background image

34

Regency GF950L Gas Fireplace

installation

CL

CL

mm

99

1

Min.  height

(Rigid)

center

of hole

Diagram 7

Diagram 5

7)

  Ensure that  the pipe clearances to combustible 

materials are maintained (Diagram 5). Install 
the termination cap.

Note:  If  installing  termination  on  a  siding 

covered wall, a siding standoff or furring 

strips must be used to ensure that the 

termination  is  not  recessed  into  the 

siding.

 

The  four  wood  screws  provided  should  be 
replaced with appropriate fasteners for stucco, 
brick, concrete, or other types of sidings.

8)

  Before connecting the horizontal run of vent pipe 

to the vent termination, slide the Wall Thimble  
over the vent pipe. The wall thimble is required 
for all horizontal terminations.

9)

  Slide the appliance and vent assembly towards 

the wall carefully inserting the vent pipe into the 
vent cap assembly. It is important that the vent 
pipe extends into the vent cap sufficient distance 
so  as  to  result  in  a  minimum  pipe  overlap  of 
32mm. Secure the connection between the vent 
pipe and the vent cap.

10)

 Install wall thimble in the center of the framed  

hole and attach with wood screws (Diagram 7).

Install    the  flue    system    according    to    the  
manufacturer's  instructions  included  with  the 
components.

1)

  Set the unit in its desired location. Check to 

determine if wall studs or roof rafters are in 
the way when the flueing system is attached. 
If this is the case, you may want to adjust the 
location of the unit. Rough in the gas preferably 
on the right side of the unit and the electrical 
(junction block is on the left side) on the left.

2)

  Simpson Dura Vent Flue pipe and fittings are 

designed with special twist-lock connections 
to connect the flueing system to the appliance 
flue  outlet.  A  twist-lock  appliance  adaptor  is 
required.

3)

  In  conjunction  with  the  Simpson  Direct Vent 

Pro system, install the adaptor after the unit 
is set in its desired location. Put a bead of Mill 
Pac inside the outer section of the adapter and 
a bead of Mill Pac on the inner collar. Slip the 
adapter over the existing inner and outer flue 
collar. Fasten to the outer collar only with the 
3 supplied screws (drilling pilot holes will make 
this easier).

4)

  Level the fireplace and fasten it to the framing 

using nails or screws through the top and side 
nailing strips.

Note:   For best results and optimum 

performance with each approved 

venting system, it is highly 

recommended to apply “Mill-Pac” 

sealant to every inner pipe connection. 

Failure to do so may result in drafting 

or performance issues not covered 

under warranty. 

Diagram 2

Horizontal  runs  of  vent  must  be  supported 

every 0.9 metre. Wall straps are available for 

this purpose.

6)

  Mark the wall for a square hole.-see chart to left 

for size. The center of the square hole should line 
up with the center-line of the horizontal pipe. Cut 
and frame the square hole in the exterior wall 
where the vent will be terminated. See diagram 
2 for center line requirements.

 

If the wall being penetrated is constructed of 
non-combustible  material,  i.e.  masonry  block 
or  concrete,  an    203mm  diameter    hole  is 
acceptable.

Note:

  a)

  The horizontal run of vent must have a 

6mm rise for every 305mm of run towards 

the termination. Never allow the vent to 

run downward. This could cause high 

temperatures and may present the possibility 

of a fire. 

 

b)

  The location of the horizontal vent 

termination on an exterior wall must meet 

all local and national building codes, 

5)

  Assemble the desired combination of pipe and 

elbows to the appliance flue outlets and secure.

Recommended Framed Opening Size

Flue Size

Framing Size

102mm x 175mm

254mm x 254mm

Horizontal Top*

76mm*

Horizontal Side

51mm

Horizontal Bottom

51mm

Vertical Vent

51mm

Minimum Flue Clearances

to Combustibles

UNIT INSTALLATION WITH HORI-
ZONTAL TERMINATION 
102MM X 175MM FLUEING

(Rigid Flue Systems)

Below are the recommended framing dimensions 

(inside measurements) for the 102mm X 168mm  

rigid vent terminations - for use with a wall 

thimble.

* Clearances noted below must be maintained; 

except when passing through a wall, ceiling or at the 

termination where the use of a firestop or wall thimble 

reduces clearance to 38mm.

"THIS UNIT MUST ALWAYS 

TERMINATE / FLUE 

DIRECTLY TO THE OUTDOORS."

NOTE:

"NOT INTENDED FOR 

FIREPLACE INSERT". 

Содержание GF950L-LP

Страница 1: ... Please keep these instructions for future reference MODELS GF950L NG GF950L LP GF950L ULPG LISTINGS AND CODE APPROVALS These gas appliances have been tested in accordance with AS 5263 0 AS NZS 5263 1 3 and have been certified by the AustralianGas Associationforinstallationand operation as described in these Installation and Operating Instructions Must be installed as per AS NZS5601 Your unit shou...

Страница 2: ... applied and will ignore this special command from the Remote after the first 30 seconds To match the control box to the remote follow the steps below 1 Remove a battery from the remote handset 2 Turn off main power to the control box by turning off the isolation switch near the heater or at the switch on the GPO to the heater 3 Wait 30 seconds approximately 4 Reconnect main power to the control b...

Страница 3: ...on 27 Flueing Arrangement for Horizontal Terminations 27 Flueing Arrangements 28 Horizontal Termination Flex 28 Horizontal terminations 29 Rigid Pipe 4 x 6 5 8 102mm x 175mm 29 Horizontal Terminations 30 Rigid Pipe 4 x 6 5 8 102mm x 175mm 30 Vertical terminations 31 Rigid Pipe 4 x 6 5 8 102mm x 175mm 31 Flueing Arrangement for Vertical Terminations 32 Direct flue zero Clearance top exit vertical f...

Страница 4: ...O NOT STORE CHEMICALS OR FLAMMABLE MATERIALS NEAR THIS APPLIANCE DO NOT OPERATE WITH PANELS COVERS OR GUARDS REMOVED FROM THIS APPLIANCE 908 602c Part 919 841 Colour Black on Grey Size 100 7 W x 2 7 H Dec 06 17 draft for approval Apr 30 18 Added Gas Consumption Low Manifold Pressure Low Values Serial Number Regency Gas Fireplace 463 Electrical 240V 50 Hz 919 841 Gas Type NG LP ULPG Model GF950L NG...

Страница 5: ...332mm 1000mm 480mm 1034mm 142mm 436mm Black Premium Glass Fascia Unit with Finishing Trim Flush Finish Unit shown with Black Flat Fascia DIMENSIONS dimensions UNIT DIMENSIONS 996mm 1091mm 113mm 540mm 890mm 332mm 159mm 726mm 796mm 933mm 14mm 523mm 560mm 258mm 500mm 74mm ...

Страница 6: ...e 10 Be aware of electrical wiring locations in walls and ceilings when cutting holes for termination THIS UNIT MUST ALWAYS TERMINATE FLUE DIRECTLY TO THE OUTDOORS IMPORTANT MESSAGE SAVE THESE INSTRUCTIONS The GF950L Direct Vent Fireplace must be installed in accordance with these instructions Carefully read all theinstructionsinthismanualfirst Consultthe authority having jurisdiction to determine...

Страница 7: ...as fireplace section b Clearances to Combustibles Refer to Clearances section c Mantle Clearances Refer to Mantel Clearances section d Framing FinishingRequirements Refer to Framing Finishing section e Flueing Requirements Refer to Flueing section 2 Assemble the standoffs and nailing strips Referto UnitAssemblyPriortoInstallation 3 Slide unit into place 4 Install vent Refer to Flueing Arrangement ...

Страница 8: ...e Opening Hot Air Outlet B Sidewall on one side 146mm Side of Fireplace Opening C Ceiling room and or alcove 1003mm Top of Fireplace Opening D Mantel Depth max 305mm 420mm Above Fireplace Opening E Alcove Width 1480mm Sidewall to Sidewall Minimum F Alcove Depth 787mm Front to Back Wall Maximum G From Floor 605mm Top of Fireplace Opening Hot Air Outlet Note 0 No hearth required Installed close to c...

Страница 9: ...ishing option A minimum thickness of 10mm 19mm combustible facing board is required when choosing the combustible flush finishing option Note must maintain 13mm air gap all around the perimeter of the appliance when choosing this option D G H Non Combustible Facing Header F E I J K L Flex or Rigid Pipe Drywall or other facing C C A B C Timber Studs Finished Floor A B C Timber Studs Finished Floor ...

Страница 10: ...e The nailing strips can be adjusted back up to 38mm to allow for varying thicknesses in non combustible material wall finishes INSTALLATION ACCESS PANEL The unit is equipped with a removable access panel for pre finish installation of optional components this panel is located on the lower front face 1 Remove 4 screws to remove access panel 2 Easier access to gas connection with panel removed 3 In...

Страница 11: ...iling strip is fixed during transit to the rear of the appliance Do not place any reinforcement in front of header and behind finishing material The nailing strip must be used It is fixed during transit to the rear of the unit NOTE The appliance must be installed on a flat solid continuous surface For example a wood metal or concrete floor In a raised on the wall application the appliance must be ...

Страница 12: ...aint that is used on the mantel and the facing is high quality or the paint may discolour COMBUSTIBLE MANTEL LEG CLEARANCES Mantel leg combustible finishing clearances as per diagram Combustible Material 152mm 305mm 0 To Unit Base 618mm 254mm Top of Fireplace Opening 508mm 305mm 407mm 178mm Combustible Stud On Edge Nailing Flange Combustible facing min 10mm max 19mm 234mm 200mm 100mm 309mm Allowab...

Страница 13: ...s panel removed 4 Reinstall access panel line up 2 upper tabs and secure in place with 4 screws Note Access panel is no longer usable accessible once facing material installed Installation Access Panel Tab locations on access panel Remove 7 standoffs REMOVE TOP NAILING STRIPS STANDOFFS Remove the top nailing strip standoff by removing 4 screws in locations shown in Diagram to the right then lift of...

Страница 14: ... Ensure the paint that is used on the mantel and the facing is high quality or the paint may discolour NON COMBUSTIBLE MANTEL LEG CLEARANCES Mantel leg Non combustible finishing clearances as per diagram Flushed Finish Allowablemantel leg projection 181mm 254mm 330mm 38mm MANTELLEG 102mm 178mm Allowablemantel leg projection 181mm 254mm 330mm 38mm MANTELLEG 102mm 178mm Allowablemantel leg projectio...

Страница 15: ... sides must also be used NOTE Theappliancemustbeinstalledon aflat solid continuoussurfaceFor exampleawood metalorconcrete floor In a raised on the wall ap plication the appliance must be installed on a metal or wood panel extending the full width and depth of the appliance 796mm 605mm 1165mm Non combustible Combustible Combustible Steel Stud on edge Timber Stud Timber Stud 159mm 446mm Non Combusti...

Страница 16: ...m Raised Height 100mm E Corner Wall Depth 1564mm F Corner Facing Wall Width 2212mm G Gas Connection Opening Height 38mm H Gas Connection Height 67mm I Gas Connection Inset 44mm J Gas Connection Opening Width 89mm K Zero Clearance Box Height 1138mm L Zero Clearance Box Width 560mm NOTE The unit and box must be raised a minimum of 100mm for the Zero Clearance fascia to fit NOTE The zero clearance bo...

Страница 17: ...ANCE BOX FRAMING AND COMBUSTIBLE REQUIREMENTS 1073mm 941mm 841mm Raise 100mm Min Material Thickness Faceplate Unit Slots 1 2 3 The following material thicknesses may be accommodated by installing the Faceplate on slot 1 2 or 3 1 10 12mm 2 16 18mm 3 22 24mm ...

Страница 18: ...re the box to the framing with 2 screws on each side and the 2 holes on the base of the box 4 Slide the unit into place while guiding the unit flue assembly back into position on top of the unit and secure to the zero clearance box with 2 screws on each side 5 Install flex venting through either top or back of zero clearance box Remove either top or back knockout Slide Zero Clearance box into fram...

Страница 19: ...ed without any sag Heat deflector must overhang front of TV by 51mm Follow mantel clearance chart for install height and heat deflector depth Note The TV mounting bracket can not be secured directly to the appliance It must be secured to framing The TV depicted in the picture may need to be higher depending on the style of TV mounting bracket used The mounting bracket shown is a simple single stri...

Страница 20: ...ireplace installation M 5 3 4 146mm 14 9 16 370mm DETAIL M SCALE 1 6 INSTALLING A TV ARTWORK ENCLOSED ABOVE THE UNIT Maximum recess is 146mm Minimum height is 370mm from top lip Ensure framing does not interfere with venting ...

Страница 21: ... bottom 2 at top and 2 on sides as shown NOTE Ensure the flat side of the steel stud is facing the timber framing 468 025 Flat side out 5 Secure horizontal steel header stud 468 039 with 2 screws per side as per diagram 6 Slide the unit into position Hook up gas flueing electrical and conversion kit if purchased prior to installing the remaining steel studs 7 Secure the upper horizontal steel stud...

Страница 22: ...d with non combustible required materials to specific dimensions above and aroundtheunits Thisisduetotheseareasreachinghighertemperature levels than required acceptable for a combustible material To obtain the best most durable finish around your fireplace this calls for a high level of care and attention to the preparation and finish around this appliance using only the highest quality materials ...

Страница 23: ...essive condensation on glass doors poor flame package carbon blue flames etc These are not product related issues 3 The unit does not have to be completely enclosed in a chase You must maintain clearances from the flue to combustible materials See Clearances section Combustible materials can be laid against the side and back standoffs and the appliance base 4 Non combustible material ie tile slate...

Страница 24: ...24 Regency GF950L Gas Fireplace installation EXTERIOR FLUE TERMINATION LOCATIONS FIGURE 6 2 in part LOCATION OF FLUE TERMINALS OF BALANCED FLUE AS NZ 5601 ROOM SEALED FAN ASSISTED OR OUTDOOR APPLIANCE ...

Страница 25: ...iances over 250MJ h input 1500 1500 All fan assisted flue appliances in the direction of discharge 1500 k From a mechanical air inlet including a spa blower 1500 1000 n Vertically below an openable window non mechanical air inlet or any other opening into a building iwth the exception of sub floor ventilation Space heaters up to 50MJ h input 150 150 Other appliances up to 50 MJ h input 500 500 App...

Страница 26: ...efer to the following instructions 1 Remove the glass door and inner panels see instructions in this manual 2 Remove6screws 3front 3back toremoveheatbaffletoaccessrestrictor plate 3 Remove the screws that hold the flue restrictor in place FLUE RESTRICTOR POSITION Heat Baffle 4 Adjust the flue restrictor plate to the required flue restrictor position as per the diagrams shown below 5 Once the flue ...

Страница 27: ...EMENT FOR HORIZONTAL TERMINATIONS The diagram shows all allowable combinations of vertical runs with horizontal terminations using one 90o two 45o elbows equal one 90o elbow Note Must use optional rigid pipe adapter Part 510 994 when using Simpson Dura Vent Only Maintain clearances to combustibles as listed in Clearances section Horizontal flue must be supported every 0 9m A flue guard should be u...

Страница 28: ...m flexible outer liner Kit length 2 102mm flexible inner liner Kit length 3 spring spacers 4 thimble 5 AstroCap termination cap 6 screws 7 tube of Mill Pac 8 plated screws 9 S S screws 8 x 1 1 2 drill point 946 516 3 m FLUEING ARRANGEMENTS HORIZONTAL TERMINATION FLEX Regency Direct Vent System These flueing systems in combination with GF950L have been tested and listed as a Direct Vent system by A...

