Regency Hume Freestanding Wood Fire
7
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
INSTALLATION
A
400mm
400mm
450mm
B
210mm
180mm
300mm
C
200mm
200mm
200mm
D
181mm
181mm
181mm
E
123mm
123mm
123mm
F
400mm
400mm
400mm
G
1015mm
1015mm
1015mm
H
1120mm
1120mm
1120mm
Floor Protection
A combustible floor must be protected by non-combustible material (like
tile, concrete board, or as defined by local codes) extending beneath
the heater as follows;
From Sides:
123mm
From Front:
400mm
From Back:
181mm
The floor protector should consist of 6mm thick cement fibre sheet
which has a thermal resistance of 0.8m
2
k/w for 4mm sheets of cement
fibre sheet.
The flue pipe shall extend not less than 4.6m above the top of the floor protector.
NOTE: Installation must be carried out by a licensed installer in accordance
with AS/NZS 2918:2001.
Flo-Met
Super Single
*(1)
Hawkwind
Standard
AHD Special
Insulated
*(2)
IMPORTANT
* (1) The
Flomet Super Single flue kit
must be installed with a 130
o
x
900mm stainless reflective shield between decromesh.
* (2) The
AHD Special Insulated flue kit
must be installed with a
40mm air gap around the flue to any combustible surfaces and the
ceiling ring must be spaced as such to provide an air gap of 20mm to
the ceiling. The AHD Special Insulated flue kit must be installed with
a perforated ceiling plate and 250mm dia. x 195mm high heatshield
positioned directly above the ceiling plate.
NOTE:
A minimum clearance of 180mm (flat wall) or 200mm (corner wall) must be retained for all wall surfaces to allow for fan access and maintenance.