove the safety screen and glass front if it is already installed 3 Put the rear brick panel flat against the back of the unit TEST FOR FLUE SPILLAGE A spillage test must be made before the installed unit is left with the customer Follow the procedure below 1 Start all exhaust fans in the ho...

Страница 15: ...2 154 Embers i 902 153 Rockwool j 902 179 P Vermiculite k 946 669 Platinum Embers supplied with packaged manual Note Install Optional Brick Panels prior to installing logs 1 Carefully remove the logs from the box and unwrap them The logs are fragile handle with care do not force into position 2 Sprinkle the vermiculite around the firebox base Take some of the embers approx 1 3 of the bag and sprin...

Страница 16: ...Center Log E 02 47 over Log B 02 45 and across the cutout on Log A 02 43 Cutout Pin Cutout Notch 8 Position notch in Front Right Log F 02 48 on Log E 02 47 and push the bottom right edge against the bracket on the burner tray and the front edge of the rear burner Notch Bracket D 02 46 E 02 47 F 02 48 C 02 56 A 02 43 B 02 45 A 02 43 B 02 45 E 0 2 4 7 Logs A 02 43 C 02 56 and B 02 45 in position C 0...

Страница 17: ...sit snugly against the bracket and the front edge of the rear burner Side View Page 3 of 3 11 Separate platinum embers and place on and around the embers and rockwool on the burner tray Avoid stacking platinum embers 12 Test fire to ensure proper light off make sure flame flows smoothly from one end of burner to the other If there is any flame hesitation check that area for any blockage of the bur...

Страница 18: ... Label all wires prior to disconnection when servic ing controls Wiring errors can cause improper and dangerous operation WARNING Electrical Grounding Instructions This appliance is equipped with a three pronged grounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle Do not cut or remove the grounding prong from this pl...

Страница 19: ... 1 3 Using the connectors provided join the left side trim with the ON OFF switch to the top trim Diagram 2 Connect the right side trim to the top trim 4 Place the trim on the assembled faceplate panels aligning the wire connections from the switches with the notch on the left side panel 5 Connect the fan switch wires by taking the black and red wires with the male ends in the grey harness and con...

Страница 20: ...on fit if the Louver needs to be adjusted bend the bracket out as shown in the diagram 2 Install the Spring Hinges on the left and right side of the bottom of the Firebox using 2 screws per hinge Bottom Louver Hinge Location 3 Place the Bottom Louver near the hinge Flip hinge over the Bottom Louver and secure using 3 screws ...

Страница 21: ...rol Diagram 5 Diagram 6 3 Tuck the wires into the clip to k eep them away from the inser t using the clip provided Attach the clip to the rear of the f aceplate to en sure that the wires do not touch the side of the unit The po wer cord should be r un behind the inner f aceplate panel 4 5 Feed wires through the left air chamber clip then clip them it to lower left of firebox as sho w below Wire fe...

Страница 22: ...anel pins 11 Install safety screen see next page 9 Hook door frame on 2 pins over glass door in locations shown below in Diagram 10 7 Attach 2 brackets near the bottom of the unit with one screw as shown below in Diagram 8 left and right brackets are inter changeable 8 Attach Regency logo to bottom louver Install bottom louver by hanging louver on brackets installed in step 8 Final Install Diagram...

Страница 23: ...installation SAFETY SCREEN INSTALLATION REMOVAL 1 Identify the four 4 slots located on the unit in locations shown below 2 Hook the tabs on the safety screen into the slots on the unit 3 To remove lift screen assembly up and pull away from unit ...

Страница 24: ...n label at 15 minutes 2 If required adjusting the primary air to ensure that the flame does not carbon First allow the unit to burn for 15 min to stabilize CAUTION Any alteration to the product that causes soot ing or carboning that results in damage to the exterior facia is not the responsibility of the manufacturer Thermostat Wire Table Recommended Maximum Lead Length Two Wire When Using Wall Th...

Страница 25: ...t Flame While the pilot flame is on it can make a very slight whisper sound Gas Control Valve As the gas control valve turns ON and OFF a dull clicking sound may be audible this is normal operation of a gas regulator or valve Unit Body Firebox Different types and thicknesses of steel will expand and contract at different rates resulting in some cracking and ticking sounds will be heard throughout ...

Страница 26: ...ment de modification de service ou d entretien peut provoquer des blessures ou des dommages matéri els Reportez vous au manuel du propriétaire de l information fournie avec cet appareil Pour obtenir de l aide ou des informations supplé mentaires consulter un installateur qualifié une agence de service ou fournisseur de gaz Important If the pilot does not hold turn pilot knob to OFF position Wait 5...

Страница 27: ...ot block the pilot 5 Keep the area near the appliance clear and free from combustible materials gasoline and other flammable vapours and liquids 6 Each time the appliance is lit it may cause condensation and fog the glass This con densation and fog is normal and will disap pear in a few minutes as the glass heats up Never operate the appliance without the glass properly secured in place with broke...

Страница 28: ... a bit of dish soap on the grommet so it will slide more easily onto the pin Check to make sure the fan is seated properly on the pins this is very important try to move the fan back and forth there should be no noise if there is check that the grommets haven t come loose When replacing the Burner Tray slide the aeration adjustment rod through the opening in the front of the Valve Assembly 1 Turn ...

Страница 29: ...lush Glass Bracket 59 936 233 3 4 Rope Gasket 404 969 Conversion to LP Kit 919 435 Manual Not available as a replacement part 1 400 011 Fan Opening Cover 2 911 071 P Fan Motor 120 V 5 910 750 Power Cord 120 V 910 752 Wire Harness intermediate 6 Thermodisc cover 7 Thermodisc bracket 8 910 142 Thermodisc Fan Auto ON OFF 10 Drafthood Assembly 11 Spill Switch Bracket 12 910 220 Spill Switch 13 Levelli...

Страница 30: ...525 Burner Assembly NG LP 63 910 048 Pilot Assembly NG 4 flame convertible top 910 049 Pilot Assemby LP 4 flame convertible top 67 Firebox Base 69 402 935 Log Set 402 572 Ember Package 70 Air Channel 72 Glass Trim Retainer 73 Firebox back and top 74 Glass Gasket Retainer 75 704 050 Firebox Baffle 76 400 090 Brick Clip 77 Fan Access Plate 78 Thermodisc Bracket 79 Thermodisc cover plate 80 Fan Shiel...

Страница 31: ...t Faceplate Assembly Part 405 900 Description Standard Faceplate Assembly 1 2 4 3 5 LOW PROFILE FACEPLATE Part 403 954 Description Low Profile Faceplate 1 Back plate Assembly 2 Bottom Louver 3 Right mounting bracket 4 Left mounting bracket 5 Front Frame ...

Страница 32: ...32 Regency U31 10 Gas Fireplace Insert 32 notes ...

Страница 33: ...Regency U31 10 Gas Fireplace Insert 33 33 notes ...

Страница 34: ...34 Regency U31 10 Gas Fireplace Insert 34 notes ...

Страница 35: ...ective part be returned to the distributor or agent Transportation Prepaid if requested Porcelain Enamel Absolute perfection is either guaranteed nor commercially possible Any chips must be reported and inspected by an authorized dealer within three days of installation Reported damage after this time will be subject to rejection It is the general practice of FPI to charge for larger higher priced...

Страница 36: ...___________________________________________________ Phone ____________________________________________________________ Date Installed _______________________________________________________ Serial No ___________________________________________________________ Register your Regency warranty online www regency fire com Reasons to register your product online today View and modify a list of all your ...

Отзывы: