Vertical Venting with Two (2) 90° Elbows 

- Initial vertical section.

Two 45° elbows = One 90° elbow

Option

V

H

V+ V1

Maximum total pipe: length, of 
all sections, must not exceed 
30 feet.  
Total horizontal sections must 
not exceed 8 feet.

Minimum of 1 foot between 
90° elbows is required.

A)

1’ Min.

4’ Max.

2’ Min.

B)

2’ Min.

5’ Max.

3’ Min.

C)

3’ Min.

6’ Max.

4’ Min.

D)

4’ Min.

7’ Max.

5’ Min.

E)

5’ Min.

8’ Max.

6’ Min.

Vertical Venting with Two (2) 90° Elbows 

- Initial horizontal section.

Two 45° elbows = One 90° elbow

Option

H + H1

V

Maximum total pipe: length, of 
all sections, must not exceed 
30 feet.  
Total horizontal sections must 
not exceed 6 feet.

Minimum of 1 foot between 
90° elbows is required.

A)

2’ Max.

2’ Min.

B)

3’ Max.

3’ Min.

C)

4’ Max.

4’ Min.

D)

5’ Max.

5’ Min.

E)

6’ Max.

6’ Min.

Vertical Venting with Three (3) 90° 

Elbows - Initial vertical section.

Two 45° elbows = One 90° elbow

Option

V

H + H1

V+ V1

Maximum total pipe: length, of 
all sections, must not exceed 
30 feet.  
Total horizontal sections must 
not exceed 8 feet.

Minimum of 1 foot between 
90° elbows is required.

A)

2’ Min.

3’ Max.

4’ Min.

B)

3’ Min.

4’ Max.

6’ Min.

C)

4’ Min.

5’ Max.

7’ Min.

D)

5’ Min.

6’ Max.

8’ Min.

E)

6’ Min.

7’ Max.

9’ Min.

F)

7’ Min.

8’ Max.

10’ Min.

Vertical Venting with Three (3) 90° 

Elbows - Initial horizontal section.

Two 45° elbows = One 90° elbow

Option

H

V

H + H1

V+ V1

Maximum total pipe: 
length, of all sections, 
must not exceed 30 
feet.  
Total horizontal sections 
must not exceed 7 
feet.

Minimum of 1 foot 
between 90° elbows 
is required.

A)

1’ Max.

1’ Min.

3’ Max.

3’ Min.

B)

2’ Max.

2’ Min.

4’ Max.

5’ Min.

C)

3’ Max.

3’ Min.

5’ Max.

7’ Min.

D)

4’ Max.

4’ Min.

6’ Max.

9’ Min.

E)

5’ Max.

5’ Min.

7’ Max.

11’ Min.

P33 Gas Fireplace

34

August 2008 Product Speci

fi

 cations Book

Gas Fir

eplaces

Gas Fireplaces

Содержание 510-994

Страница 1: ...th Vertical 19 1 2 495mm Vertical Rise 16 1 2 419mm Rigid 12 3 4 324mm Flex Horizontal J Corner Wall Length 37 1 2 953mm K Corner Facing Wall Width 53 1 4 1353mm L Framed Chase Ceiling 36 914mm Rigid 32 813mm Flex M Vent Centerline Height 30 762mm Rigid 26 660mm Flex G H I K J L Q O P N M 10 254mm dia Hole through wall Vent Opening for gas connection Top Header Drywall or other facing R Dimension ...

Страница 2: ...m Floor 1 25mm minimum J Framing Depth Vertical 19 1 2 495mm Vertical Rise 16 1 2 419mm Rigid 12 3 4 324mm Flex Horizontal K Corner Wall Length 37 1 2 953mm L Corner Facing Wall Width 53 1 4 1353mm M Framed Chase Ceiling 36 914mm Rigid 32 813mm Flex N Vent Centerline Height 30 762mm Rigid 26 660mm Flex The unit must be raised a minimum of 1 above the finished floor Dimension H H I minimum Dimensio...

Страница 3: ...rs are shown in the diagram below Mantel may be installed anywhere in the shaded area or higher Drywall Mantel Clearances 2 0 12 6 4 8 10 0 Side View Top of Unit 12 305mm 3 1 2 89mm 7 1 2 191mm A 3 76mm Standoff B C D Note If desired a non combustible mantel may be installed at a lower height Note Ensure the paint that is used on the mantel and the facing is heat resistant or the paint may discolo...

Страница 4: ...replace and vent system be installed only in accordance with these instructions Clearance Dimension Measured From A Front Floor Clearance min 1 25mm Underside of Unit B Sidewall 7 1 2 241mm Side of Unit C Ceiling room and or alcove 30 889mm Top of Unit D Alcove Width 48 1219mm Sidewall to Sidewall Minimum E Alcove Depth 36 914mm Front to Back Wall Maximum Flue Clearances to Combustibles Horizontal...

Страница 5: ...e supported every 3 feet If required by the external termination location the listed alternate termination caps may be used Important When installing Cabinet Mantels the wall thimble must be secured first and venting must be attached to unit before sliding into final position Alternate Horizontal Termination Caps Snorkel Terminations Snorkel Terminations For installations requiring a vertical rise...

Страница 6: ... must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall Maintain clearances to combustible materials Minimum of 1 pipe section between elbows Note Must use optional rigid pipe adapter when using Rigid Pipe Part 510 994 Unit must be raised by 1 when using Contemporary Faceplate Maximum 40 ft 12 2m Minimum 9 6 2 9m Minimum 8 6 2 6m Max 10 3m cen...

Страница 7: ...x 6 Min Vertical Venting with Three 3 90 Elbows Initial vertical section Two 45 elbows One 90 elbow Option V H H1 V V1 Maximum total pipe length of all sections must not exceed 30 feet Total horizontal sections must not exceed 8 feet Minimum of 1 foot between 90 elbows is required A 2 Min 3 Max 4 Min B 3 Min 4 Max 6 Min C 4 Min 5 Max 7 Min D 5 Min 6 Max 8 Min E 6 Min 7 Max 9 Min F 7 Min 8 Max 10 M...

Страница 8: ...ibles Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall A vent guard may be required as per local codes refer to Exterior Vent Termination Locations Note FPIDirectVentSystem Flex isonlyapprovedforhorizontal terminations P33 Gas Fireplace Unit must be raised by 1 when using Contemporary Faceplate Please refer to Exterior Ve...

Страница 9: ... Horizontal Venting with Three 3 90 Elbows Initial vertical section Two 45 elbows One 90 elbow Option V H V V1 H H1 Maximum total pipe length of all sections must not exceed 30 feet Total horizontal sections must not exceed 8 feet Minimum of 1 foot between 90 elbows is required A 2 Min 1 Max 3 Min 4 Max B 3 Min 2 Max 4 Min 5 Max C 4 Min 3 Max 6 Min 6 Max D 5 Min 4 Max 8 Min 7 Max E 6 Min 5 Max 10 ...

Страница 10: ... inlet air collar of the termination cap This appliance is designed to be attached to two 3 76mm co linear aluminium flex running the full length of the chimney See the Venting Arrangements for minimum and maximum heights Required Parts Part Description 946 529 Co linear DV Vertical Termination Cap 948 305 3 Flex 35 ft 946 563 Coaxial to Co linear Adapter Kit 510 994 Rigid Pipe Adapter 58dva E45 4...