Regency
®
PG36-5 Gas Log Fireplace
6
INSTALLATION
Clearances for Bay or Flush Front
NOTE: The minimum fl oor clearance must
be maintained from the top surface of the
carpeting, tile, etc.
Minimum Clearance from Top of Unit to:
Mantel*
Minimum
7" (177mm)
Ceiling
from top of unit.
32" (1016mm)
Side Wall Clearance
Bay or Flush Front
6"
(152mm)
Horizontal Flue Clearances
Top
2" (51mm)
Side
1-1/2"
(38mm)
Bottom
1-1/2"
(38mm)
Vertical Flue Clearances
1-1/4"
(32mm)
Alcove Clearances**:
Max.
Depth
36"
(914mm)
Min.
Width
48"
1219mm)
Min.
Height
72"
1829mm)
* see mantle clearance instructions
(Refer to the "Combustible Mantels," & "Mantel
Leg Clearances" sections.)
CLEARANCES
The clearances listed below are Minimum
distances unless otherwise stated:
A major cause of chimney related fi res is
failure to maintain required clearances (air
space) to combustible materials. It is of the
greatest importance that this fi replace and
fl ue system be installed only in accordance
with these instructions.
Clearance to Combustibles from:
Back
0"
(0mm)
Side
0"
(0mm)
Floor
0
"
(0mm)
Diagram 1
LOCATING YOUR
FIREPLACE
1)
When selecting a location for your fi replace,
ensure that the clearances outlined on this
page are met.
2)
Provide adequate clearances for servicing.
3)
The appliance must be installed on a fl at,
solid, continuous surface (e.g. wood, metal,
concrete). This may be the fl oor, or raised up
on a platform to enhance its visual impact.
If the appliance is going to be installed
on carpeting, combustible linoleum tile or
other combustible material other than wood
fl ooring, the appliance must be installed on
a metal or wood panel extending the full
width and depth of the appliance.
4)
The PG36 Co Axial Flue Gas Fireplace
can be installed in a recessed position or
framed out into the room as in A, B, C, D.
See Diagram 1.
5)
This appliance is Listed for bedroom
installations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6)
The PG36 Co Axial Flue Gas Fireplace is
approved for alcove installations, which
meet the clearances listed on this page.
7)
We recommend that you plan your installation
on paper using exact measurements for
clearances and fl oor protection before
actually installing this appliance. Have an
authorized inspector, dealer, or installer
review your plans before installation.
Note: For fl ue terminations see the "Exterior
Flue Termination Locations" section.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1)
Ensure that structural members are not cut
or weakened during installation.
2)
Ensure proper grounding using the #8
ground lug provided. Refer to the "Wiring"
section.
A)
Flat on Wall
B)
Flat on Wall Corner
C)
Recessed into Wall/Alcove
D)
Corner
WARNING
Fire hazard is an extreme
risk if these clearances
are not adhered to.