City Series ACC40E
|
23
installation
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may
NOT
be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fireplace and flue
system be installed only in accordance with these instructions.
Clearances
The clearances listed below are minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
fireplace and flue system be installed only in accordance with these instructions.
Note: ACC40LE shown in illustration. Clearances will be the same for the ACC40RE.
Clearance: single sided
Dimension
Measured From:
A: Mantel Height (min.)
**
Top of Fireplace Opening
B: Opening Height
382mm
Bottom/Top of Fireplace Opening
C: From Floor
Min. 0mm
Bottom of Fireplace Opening
D: Sidewall (on one side)
Min. 914mm
Side of Fireplace Opening
E: Mantel Depth (Max.)
**
Front of Fireplace Opening
F: Alcove Depth
Min. 914mm
Front of Fireplace Opening
G: Convection Air Outlet
*
Top of Enclosure
H: Convection Air Outlet Opening Offset
0-76mm
Max. offset from top of chase enclosure
I: Chase Enclosure (Min.)
1600mm
From Base of Unit
K:
Clearance to sprinkler head
(Min.)
914mm
Perpendicular from chase grill
Hearth
0mm
No hearth required
**
See mantel clearances chart in this manual.
Top View
Alcove
The
HeatWave
Duct Kit has differ-
ent clearance and framing require-
ments, check the
HeatWave
manual
for details.
*
A minimum of 774 square centimetres of
open area, not lower than 76mm from top
of enclosure, required for all installations
H
I
A
E
B
C
G
D
F
D
F
CC40 UNIT
Side View
L
Chase grill
Sprinkler
K
Flue Clearances to Combustibles
Horizontal - Top
76mm
Horizontal - Side
51mm
Horizontal - Bottom
51mm
Vertical
51mm
Passing through wall/
floor/ceiling - when
firestop is used.
38mm