P33 Gas Fireplace

Combustible Mantels with 

Contemporary Faceplate

Because of the extreme heat this 

fi

 replace emits, the mantel 

clearances are critical.

 Combustible mantel clearances from top of 

the louvers are shown in the diagram below. Mantel may be installed 
anywhere in the shaded area or higher.

Mantel Leg Clearances with 

Contemporary Faceplate

Combustible mantel leg clearances from side of unit as per diagram 
below:
Clearances are from the 

fi

 nished edge of the unit or an installed front.

Caution Requirements

The top, back and sides of the 

fi

 replace are de

fi

 ned by 

standoffs. The metal ends of the standoff may 

NOT

 be 

recessed into combustible construction.

WARNING

Fire hazard is an extreme risk 

if these clearances (air space) to combustible materials are not 

adhered to. It is of greatest importance that this 

fi

 replace and vent 

system be installed only in accordance with these instructions.

Clearance:

Dimension

Measured 

From:

A: *Front Floor Clearance 
(min.)

1" (25mm)

Underside of 
Unit

B: *Sidewall

7-1/2" (241mm)

Side of Unit

C: *Ceiling
     (room and/or alcove)

30" (889mm)

Top of Unit

D: Alcove Width

48" (1219mm)

Sidewall to 
Sidewall 
(Minimum)

 E: Alcove Depth

36" (914mm)

Front to 
Back Wall 
(Maximum)

Flue Clearances to 

Combustibles

Horizontal - Top

2-1/2"

Horiztonal - Side 

1-1/2"

Horiztonal - Bottom

1-1/2"

Vertical (Flex Vent)

1-1/2"

Vertical (Rigid)

1-1/4"

*Note:  All measurements are from the top/side 

of the unit, not optional front.

Clearance Requirements with 

Contemporary Faceplate

Top View

0-3

WARNING

Failure to maintain required clearances is a major cause of chimney related 

fi

 res.  

Installation of this 

fi

 replace must comply with these clearances

Please note:

 Due to ongoing product development, product appearance and speci

fi

 cations 

are subject to change without notice.

C

B

C

Close to Ceiling

31

August 2008 Product Speci

fi

 cations Book

Gas Fireplaces

Gas Fir

eplaces

Содержание 510-994

Страница 1: ...th Vertical 19 1 2 495mm Vertical Rise 16 1 2 419mm Rigid 12 3 4 324mm Flex Horizontal J Corner Wall Length 37 1 2 953mm K Corner Facing Wall Width 53 1 4 1353mm L Framed Chase Ceiling 36 914mm Rigid 32 813mm Flex M Vent Centerline Height 30 762mm Rigid 26 660mm Flex G H I K J L Q O P N M 10 254mm dia Hole through wall Vent Opening for gas connection Top Header Drywall or other facing R Dimension ...

Страница 2: ...m Floor 1 25mm minimum J Framing Depth Vertical 19 1 2 495mm Vertical Rise 16 1 2 419mm Rigid 12 3 4 324mm Flex Horizontal K Corner Wall Length 37 1 2 953mm L Corner Facing Wall Width 53 1 4 1353mm M Framed Chase Ceiling 36 914mm Rigid 32 813mm Flex N Vent Centerline Height 30 762mm Rigid 26 660mm Flex The unit must be raised a minimum of 1 above the finished floor Dimension H H I minimum Dimensio...

Страница 3: ...rs are shown in the diagram below Mantel may be installed anywhere in the shaded area or higher Drywall Mantel Clearances 2 0 12 6 4 8 10 0 Side View Top of Unit 12 305mm 3 1 2 89mm 7 1 2 191mm A 3 76mm Standoff B C D Note If desired a non combustible mantel may be installed at a lower height Note Ensure the paint that is used on the mantel and the facing is heat resistant or the paint may discolo...

Страница 4: ...replace and vent system be installed only in accordance with these instructions Clearance Dimension Measured From A Front Floor Clearance min 1 25mm Underside of Unit B Sidewall 7 1 2 241mm Side of Unit C Ceiling room and or alcove 30 889mm Top of Unit D Alcove Width 48 1219mm Sidewall to Sidewall Minimum E Alcove Depth 36 914mm Front to Back Wall Maximum Flue Clearances to Combustibles Horizontal...

Страница 5: ...e supported every 3 feet If required by the external termination location the listed alternate termination caps may be used Important When installing Cabinet Mantels the wall thimble must be secured first and venting must be attached to unit before sliding into final position Alternate Horizontal Termination Caps Snorkel Terminations Snorkel Terminations For installations requiring a vertical rise...

Страница 6: ... must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall Maintain clearances to combustible materials Minimum of 1 pipe section between elbows Note Must use optional rigid pipe adapter when using Rigid Pipe Part 510 994 Unit must be raised by 1 when using Contemporary Faceplate Maximum 40 ft 12 2m Minimum 9 6 2 9m Minimum 8 6 2 6m Max 10 3m cen...

Страница 7: ...x 6 Min Vertical Venting with Three 3 90 Elbows Initial vertical section Two 45 elbows One 90 elbow Option V H H1 V V1 Maximum total pipe length of all sections must not exceed 30 feet Total horizontal sections must not exceed 8 feet Minimum of 1 foot between 90 elbows is required A 2 Min 3 Max 4 Min B 3 Min 4 Max 6 Min C 4 Min 5 Max 7 Min D 5 Min 6 Max 8 Min E 6 Min 7 Max 9 Min F 7 Min 8 Max 10 M...

Страница 8: ...ibles Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall A vent guard may be required as per local codes refer to Exterior Vent Termination Locations Note FPIDirectVentSystem Flex isonlyapprovedforhorizontal terminations P33 Gas Fireplace Unit must be raised by 1 when using Contemporary Faceplate Please refer to Exterior Ve...

Страница 9: ... Horizontal Venting with Three 3 90 Elbows Initial vertical section Two 45 elbows One 90 elbow Option V H V V1 H H1 Maximum total pipe length of all sections must not exceed 30 feet Total horizontal sections must not exceed 8 feet Minimum of 1 foot between 90 elbows is required A 2 Min 1 Max 3 Min 4 Max B 3 Min 2 Max 4 Min 5 Max C 4 Min 3 Max 6 Min 6 Max D 5 Min 4 Max 8 Min 7 Max E 6 Min 5 Max 10 ...

Страница 10: ... inlet air collar of the termination cap This appliance is designed to be attached to two 3 76mm co linear aluminium flex running the full length of the chimney See the Venting Arrangements for minimum and maximum heights Required Parts Part Description 946 529 Co linear DV Vertical Termination Cap 948 305 3 Flex 35 ft 946 563 Coaxial to Co linear Adapter Kit 510 994 Rigid Pipe Adapter 58dva E45 4...

Отзывы: