City Series CB60E | 5
H
I
A
E
B
C
G
D
F
CLEARANCES CB60E (Corner Install)
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not adhered
to. It is of greatest importance that this fireplace and vent system be
installed only in accordance with these instructions.
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that
this fireplace and vent system be installed only in accordance with these instructions.
Note: Left handed corner shown in illustration. Clearances will be the same for the right hand side.
Clearance:
Dimension
Measured From:
A: Mantel Height (min.)
**
Top of Fireplace Opening
B: Opening Height
18" (457 mm)
Bottom/Top of Fireplace Opening
C: From Floor (min.)
10-1/4" (260 mm)
Bottom of Fireplace Opening
D: Sidewall (on one side) min.
39" (991 mm)
Side of Fireplace Opening
E: Mantel Depth (max.)
**
Front of Fireplace Opening
F: Alcove Depth
35" (889 mm)
Front of Fireplace Opening
G: Convection Air Outlet
180 square inches
H: Convection Air Outlet Opening Offset
*1" (25 mm)
Max. offset from top of chase enclosure
I: Chase Enclosure (Min.)
81-1/4" (2064 mm)
From Base of Unit/Floor to top of enclosure
Hearth
0"
No hearth required
** See mantel clearances chart in this manual.
Flue Clearances to Combustibles
Horizontal - Top
3"
Horizontal - Side
2"
Horizontal - Bottom
2"
Vertical
2"
Passing through wall/
floor/ceiling - when
firestop is used.
1-1/2"
Top View
Alcove
The
HeatWave
Duct Kit has different
clearance and framing require-
ments, check the
HeatWave
manual
for details.
D
F
Left Corner
Shown