Regency I43-1 ULTIMATE Gas Inbuilt Fireplace
INSTALLATION
GAS CONNECTION
For minimum and maximum supply pressure see the System
Data table on page 8.
Note: Prior to any pressure testing of the gas supply
piping system that exceeds test pressures of 1/2
psig (3.45 kPa), this appliance and its individual
shut-off valve must be disconnected from the piping
system. If test pressures equal to or less than 1/2
psig (3.45 kPa) are used then this appliance must
be isolated from the piping system by closing its
individual manual shut-off valve during the testing.
Valve Access:
Loosen and remove the wingnuts on the both
sides of the bottom louvre and then remove the louvre.
GAS CONNECTION WARNING:
Only persons licensed to work with gas piping may make the
necessary gas connections to this appliance.
1)
If the appliance is to be installed into an existing chimney
system, thoroughly clean the masonry fi replace and have
the chimney swept.
2)
The gas connection is a 1/2" BSP male pipe on the
rear left side of the unit. The gas line can be rigid
pipe or to make installation easier use a listed fl ex-
ible connector and
manual shut-off valve
if allowed by local
building codes. A 1/2"
gas supply pipe must
be brought near this inlet hole.
3)
Locate the center point where the fl ue will pass through
the chimney above the appliance. Move the appliance
into the exact location where it is to be installed. Ensure
that the Inbuilt is level.
4)
The gas control valve is provided with two "IN" and "OUT"
pressure taps, and are easily accessible for a test gauge
connection (see diagram on page 10).
5)
Once the gas has been connected ensure that the pilot
valve is in line with burner.
CAUTION: If the door is removed or opened for servicing,
it must be replaced and closed prior to operating the appli-
System Data
For 0 to 610 metres altitude*
Burner Inlet Orifi ce Sizes:
NG LPG
Rear Burner
n/a
#54(1.4mm)
Front Burner
#31(3.0mm) #56(1.15mm)
Input Rating
-
NG
40 mj
-
LPG
39
mj
Supply Pressure:
NG min. 1.13
kPa
LPG min.
2.75
kPa
Manifold Pressure
NG
.85 kPa
LPG
2.55
kPa
ance. The glass must be
fi
xed in the door when operating.