background image

Regency P33SE Gas Fireplace

29

INSTALLATION

GAS PIPE PRESSURE 

TESTING

The appliance must be isolated from the gas 
supply piping system by closing its individual 
manual shut-off valve during any pressure 
testing of the gas supply piping system at test 
pressures equal to or less than 1/2 psig. (3.45 
kPa).  Disconnect piping from valve at pressures 
over 1/2 psig.

The manifold pressure is controlled by a regulator 
built into the gas control, and should be checked 
at the pressure test point.

Note: To properly check gas pressure, both 

inlet and manifold pressures should 
be checked using the valve pressure 
ports on the valve.

1)

  Make sure the valve is in the "OFF" position.

2)

  Loosen the "IN" and/or "OUT" pressure tap(s), 

turning counterclockwise with a 1/8" wide fl at 
screwdriver.

3)

  Attach manometer to "IN" and/or "OUT" 

pressure tap(s) using a 5/16" ID hose.

4)

  Light the pilot and turn the valve to "ON" 

position.

5)

  The pressure check should be carried out 

with the unit burning and the setting should 
be within the limits specifi ed on the safety 
label.

6)

 When fi nished reading manometer, turn 

off the gas valve, disconnect the hose and 
tighten the screw (clockwise) with a 1/8" fl at 
screwdriver. 

Note: Screw should be snug, 

but do not over tighten.

HIGH ELEVATION

This unit is approved in Canada for altitude to 
4500 ft. (CAN/CGA-2.17-M91). For Natural Gas 
installations above 4500 ft. follow current CAN/
CGA-B149.1.

P33SE-NG4 System Data 

Conversion Kit#  434-972 (NG to LP)

For 0 to 4500 feet altitude

Burner Inlet Orifi ce Sizes: 

#47

 

                 

Max. Input Rating 

17,000 Btu/h

Min. Input Rating 

12,000 Btu/h

Supply Pressure

 min.5.0" 

w.c.

Manifold Pressure  
 (High)

  

3.5"+/- 0.3" w.c.

P33SE-LP4 System Data 

For 0 to 4500 feet altitude

Burner Inlet Orifi ce Sizes: 

#56

 

 

                  

Max. Input Rating 

  1 5 , 5 0 0  

B t u / h  

Min. Input Rating 

12,000 Btu/h 

 

Supply Pressure

 min.11.0" 

w.c.

 

 

 

Manifold Pressure  
 (High)

 10"+/- 

0.4"w.c.

PILOT ADJUSTMENT

Note: If 

you 

have an incorrect fl ame pattern, 

contact your Regency

®

 dealer for 

further instructions.

Incorrect  fl ame pattern will have small, 
probably yellow fl ames, not coming into 
proper contact with the rear burner or fl ame 
sensor. 

 

Periodically check the pilot fl ames. Correct 
fl ame pattern has two strong blue fl ames: 
1  fl owing around the fl ame sensor and 1 
fl owing across the burner (it does not have 
to be touching the burner).

886 S.I.T. VALVE DESCRIPTION

1)

  Manual high/low adjustment

2)

 Pilot 

adjustment

3)

 Outlet 

Pressure 

Tap

4)

 Inlet 

Pressure 

Tap

5) 

Pilot Outlet

6)

  Main Gas Outlet

7)

  Main Gas Inlet

1

3

2

4

5

6

7

Burner

Flame Sensor

Pilot

Ignitor

Содержание Sunrise P33SE-LP4

Страница 1: ...light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department FPI FIREPLACE PRODUCTS INTERNATIONAL LTD 6988 Venture St Delta BC Canada V4G 1H4 918 850a Regency P33SE Gas Fireplace 04 13 11 Owners Installatio...

Страница 2: ...e warmth and charm of a fire at the flick of a switch The model P33SE has been approved by Warnock Hersey for both safety and efficiency As it also bears our own mark it promises to provide you with economy comfort and security for many trouble free years to follow Please take a moment now to acquaint yourself with these instructions and the many features of your Regency Fireplace ...

Страница 3: ...d local codes if any In the absence of local codes follow the current National Fuel Gas Code ANSI Z223 1 and the current National Electrical CodeANSI NFPA70 in the U S A and the current CAN CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22 1 in Canada This appliance comes equipped with a dedicated 8 Ground Lug for attachment of the ground wire to the steel chassis as ...

Страница 4: ...lation with Vertical Termination 28 Gas Line Installation 28 Pilot Adjustment 29 High Elevation 29 886 S I T Valve Description 29 Gas Pipe Pressure Testing 29 Conversion from NG to LP 30 Wiring Diagrams 36 Optional fan Wiring Diagram 37 Installing the Optional Fan 38 Optional Wall Thermostat 39 Battery Installation 39 Optional Remote Control 39 Wall Switch 39 Aeration Adjustment 39 Optional Stainl...

Страница 5: ...rfique maximum selon l altitude Modéle P33SE LP4 é é é é é é MAY BE INSTALLED IN MANUFACTURED MOBILE HOMES AFTER FIRST SALE Listed Certified for Certifi e pour Tested to WN 16510 VENTED GAS FIREPLACE HEATER CANADA and U S A é CAN CGA 2 17 M91 ANSI Z21 88 2009 CSA 2 33 2009 Model Modele P33SE NG4 Model Modele P33SE LP4 Made in Canada Fabrique au Canada Duplicate S N 11 WC 2 73 kPa 10 WC 2 49 kPa 6 ...

Страница 6: ...in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection t...

Страница 7: ...Regency P33SE Gas Fireplace 7 DIMENSIONS UNIT DIMENSIONS ...

Страница 8: ...l Code 3 See general construction and assembly in structions The appliance and vent should be enclosed 4 Thisappliancemustbeconnectedtothespeci fied vent and termination cap to the outside of the building envelope Never vent to another room or inside a building Make sure that the vent is fitted as per Venting instructions 5 Inspect the venting system annually for block age and any signs of deterio...

Страница 9: ...ontrol or Wall Thermostat e Optional Fan Assembly f Faceplate 10 Wall Mounted ON OFF Switch Use the toggle wall switch supplied with the manual package Use of a decor switch causes higher resistance which is a problem on gas fireplaces 11 Final check Before leaving this unit with the customer the installer must ensure that the appliance is firing correctly and operation fully explained to customer...

Страница 10: ...of chimney related fires is failure to maintain required clearances air space to combustible materials It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions C F Clearance Dimension Measured From A Front Floor Clearance min 1 25mm Underside of Unit B Sidewall on one side 7 1 2 241mm Side of Unit C Ceiling room and or alcove 30 8...

Страница 11: ...ARANCES Combustible mantel leg clearances from side of unit as per diagram Due to the extreme heat this fireplace emits the mantel clearances are critical Combustible mantel clearances from top of front facing are shown in the diagram on the right Note A non combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board ...

Страница 12: ...low the finished surface to be flush with the front of the unit Total facing thickness can vary from 1 2 13mm to 1 1 4 32mm thick NOTE Facing material may not protrude beyond unit otherwise the optional accesories will not be able to be mounted to the unit Install Side Nailing Strips and Top Facing Supportbeforeunitisslippedintoposition See Unit Assembly Prior to Installation Section 4 Combustible...

Страница 13: ...rtical Rise 16 1 2 419mm Rigid 12 3 4 324mm Flex K Corner Wall Length 37 1 2 953mm L Corner Facing Wall Width 53 1 4 1353mm M Framed Chase Ceiling 36 914mm Rigid 32 812mm Flex N Vent Centerline Height 30 762mm Rigid 26 660mm Flex O Gas Connection Height 1 1 2 38mm P Gas Connection Inset 4 102mm Q Gas Connection Width 3 76mm FRAMING DIMENSIONS NOTE If this is an outside corner the minimum distance ...

Страница 14: ...d facing material depth 2 Mount Side Nailing Strip using the 3 supplied screws into the three pre punched screw holes at the front sides of the unit Adjust support to desired facing material thickness UNIT ASSEMBLY PRIOR TO INSTALLATION Top Facing Support Side Nailing Strips folded out VENTING INTRODUCTION The P33E uses the balanced flue technology Co Axial system The inner liner vents products of...

Страница 15: ...above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 30cm 9 23cm L Clearance to a mechanical air supply inlet 3 91cm above if within 10 3m horizontally 72 1 8m 36 90cm b M Clearance above paved sidewalk or a paved driveway located on public prope...

Страница 16: ...ll the P33SE 4 with a maximum run of 2 feet If installing the P33SE 4 with a continuous vent length of more than 2 ft 6m to a maximum of 10 ft 3 0m use Kit 946 515 4 ft or 946 516 10 ft or see Rigid Pipe Venting Systems Section for alternate venting arrangements MINIMUM FLEX KIT CENTER LINE MINIMUM RIGID PIPE CENTER LINE AstroCap Flex Kits 1 6 7 8 dia flexible liner kit length 2 4 dia flexible lin...

Страница 17: ... Adaptor in conjunction withDuraventDirect Vent SelkirkDirect Temp Ameri Vent Direct venting and Security Secure Vent systems Use of these systems with the Rigid Pipe adaptor is deemed acceptable and does not affect the Intertek WHI listing of components WARNING Do not combine venting components from different venting systems Exception However useofthetheAstroCapTM and FPI Riser is acceptable with...

Страница 18: ... A N A N A Adjustable Length 7 Black N A N A 4D7AB N A N A N A Extension Pipe 8 1 2 Galvanized 46DVA 08A N A N A N A N A N A Extension Pipe 8 1 2 Black 46DVA 08AB N A N A N A N A N A Adjustable Length 12 Galvanized N A N A 4D12A N A SV4LA12 N A Adjustable Length 12 Black N A N A 4D12A N A SV4LBA12 N A Extension Pipe 16 Galvanized 46DVA 16A N A N A N A N A N A Extension Pipe 16 Black 46DVA 16AB N A...

Страница 19: ...N A N A N A N A N A TM 4ST36 Basic Horizontal Termination Kit A Disc 4DT HKA 4DHTK2 4DHTKA SV SHK N A Horizontal Termination Kit B 46DVA KHA Changed Components 4DT HKB 4DHTK1 4DHTKB SV HK N A Vertical Termination Kit Disc 4DT VKC 4DHTK 4DHTK SV FK N A FPI 946 506 P Vent Guard Optional for AstroCap 946 205 Vinyl Siding Shield for Riser Vent Terminal 510 994 Rigid Pipe Adaptor Must use with all rigi...

Страница 20: ...straight vertical and offset to vertical terminations using one 90o elbow with rigid pipe vent systems for Propane and Natural Gas Unit must be raised 1 Firestops are required at each floor level and whenever passing through a wall Maintain clearances to combustibles Vent must be supported at offsets Note Must use optional rigid pipe adapter when using rigid vent systems Part 510 994 ...

Страница 21: ...s Section for minimum and maximum heights Required Parts Part Description 946 529 Co linear DV Vertical Termination Cap 948 305 3 Flex 35 ft 946 563 Co Axial to Co Linear Adapter Kit which contains the following Co linear Flex Adapter Outer Pipe Inner Pipe Adapter 510 994 Rigid Pipe Adaptor 46DVA E45 45o Elbow Alternate Approved Caps 46DVA VC Vertical Termination Cap 46DVA VCH High Wind Cap 46DVAG...

Страница 22: ...es into Masonry Fireplaces The shaded area in the diagrams show the allowable vertical terminations 8 2 4m Min 30 762mm 30 9 1m Max 30 Horizontal Distance Feet Vertical Height feet 8 2 4m Min 30 762mm 30 9 1m Max 30 Horizontal Distance Feet Vertical Height feet 2 51mm max 8 2 4m Min 30 762mm 30 9 1m Max 30 Horizontal Distance Feet Vertical Height feet ...

