Regency Plateau™ Series Outdoor Gas Fireplace
9
INSTALLATION
INSTALLATION
CHECKLIST
1)
Appliance is factory equipped for Natural Gas.
When using Propane, see LP conversion section
in this manual. For LP - use a maximum 11
pound tank or direct hard pipe from an external
LP supply.
2)
Locate appliance:
a) Refer to "Locating Your Outdoor decorative
gas appliance" section
b) Clearances to Combustibles (Refer to
"Clearances" section)
3)
Gas Connection - for ease of installation and
gas connection, remove left side panel
(one facing ON/OFF switch. Test for leaks.
.
4)
Install 4 "AA" batteries into battery pack and
replace into battery compartment holder.
DO NOT USE A 9V battery.
5)
Connect the ON/OFF switch wires to the switch.
6)
Install standard and optional features. Refer to
the following sections:
a. Tabletop
Installation
b. Glass
Crystals
c.
Volcanic Stone Installation (optional)
d.
Log Installation (optional)
e.
Glass Surround Installation (optional)
f.
Weather Cover Installation
7)
Final
check.
This includes:
1)
Clocking the appliance to ensure the correct
fi ring rate (rate noted on label), after burning
appliance for 15 minutes.
2)
If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow the
unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results in dam-
age is not the responsibility of the manufacturer.
LOCATING YOUR
OUTDOOR DECORATIVE GAS APPLIANCE
1)
When selecting a location for your outdoor decorative gas appliance, ensure that the clearances are
met.
2)
This appliance must be installed in an open-air situation with natural ventilation, without stagnant
areas, where gas leakage and products of combustion are rapidly dispersed by wind and natural
convection.
3)
Certain materials or items, when placed under or near the appliance, will be subjected to radiant
heat and could become damaged.
4)
Typically an outdoor space is not enclosed but, any enclosure in which the appliance is used shall
comply with one of the following:
An enclosure with walls on all sides, but at least one permanent opening at ground level and no
overhead cover.
Within a partial enclosure that includes an overhead cover and no more that two walls.
Within a partial enclosure that includes an overhead cover and more than two walls, the following
shall apply:
•
At least 25% of the total wall area is completely open, and
•
At least 30% of the remaining wall area is open and unrestricted
30% or more in total of the remaining wall
area is open and unrestricted.
Open side at least 25% of total wall area