8 |
Regency CS1205 Freestanding Wood Stove
installation
Z
6"
6"
16"
Y
Y
X
X
6"
for angled
corners
6"
16"
6"
6"
Z
The Regency Freestanding models have been alcove approved and must be installed
with a listed double wall connector to the ceiling level.
Note: Minimum alcove ceiling height - 84"
Maximum depth of alcove - 36"
Minimum Overall Width (X) of Floor
Protector
for all installations:
US
38-3/4"
Canada
42-3/4"
Floor Protection
A combustible floor must be protected by a non-combustible material (like tile,
concrete board, or certified to UL-1618 or as defined by local codes) extending
beneath the heater and a minimum of 6" from each side and minimum 16" from
the fuel door opening of the stove and minimum 6" (or the rear clearance to
combustibles whichever is smaller) from the rear of the stove.
NOTE: In Canada, floor protection must extend 18" to the front and 8" to each side of the stove.
Minimum Alcove Clearance to Combustible Materials
Unit
From Back Shield
+ Side Shields.
From Flue
Center-Line
Min.
Width
Min. Hearth
to Rear Wall
CS1205
G
H
I
J
K
L
11"
7"
24-1/2"
14-1/2"
49-1/8"
39-1/4"
Minimum Overall Depth (Y) of Floor Protector
Unit
Residential
"C" Vent
Residential
Close Clearance
Mobile Home
Close Clearance
Alcove
CS1205
Y
Z
Y
Z
Y
Z
Y
Z
USA
39"
6"
39
6"
39"
6"
39"
6"
Canada
43"
8"
43"
8"
43"
8"
43"
8"
MINIMUM ALCOVE CLEARANCE TO COMBUSTIBLE MATERIALS
MEASUREMENTS "FROM UNIT" ARE FROM THE SIDE SHIELDS OF THE STOVE TO A SIDE WALL OR TO A CORNER, AND FROM
THE REAR HEAT SHIELD TO A BACK WALL
Содержание Alterra CS1205
Страница 36: ...36 Po le bois autoportant Regency CS1205 garantie...
Страница 37: ...Po le bois autoportant Regency CS1205 37 notes...
Страница 38: ...38 Po le bois autoportant Regency CS1205 notes...
Страница 39: ...Po le bois autoportant Regency CS1205 39...
Страница 76: ......
Страница 77: ...Regency CS1205 Freestanding Wood Stove 37 notes...
Страница 78: ...38 Regency CS1205 Freestanding Wood Stove notes...
Страница 79: ......