Страница 23: ...sing one 45o and one 90o elbow two 45o elbows equal one 90o elbow Note Must use optional rigid pipe adaptor Part 510 994 when using rigid pipe vent systems Refer Rigid Pipe Venting Systems Section Maintain clearances to combustibles Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall A vent guard should be used whenever the ...

Страница 24: ...2 With these options maximum total pipe length is 30 feet with minimum of 11 feet total vertical and maximum 9 feet total horizontal P l e a s e n o t e minimum 1 foot between90o elbows is required A 1 Max 1 Min 3 Max B 2 Max 3 Min 5 Max C 3 Max 5 Min 6 Max D 4 Max 7 Min 7 Max E 5 Max 9 Min 8 Max F 6 Max 11 Min 9 Max Horizontal Venting with Two 2 90o Elbows One 90o elbow Two 45o elbows Option H V ...

Страница 25: ...ax 4 Min 5 Max C 4 Min 3 Max 6 Min 6 Max D 5 Min 4 Max 8 Min 7 Max E 6 Min 5 Max 10 Min 8 Max F 7 Min 6 Max 12 Min 9 Max One 90o elbow Two 45o elbows Option V H V V1 With these options maximum total pipe length is 30 feet with minimum of 6 feet total vertical and maximum 8 feet total horizontal Please note minimum 1 foot between 90o elbows is required A 1 Min 4 Max 2 Min B 2 Min 5 Max 3 Min C 3 Mi...

Страница 26: ... 90o elbow Two 45o elbows With these options max total pipe length is 30 feet with min of 11 feet total vertical and max 7 feet total horizontal Please note min 1 foot between 90o elbows is required Option V H H1 V V1 A 2 Min 3 Max 4 Min B 3 Min 4 Max 6 Min C 4 Min 5 Max 7 Min D 5 Min 6 Max 8 Min E 6 Min 7 Max 9 Min F 7 Min 8 Max 10 Min With these options max total pipe length is 30 feet with min ...

Страница 27: ...Set the unit in its desired location Check to determine if wall studs or roof rafters are in the way when the venting system is attached If this is the case you may want to adjust the location of the unit Rough in the gas preferably on the right side of the unit and the electrical junction block is on the left side on the left 2 Direct Vent pipe and fittings are designed with special twist lock co...

Страница 28: ...em it is highly recommended to apply Mill Pac sealant supplied to every in ner pipe connection Failure to do so may result in drafting or performance issues not covered under warranty Silicone red RTV is optional 8 Slide the appliance and vent assembly towards the wall carefully inserting the vent pipe into the vent cap assembly It is important that the vent pipe extends into the vent cap sufficie...

Страница 29: ... with a 1 8 flat screwdriver Note Screw should be snug but do not over tighten HIGH ELEVATION This unit is approved in Canada for altitude to 4500ft CAN CGA 2 17 M91 ForNaturalGas installations above 4500 ft follow current CAN CGA B149 1 P33SE NG4 System Data Conversion Kit 434 972 NG to LP For 0 to 4500 feet altitude Burner Inlet Orifice Sizes 47 Max Input Rating 17 000 Btu h Min Input Rating 12 ...

Страница 30: ...cal Converted to LPG 1 908 528 Red LPG label 1 904 529 5 32 Allen Key 1 910 101 LPG Injector Pilot Orifice 1 911 009 Hi Lo Conversion LP 1 918 862 Instruction Sheet Installation of the LPG Conversion Kit 1 Shut off the gas supply 2 a Remove the Faceplate by lifting it off of the flush door b Remove the flush door c Remove the Glass Crystals or Ceramic Stones Also remove Stainless Steel Panels if i...

Страница 31: ... receiver with two screws and attach to the floor of the unit with a velcro pad 12 Reverse steps 5 and 4 13 Match the remote control to the receiver see remote control instructions 14 Reverse steps 2 and 1 15 Check to ensure there are no gas leaks 4 Remove DFC digital firebox control box from the floor of the unit 5 Disconnect wire harness ground wire and spark wire from DFC See attached wiring di...

Страница 32: ...b if installed by removing 2 screws as shown below 8 Plug in receiver DC supply wire as shown below 5 Disconnect wire harness ground wire and spark wire from DFC DFC 4 Remove DFC digital firebox control box from the floor of the unit 1 Shut off the gas supply and disconnect all power to the unit 2 Remove the louvers bay door or faceplate if installed 3 Disconnect battery pack located on the floor ...

Страница 33: ...so peel off paper on back side of wire clip and place wires conveniently in appliance 16 Bundle all wires together and clip with supplied wire clip as shown below 18 Match the remote control to the receiver see remote control instructions 19 Reverse steps 2 and 1 20 Check to ensure there are no gas leaks Heat shield 15 Install 4 AA batteries into the receiver 13 Plug the stepper motor into the mot...

Страница 34: ...or of the unit as shown below and discard 7 Connect the TPTH and TH wires green to green and white to white as shown below TPTH DFC TH 4 Identify wires in the GTM GTMF remote wiring harness see wiring diagram 5 Remove DFC digital firebox control box from the floor of the unit 9 Remove the hi lo knob by removing 2 screws as shown below 8 Plug in receiver DC supply wire as shown below 10 Install the...

Страница 35: ...s from step 5 14 Reinstall the DFC box onto the velcro pad on the floor of the unit 15 Install the heat shield to the receiver with two screws and attach to the floor of the unit with a velcro pad 18 Plug fan control module into recepticle located on the left hand side of the unit 19 Match the remote control to the receiver see remote control instructions 20 Reverse steps 2 and 1 21 Check to ensur...

Страница 36: ...a later date Proflame System Configuration 886 GTMF Wire Diagram SureFire Switch Proflame System 886 ON OFF Stand Alone Illustrated Wire Diagram Surefire Switch IPI CPI Standard Main ON OFF Switch or Optional Wall Switch Battery Holder Pilot Ground Wire Chassis Ground EI Pilot Sense Electrode Spark Electrode DFC Wire Harness Assembly Proflame DFC Board 886 Proflame Valve Note 4 AA batteries must b...

Страница 37: ... Volts plug in fan circuit with speed control switch on wall Lockwasher Fan ground wire Nut 8 Ground Lug for mobile home Star washer Ground Green Neutral Live Black Red Red Fan Thermodisc normally open Ground ON OFF Rotary Speed Control 120V AC 60 Hz Fan OPTIONAL FAN WIRING DIAGRAM ...

Страница 38: ...e hot surfaces Diagram 2 Diagram 1 Diagram 2 Diagram 3 Diagram 4 Fan Control Box Control Mounting Plate Diagram 5 Diagram 7 Diagram 6 9 Secure the fan wires and power cord by attaching one of the adhesive backed wire holder clips Part 910 199 onto the Fire placebase Usethesecondcliptobundleup the wires approximately 4 from the control box Ensure that there is no interference with the wires when th...

Страница 39: ...the wall to install the receiver and the receptacle box protection from extreme heat is very important Run wires from the fireplace to that location Use Thermostat Wire Table 2 Connect the two wires to the gas valve See wiringdiagram WallswitchGT GTM GTMF using wire 0 584 907 CAUTION Do not wire millivolt remote control wires to 120V wire 3 Install 3AAAalkaline batteries in transmitter and 4 AA al...

Страница 40: ...ion Black Enamel panels must be inspected for scratches and dimples prior to installation All claims to be recorded at this time Claims for damage after installation will not receive consideration To protect the finish during installation and handling cotton gloves MUST be worn at all times while handling the panels even when removing protective coating Use a hair dryer to remove the protective co...

Страница 41: ...ss or stones will not be covered under warranty NOTE When using Ceramic Stones DO NOT cover burner ports that lead to pilot flame Glass Crystals shown on Burner Optional Ceramic Stones shown on Burner There are 2 optional pebble packages to choose from 1 White River Pebbles 2 Natural River Pebbles Spread the pebbles evenly on the exposed base of the firebox Pebbles are NOT to be placed anywhere on...

Страница 42: ... the unit diagram 1 Be careful that the glass gasket does not roll up there must be a gap between the gasket and the door lip to ensure that the door sits securely on the unit See Diagram 2 Use the hook to pull the spring out until you can put the hook into the slot on the bottom door bracket Repeat for 2nd spring See diagram 3 To remove the flush door reverse the above steps To remove the flush d...

Страница 43: ...f the faceplate has a flange that hooks over the top of the flush door 2 Install the heat deflector on the fire box as shown in Diagrams 2 3 Loosen 3 Phillips head screws already in firebox slide heat deflector on to screws and retighten Diagram 1 Diagram 2 Top of Firebox Heat Deflector Diagram 3 Diagram 4 Diagram 5 Bend Diagram 6 Flange Mounting Frame Heat Deflector Control Shield Faceplate Suppo...

Страница 44: ...TION Diagram 7 Diagram 8 Diagram 9 Faceplate Faceplate Support 6 Hook the flange on the faceplate over the top of the flush door and gently lower the faceplate into place until it rests against the faceplate supports as shown in Diagrams 7 8 ...

Страница 45: ...ted below are some examples All are normal operating soundsandshouldnotbeconsideredasdefects in your appliance Burner Tray The burner tray is positioned directly under the burner and is made of a different gauge material from the rest of the firebox and body Therefore the varying thicknesses of steel will expand and contractatslightlydifferentrateswhichcancause ticking and cracking sounds You shou...

Страница 46: ...vice or maintenance can cause injury or property damage Refer to the owner s information manual provided with this appliance For assistance or additional information consult a qualified installer service agency or gas supplier AVERTISSEMENT Quiconque ne respecte pas à la lettre les instructions dans la présente notice risquede déclencher un incendie ou une explosion entraînant des dommages des ble...

Страница 47: ...areas to inspect as follows 1 Check the Venting System for corrosion in areas that are exposed to the elements These will appear as rust spots or streaks and in extreme cases holes These components should be replaced immediately 2 Remove the Cap and shine a flashlight down the Vent Remove any bird nests or other foreign material 3 Check for evidences of excessive condensation suchaswaterdropletsfo...

Страница 48: ...he 2 screws and then lift out the burner assembly Installing Valve 1 Install new Valve Tray Assembly 2 Reverse steps 9 1 Diagram 5 Lift out Valve Tray Assembly Diagram 4 Diagram 2 Diagram 3 6 Remove the fire box base Diagram 3 5 Remove the retainer bar Diagram 2 9 Remove the 10 screws securing the valve tray assembly in place Diagram 4 and then lift the entire assembly out Diagram 5 7 Disconnect t...

Страница 49: ...33 Control Mounting Plate 15 434 574E P Valve Assembly P33SE NG4 SIT Packaged 434 576E P Valve Assembly P33SE LP4 SIT Packaged 911 004 Valve SIT NG 911 005 Valve SIT LP 911 006 Valve Pilot Assembly NG 911 007 Valve Pilot Assembly LP 904 434 Orifice 47 NG 904 241 Orifice 56 LP Part Description 16 341 525 Burner Assembly NG LP c w Cap 17 Outerbox Assembly 18 Firebox Assembly 19 433 538 Flush Door As...

Страница 50: ...50 Regency P33SE Gas Fireplace PARTS LIST 8 10 24 21 19 16 20 15 3 1 2 18 23 17 4 FAN SWITCH ASSEMBLY 25 28 29 27 30 13 22 14 MAIN ASSEMBLY ...

Страница 51: ... be returned to the distributor or agent Transportation Prepaid if requested Porcelain Enamel Absolute perfection is either guaranteed nor commercially possible Any chips must be reported and inspected by an authorized dealer within three days of installation Reported damage after this time will be subject to rejection It is the general practice of FPI to charge for larger higher priced replacemen...

Страница 52: ...ler ___________________________________________________________ Phone ___________________________________________________________ Date Installed ______________________________________________________ Serial No __________________________________________________________ Register your Regency warranty online www regency fire com Reasons to register your product online today View and modify a list of ...

Отзывы: