50
|
City Series ACV60E
installation
03.10.21
920-380
Page 2
127 mm x 203 mm Flueing - Vertical Flex Vent Kit (946-772)
Vertical Termination
Diagram 4
14. Put a bead of caulking on the exterior between the outer pipe and
flashing to prevent water from penetrating the chimney system.
15. Slide storm collar over pipe length until it reaches the flashing.
16. Install termination cap by twist locking it.
17. Secure the flashing to the roof using screws
Note
: Any closets or storage spaces which the vent passes through
must be enclosed.
Diagram 3
Diagram 3b
13. Slide the finished length up towards the flashing ensuring the length
of pipe is a minimum of 0.6 m measured from the top of the roof.
Level the chimney and secure using the roof support provided
with kit to bottom side of the roof as shown using a minimum of
2 screws per side- see Diagram 3b. See Diagram 4 for roof pitch
and height requirements. See Diagram 3a for securing method if
0.6 m is insufficient and additional lengths are required, this may
be purchased separately. See Simpson Duravent components list
in the instruction manual for part numbers.
City Series ACB60E
|
61
installation
920-328
09.18.20
Diagram 4
14. Put a bead of caulking on the exterior between the outer pipe and flashing
to prevent water from penetrating the chimney system.
15. Slide storm collar over pipe length until it reaches the flashing.
16. Install termination cap by twist locking it.
17. Secure the flashing to the roof using screws
Note
: Any closets or storage spaces which the vent passes through must
be enclosed.
Roof Pitch Minimum Vent Height
Meters
flat to 7/12
0.61
over 7/12 to 8/12
0.61
over 8/12 to 9/12
0.61
over 9/12 to 10/12
0.76
over 10/12 to 11/12
0.99
over 11/12 to 12/12
1.22
over 12/12 to 14/12
1.52
over 14/12 to 16/12
1.83
over 16/12 to 18/12
2.13
over 18/12 to 20/12
2.29
over 20/12 to 21/12
2.44
Diagram 3
Diagram 3a
Diagram 3b
13. Slide the finished length up towards the flashing ensuring the length of
pipe is a minimum of 0.6m measured from the top of the roof. Level the
chimney and secure using the roof support provided with kit to bottom
side of the roof as shown using a minimum of 2 screws per side- see
Diagram 3b. See Diagram 4 for roof pitch and height requirements. See
Diagram 3a for securing method if 0.6m is insufficient and additional
lengths are required, this may be purchased separately. See Simpson
Duravent components list in the instruction manual for part numbers.
Flex Pipe
Ceiling Firestop
Roof Support / Brace
Flashing
Storm Collar
Termination Cap
Ceiling Firestop
Enclosure
Flex Pipe
Ceiling Firestop
Roof Support
Flashing
Elbow Support
Termination Cap
Storm Collar
Ceiling Firestop
Support to prevent sagging
Enclosure
Ceiling firestop
Flashing
Termination Cap
Storm Collar
Roof support
Ceiling firestop
2
Enclosure
Ceiling firestop
Flashing
Termination Cap
Storm Collar
Roof support
Ceiling firestop
Roof Pitch
Minimum Vent Height
Meters
flat to 7/12
0.61
over 7/12 to 8/12
0.61
over 8/12 to 9/12
0.61
over 9/12 to 10/12
0.76
over 10/12 to 11/12
0.99
over 11/12 to 12/12
1.22
over 12/12 to 14/12
1.52
over 14/12 to 16/12
1.83
over 16/12 to 18/12
2.13
over 18/12 to 20/12
2.29
over 20/12 to 21/12
2.44
City Series ACB60E
|
61
installation
920-328
09.18.20
Diagram 4
14. Put a bead of caulking on the exterior between the outer pipe and flashing
to prevent water from penetrating the chimney system.
15. Slide storm collar over pipe length until it reaches the flashing.
16. Install termination cap by twist locking it.
17. Secure the flashing to the roof using screws
Note
: Any closets or storage spaces which the vent passes through must
be enclosed.
Roof Pitch Minimum Vent Height
Meters
flat to 7/12
0.61
over 7/12 to 8/12
0.61
over 8/12 to 9/12
0.61
over 9/12 to 10/12
0.76
over 10/12 to 11/12
0.99
over 11/12 to 12/12
1.22
over 12/12 to 14/12
1.52
over 14/12 to 16/12
1.83
over 16/12 to 18/12
2.13
over 18/12 to 20/12
2.29
over 20/12 to 21/12
2.44
Diagram 3
Diagram 3a
Diagram 3b
13. Slide the finished length up towards the flashing ensuring the length of
pipe is a minimum of 0.6m measured from the top of the roof. Level the
chimney and secure using the roof support provided with kit to bottom
side of the roof as shown using a minimum of 2 screws per side- see
Diagram 3b. See Diagram 4 for roof pitch and height requirements. See
Diagram 3a for securing method if 0.6m is insufficient and additional
lengths are required, this may be purchased separately. See Simpson
Duravent components list in the instruction manual for part numbers.
Flex Pipe
Ceiling Firestop
Roof Support / Brace
Flashing
Storm Collar
Termination Cap
Ceiling Firestop
Enclosure
Flex Pipe
Ceiling Firestop
Roof Support
Flashing
Elbow Support
Termination Cap
Storm Collar
Ceiling Firestop
Support to prevent sagging
Enclosure
Ceiling firestop
Flashing
Termination Cap
Storm Collar
Roof support
Ceiling firestop
2
Diagram 3a
Vertical Termination - 127 mmx 203 mm Flueing - Vertical Flex Kit (Part 946-772)