Страница 29: ...d add 51mm When using Rigid Flue other than Simpson Dura Vent 3 screws must be used to secure rigid pipe to adaptor WARNING Do not combine flueing components from different flueing systems However use of the the AstroCapTM and FPI Riser is acceptable with all systems ThisproducthasbeenevaluatedbyIntertek forusingaRigidPipeAdaptorinconjunction with Duravent Direct Vent The FPI AstroCapTM and Regenc...

Страница 30: ...or two 45o elbows is permitted 2 Minimum distance between elbows is 305mm Maintain clearances to combustibles as listed in the Clearances section Horizontal vent must be supported every 0 9m Must use optional rigid pipe adaptor Part 510 994 when using Duravent systems A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes Flex system can only...

Страница 31: ...or installations using FPI flueing systems as well as Simpson Dura Vent Direct Vent is a proprietary trademark of FPI Fireplace Products International Ltd Dura Vent and Direct Vent are registered and or proprietary trademarks of Simpson Dura Vent Co Inc Galvanized pipe is desirable above the roofline due to its higher corrosion resistance Continue to add pipe sections through the flashing until th...

Страница 32: ...to combustibles as listed in the Clearances section in the manual Horizontal flue must be supported every 1M Refer to the Flue Restrictor Position section for details on how to change the flue restrictor from the factory setting of Set 0 or Set 3 if required Note For ULPG Flue Restrictor Set to 0 75mm open FLUEING ARRANGEMENT FOR VERTICAL TERMINATIONS Vertical Venting with Two 2 45o Elbows 6 7m 4m...

Страница 33: ...using non combustible brac ing to stop movement On penetration of roof fit an appropriate flashing or weather seal to suit the roofing material ensure all joints outside are sealed with appropriate sealer 6 Fit gas cowl 46DVA VCH 9 or flomet cap 946 651 ensuring inner and outer flue pipes are sealed 7 Start heater and run for at least 15 minutes to check flue seal If operational issues are noted c...

Страница 34: ...e existing inner and outer flue collar Fasten to the outer collar only with the 3 supplied screws drilling pilot holes will make this easier 4 Level the fireplace and fasten it to the framing using nails or screws through the top and side nailing strips Note For best results and optimum performance with each approved venting system it is highly recommended to apply Mill Pac sealant to every inner ...

Страница 35: ...he cap indicating which way is up This will position the termination cap with proper down slope for draining water Fasten the cap to the outer wall with the 4 supplied screws 6 Pull the centre inner and outer flex liner out enough to slip over the flue collars of the fireplace You may wish to cut the liner shorter to make it more workable Do not bend liner more than 90o The liners must slip over t...

Страница 36: ... elbows and possible separation Metal Wall straps can be used Do not combineflueingcomponentsfromother manufacturers Galvanizedpipeisdesirableabovetheroofspace due to its higher corrosion resistance Continue to add pipe sections through the flashing until the height of the flue cap meets the minimum height requirements specified in Dia 4 or local codes Note that for steep roof pitches the vertical...

Страница 37: ... local authorities When using copper or flex connectors use only approved fittings Always provide a union so that gas lines can be easily disconnected for servicing Flare nuts for copper lines and flex connectors are usually considered to meet this requirement NOTE A shutoff valve should be supplied in or near the unit or as per local codes for ease of servicing this appliance GF950L NG SYSTEM DAT...

Страница 38: ... SIGMA 845 EARTH EARTH JUMPER 2 12 1 10 11 9 RED BLUE GREEN BROWN 4 5 3 2 1 YELLOW 3 YELLOW BLUE EARTH BROWN LOW SPEED WHITE RED BLACK FAN 5 3 4 BROWN VIOLET BLUE RED 1 3 2 4 WHITE YELLOW VIOLET BLACK 5 6 1 2 BROWN BLUE VIOLET RED BLACK WHITE YELLOW VIOLET ORANGE ORANGE MODULATING 7 8 6 5 4 3 VALVE RESET SWITCH NC BLACK BLACK 2 1 COIL MODULE SPARK MODULE EARTH MODULE FLAME ORANGE ORANGE 5 4 ORANGE...

Страница 39: ...5mm LP 13mm ULPG Full Open Note Any damage due to carboning resulting from improperly setting the aeration controlsisNOTcoveredunderwarranty 845 S I T VALVE DESCRIPTION 1 On Off Solenoid Valve EV1 2 On Off Solenoid Valve EV2 3 Inlet Pressure Test Point 4 Outlet Pressure Test Point 5 ConnectionforPressureRegulator Combustion Chamber Compensation 6 PressureRegulatorforMinimumandMaximum Outlet Pressu...

Страница 40: ...ire hazard 6 Plan the location of the fireplace and the warm air duct runs see diagram 1 as a guide for possible duct runs and locations Diagram 1 Guide for possible air duct runs and locations Keep duct length and number of bends to a minimum Maximum duct length is 9 0m The Extension Kit contains a maximum of up to 4 5m Please purchase the Fan Duct Extension Kit to increase the 9 0m MINIMUM FRAMI...

Страница 41: ...n Housing See diagram 4 8 Remove the knock out on the top of the unit Cut out the insulation Remove the second and thirdknockout botharebelowthetopknockout 9 On the top of the unit bend the 3 tabs up Insert the Duct collar Secure the collar to the 3 tabs with screws 10 Attach fan duct to the unit Slide the ducting over the collar and secure with screws 11 Final step double check the fan ducting co...

Страница 42: ...M Caution Ensure that the wires do not touch any hot surfaces and are away from sharp edges AlternateSwitches Mayusethefollowing Checkwithlocalauthoritiesandelectrician CLIPSAL 203 2E45 OUD Dimmer CLIPSAL 2031 VF3CSF 3 Speed CAUTION Labelallwirespriortodis connection when servicing controls Wiringerrorscancauseimproperand dangerous operation Wire Nut Wire Nut Wire Nut Rheostat Wire Nuts Wire Wire ...

Страница 43: ...der warranty Log kit 466 930 contains the following pieces 1 Line up locators on Log 1 with corresponding locators on Log Tray as shown in Diagram 2 2 Line up locators on Log 2 with corresponding locators on Ceramic Log Burner as shown in Diagram 3 3 Line up locator on Log 3 with corresponding locator on Ceramic Log Burner as shown in Diagrams 4 and 5 Diagram 2 Diagram 3 Diagram 4 Diagram 5 3 4 5 ...

Страница 44: ... Log 3 as shown in Diagram 9 8 Line up locator on bottom of Log 7 with locator on Ceramic Log Burner as shown in Diagram 10 6 Log 5 final position shown in Diagram 8 6 Log 8 in final position shown in Diagram 11 Place supplied embers over burner screw holes in locations shown below Diagram 7 Diagram 8 Diagram 9 Diagram 10 Diagram 11 Log 8 and ember locations Diagram 6 3 6 1 3 8 7 4 4 1 1 2 2 2 4 5...

Страница 45: ...ce 3 Reverse steps to reinstall 1 Remove burner side panels by lifting them up and out 2 Remove front trim piece see instructions above 3 Remove two 2 screws in locations shown below to release panel clips 4 Remove panels by sliding out 5 Reverse steps to reinstall Front Trim Piece Panel Clip Screw Locations Panel Clip Diagram 1 Front Trim Screw Locations INNER PANEL REMOVAL INSTALLATION FRONT TRI...

Страница 46: ...first mounting slot the one clos est to the door frame overlay out of the 3 so that the faceplate and door frame overlay are flush with one another See diagram 2 1 Install the fascia to the unit by hooking the left and right side mounting brackets into the mounting slots at the side ofthe firebox as shown below Diagram 3 Diagram 4 Deflector Installed NOTE When installing the stainless steel fascia...

Страница 47: ...en Mesh over Inner Door Frame as shown in Diagram 1 3 Install Screen and Inner Door Frame to unit over glass door frame as shown in Diagram 3 Lower gently once in position over glass door frame 2 Bend Tab on Screen Mesh to 90º as shown in Diagram 2 Secure to Inner Door Frame with one 1 screw as shown in Diagram 2a Diagram 1 Diagram 3 Diagram 2 Diagram 2a ...

Страница 48: ... is to accommodate any finishing that protrudes slightly beyond the faceplate Warning Turn off the unit by way of the wall switch or remote Allow unit to cool at least 10 min prior to removing the faceplate Diagram 1 Glass Surround Install Diagram 3 Final Install Diagram 2 adjustments 1 4 6mm 1 2 13mm Use first notch in bracket for standard installation 919 615a 05 27 16 1 OPTIONAL FINISHING TRIM ...

Страница 49: ... Whentheglassiscoldandtheappliance is lit it may cause condensation and fog the glass This condensation is normal and will disappear in a few minutes as the glass heats up DO NOT ATTEMPT TO CLEAN THE GLASS WHILE IT IS STILL HOT DO NOT BURN THE APPLIANCE WITH OUT THE GLASS FRONT IN PLACE FAN OPERATION Set the fan speed on the control panel at the top rear of the unit to adjust to the desired speed ...

Страница 50: ...ames with slight yellow tips may exhibit slight carbon deposition FOR YOUR SAFETY READ BEFORE LIGHTING SUITABLE ONLY FOR INDOOR INSTALLATION A BEFORE LIGHTING smell all around the appliance areaforgas Besuretosmellnexttothefloorbecause some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use ...

Страница 51: ...n in Diagram 1 4 Remove burner by removing 2 screws in locations shown below 7 Loosen three 3 screws to remove heat deflector shown in Diagram 5 8 Remove two 2 screws to remove fan shown in Diagram 6 9 Reverse steps to reinstall fan 6 Remove access panel by removing eight 8 screws in locations shown in Diagram 4 Diagram 3 Log Tray screws Diagram 5 Heat Deflector Screws Diagram 6 Fan Screws Diagram...

Страница 52: ...pection of the venting system semi annually Recommended areas to inspect as follows 1 Check the Flueing System for corrosion in areas that are exposed to the elements These will appear as rust spots or streaks and in extreme cases holes These components should be replaced immediately 2 Remove the termination cap and shine a flashlight down the Flue Remove any bird nests or other foreign material R...

Страница 53: ...after approx 1 minute Then turn on again NOTE On initial light up this may occur a number of times until any residual air is purged from the gas line through the burner system It is essential the required waiting time as stated in the manual is observed prior to attempting re ignition Turn burner switch to ON fans will operate within 5 secs listen for audible click first from After resetting igniti...

Страница 54: ... other lower door latch 6 Pull the bottom of the door towards you until the door is angled away from the firebox by about 30 Lift the door up and over the upper door hooks 7 To install the glass door reverse steps 1 Insert the door tool into the lower door latch WARNING Do not operate the appliance with the glass panels removed cracked or broken Replacement of the glass panels should be done by a ...

Страница 55: ... tray and reverse steps Diagram 4 Valve Tray Screw Locations Diagram 5 Valve Tray Removal 1 Remove faceplate inner frame glass door front trim piece and inner panels see instructions in this manual 2 Remove logs 3 Remove burner side panels by lifting out as shown in Diagram 1 4 Remove burner by removing 2 screws in locations shown below Diagram 3 Log Tray screws Diagram 1 Burner Side Panels Diagra...

Страница 56: ...A N A N A N A N A N A N A 910 084 Control Box N A N A N A 911 101 Control Box N A N A N A N A N A N A 910 527 Manual Control Switch N A N A N A N A N A N A 910 080 Valve 910 521 Control Box Cable 1 910 522 Control Box Cable 2 910 523 Control Box Cable 3 910 525 Control Box Cable 4 N A 2 1 1 3 N A 2 N A N A 910 912 Ignition Module to Valve Cable N A N A 911 183 Reset Switch N A 910 083 Ignition Mod...

Страница 57: ... Flame Sense N S 904 658 Inlet Flex Line Gas SS Steel 24 inch N S 932 009 Gas Line From OutletValveTo Burner Orifice N S 904 599 Fitting Elbow 90 Degree N S 904 600 Fitting Elbow 90 Degree N S 904 650 Fitting 1 8 Brass Pipe Adaptor N S 904 771 Fitting 3 8 Tube to 1 2 Pipe N S 904 911 Fitting Connector 1 2 MIP x 1 2 Flare N S 936 170 Burner Orifice Gasket N S 911 113 Switch On Off W CAT 5 Cable 3 F...

Страница 58: ...58 Regency GF950L Gas Fireplace PARTS LIST parts list 15 26 10 9 12 17 4 5 18 23 2 1 19 24 16 27 7 13 25 25 22 13 11 20 12 8 6 3 MAIN ASSEMBLY ...

Страница 59: ...reen 467 932 Inner door frame Stainless w Screen 467 926 Inner door frame Gloss Black w Screen 33 467 544 Door Frame Overlay Black 34 468 934 Fascia and Door Frame Black w Screen 468 936 Fascia and Door Frame Stainless Steel w Screen 468 951 Fascia Black Glass not shown N S 468 900 Steel Stud Framing Kit N S 468 928 Finishing Trim ...

Страница 60: ...60 Regency GF950L Gas Fireplace NOTES notes ...

Страница 61: ...omponents Ignition Control Boards Wiring Switches Fans Fan Control Module Battery Pack Remote Control Systems 1 Enamel Panels 1 Venting Venting Components 1 All Stainless steel surrounds 1 All Firebox Media Crystals Fire beads Volcanic Ceramic Spa Stones 1 All hardware 1 Mesh Glass Safety Barriers 1 Accent Light Bulbs 1 Glass Crazing 1 After the original warranty coverage for any of the parts abov...

Страница 62: ...eneral practice of FPI to charge for larger higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated for manufacturer defect If a consumer has a unit installed outside an accredited distributor dealer or pre approved service agent s service area or the closest approved service agent is situated more than thirty 30 kilometres from the insta...

Страница 63: ... movement expansion and contraction of the steel is normal and is not covered under the terms of this warranty Freight damages for products or parts are not covered under the terms of the warranty Porcelain Enamel Absolute perfection is neither guaranteed nor commercially possible Any chips must be reported and inspected by the authorised selling dealer within three 3 days of installation Any dama...

Страница 64: ...o at the option of the supplier one or more of the following i replacement of the goods or the supply of equivalent goods ii the repair of the goods iii the payment of the cost of replacing the goods or of acquiring equivalent goods or iv equivalent goods or v the payment of the cost of having the goods repaired b To the extent that services supplied by the supplier are services other than service...

Страница 65: ...rvices Fireplace Products Australia Pty Ltd 1 3 Conquest Way Hallam VIC Australia 3803 Phone 61 3 9799 7277 Fax 61 3 9799 7822 To obtain warranty service in Western Australia and or New Zealand please contact one of our authorised distributors in those areas Western Australia Air Group Australia 28 30 Division St Welshpool WA Australia 6106 Phone 08 9350 2200 Fax 08 9353 4225 New Zealand Aber Hold...

Страница 66: ...66 Regency GF950L Gas Fireplace ...

Страница 67: ... to us and we will register the warranty for you It is important you provide us with all the information below in order for us to serve you better Warranty Registration Form or Register online immediately at the above Web Site Warranty Details Serial Number required Purchase Date required mm dd yyyy Product Details Product Model required Dealer Details Dealer Name required Dealer Address Dealer Ph...

Страница 68: ......

Страница 69: ...Regency GF950L Gas Fireplace 69 NOTES notes ...

Страница 70: ...70 Regency GF950L Gas Fireplace NOTES notes ...

Страница 71: ...Regency GF950L Gas Fireplace 71 ...

Страница 72: ...ion Dealer Name Address _______________________________________________ ___________________________________________________________________ Installer ____________________________________________________________ Phone ____________________________________________________________ Date Installed _______________________________________________________ Serial No _________________________________________...

Отзывы: