38

     | 

ACV40E City Series

installation

Horizontal Terminations

Rigid Pipe 

102mm x 175mm

The diagrams below shows examples of horizontal termination arrangements using one, two, or three 90

o

 elbows (two  45

elbows equal one 90

o

 elbow) 

1. A maximum of three 90

o

 elbows are permitted.

2.  Minimum distance between elbows is 305mm.

•  

Maintain clearances to combustibles as listed in the "Clearances" section.

•   Horizontal vent must be supported every 1.8m.
•   Firestops are required at each floor level and whenever passing through a wall.
•   Must use optional rigid pipe adaptor (Part# 510-994) when using rigid pipe vent systems.
•   A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
•  Flex system can only be used up to 3m - otherwise rigid flueing must be used.
 

Horizontal Flueing with Two (2) 90

o

 Elbows

One 90

o

 elbow = Two 45

o

 elbows.

Option

V

H + H1

W it h   t h e se   o p ti o n s, 
maximum total pipe length 
is  9.1m  with  minimum  of 
1.8m  feet  total  vertical 
and  maximum  2.4m  total 
horizontal.

Please note minimum 
0.3m between 90

o

 elbows 

is required.

Min.

Max.

 A)

0.3m

0.6m

B)

0.6m

1.2m

C)

0.9m

1.5m

D)

1.2m

1.8m

E)

1.5m

2.1m

F)

1.8m

2.4m

Restrictor Set 0 - Factory Setting

Horizontal Flueing with Three (3) 90

o

 Elbows

One 90

o

 elbow = Two 45

o

 elbows.

Option

V

H

V + V1

H + H1

With these options, 
max.  total  pipe 
length is 9.1m with 
min.  of  3.6m  total 
vertical  and  max. 
2.7m total horizon-
tal.

Please note min. 
0.3m between 90

 

elbows is required.

Min.

Max.

Min.

Max.

A)

0.3m

0.3m

0.6m

0.6m

B)

0.3m

0.6m

0.9m

0.9m

C)

0.6m

0.6m

1.5m

1.2m

D)

0.9m

0.6m

2.1m

1.5m

 E)

1.2m

0.9m

2.7m

1.8m

 F)

1.5m

1.2m

3m

2.1m

G)

1.8m

1.5m

3.3m

2.4m

H)

2.1m

1.8m

3.6m

2.7m

Restrictor Set 0 - Factory Setting

Содержание City New York View 40 Series

Страница 1: ...ervice must be performed by a qualified installer service agency or the gas supplier Warning Fire or explosion Hazard failure to follow safety warnings exactly could result in serious injury death or property damage 920 110 03 03 20 Installer Please complete the details on the back cover and leave this manual with the homeowner Homeowner Please keep these instructions for future reference LISTINGS...

Страница 2: ...r additional information co A BEFORE LIGHTING smell heavier than air and will s WHAT TO DO IF YOU SMELL Do not try to light any a Do not touch any electri Immediately call your ga If you cannot reach your B Do not use this appliance i appliance and to replace a This appliance needs fresh a and ventilation air 1 Ensure the Main switch is in t 2 Press and release the ON OFF using the remote the unit...

Страница 3: ...e Height Dimension may vary depending on the height of the leveling legs Note These units are non load bearing ALL PICTURES DIAGRAMS SHOWN THROUGHOUT THIS MANUAL ARE FOR ILLUSTRATION PURPOSES ONLY ACTUAL PRODUCT MAY VARY DUE TO PRODUCT ENHANCEMENTS ...

Страница 4: ...ening B2 Opening Height 383mm Bottom Top of Fireplace Opening C Sidewall on one side 216mm Side of Fireplace Opening D Mantel Depth max E Alcove Width 2134mm Sidewall to Sidewall Minimum F Alcove Depth 914mm Front to Unit Maximum G Ceiling in front of fireplace 953mm Top of Fireplace Opening H Convection Air Outlet Top of Enclosure J Convection Air Outlet Opening Offset 0 76mm Max offset from top ...

Страница 5: ...n in the diagram on the right Mantel Leg Clearances Combustible mantel leg clearances as per diagram 254 0 229mm 383mm 254 508 Top of Fireplace Opening 305mm 13mm Plasterboard timber timber panel etc To Bottomof Fireplace Opening 130mm 127 305mm 102mm Allowable mantel MANTEL LEG leg projection 178mm 216mm 51mm ACV40E ...

Страница 6: ...ning Height 51mm J Gas Connection Height 106mm K Gas Connection Inset 330mm L Gas Connection Opening Width 89mm Note A combined minimum of 774 square centimetres of open area is required for the convection air outlet to cool the enclosure Ensure clearances for Convection Air Outlets are met See clearances ACV40E single sided in this manual as there are different methods as to how this can be achie...

Страница 7: ...30 ACV40E City Series installation TV Recessed into Wall Maximum TV Recess TV Flush with Hearth ACB40E shown ACB40E shown ...

Страница 8: ...e 90o two 45o elbows equal one 90o elbow Note Must use optional rigid pipe adapter Part 510 994 when using Rigid Pipe Flueing Systems Maintain clearances to combustibles as listed in Clearances section Horizontal vent must be supported every 0 9 metres Firestops are required at each floor level and whenever passing through a wall A vent guard should be used whenever the termination is lower than t...

Страница 9: ...ex Vent 102mm x 173mm These flueing systems in combination with the ACV40E Direct Vent Gas Fireplace have been tested and listed as a direct vent heater system The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in Exterior Vent Termination Locations section Regency Direct Vent Flex System Termination Kits includes all the parts needed to ins...

Страница 10: ...ndoff is required it must be used with vinyl siding measure to outside surface of wall without siding and add 51mm When using Rigid Flue other than Simpson Dura Vent 3 screws must be used to secure rigid pipe to adaptor WARNING Do not combine flueing components from different flueing systems However use of the the AstroCapTM and FPI Riser is acceptable with all systems Thisproducthasbeenevaluatedb...

Страница 11: ...can only be used up to 3m otherwise rigid flueing must be used Horizontal Flueing with Two 2 90o Elbows One 90o elbow Two 45o elbows Option V H H1 With these options maximum total pipe length is 9 1m with minimum of 1 8m feet total vertical and maximum 2 4m total horizontal Please note minimum 0 3mbetween90o elbows is required Min Max A 0 3m 0 6m B 0 6m 1 2m C 0 9m 1 5m D 1 2m 1 8m E 1 5m 2 1m F 1...

Страница 12: ...bow Vent must be supported at offsets Minimum distance between elbows is 305mm Maintain clearances to combustibles as listed in the Clearances section Horizontal vent must be supported every 1 2m Firestops are required at each floor level and whenever passing through a wall Must use optional rigid pipe adaptor Part 510 994 when using rigid pipe vent systems Refer to the Vent Restrictor Position se...

Страница 13: ...over 10 12 to 11 12 0 99 over 11 12 to 12 12 1 22 over 12 12 to 14 12 1 52 over 14 12 to 16 12 1 83 over 16 12 to 18 12 2 13 over 18 12 to 20 12 2 29 over 20 12 to 21 12 2 44 Pipe Length Storm Collar Flashing Ceiling Firestop Rigid Pipe Adapter High wind cap This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with Duravent Direct Vent Selkirk Direct Temp Ameri...

Страница 14: ...evel and whenever passing through a wall Must use optional rigid pipe adaptor Part 510 994 when using rigid pipe vent systems Vertical Flueing with Three 3 90o Elbows One 90o elbow Two 45o elbows V H1 H V1 Option V H H1 V V1 With these options max totalpipelength is 9 1m with min of 3m total vertical and max 2 4m total horizontal Please note min 0 3m between 90o elbows is required Min Max Min A 0 ...

Отзывы: