Regal Smartvalve 7001 Скачать руководство пользователя страница 16

16

DRAWING NO. 2 — SMARTVALVE™ INSTALLATION  
to Provide BOTH Manual and Automatic Operation

REGAL 7500 

 

Remote Meter Assembly

Gas Flow 

from Vacuum Regulator

Vacuum Tubing or

 

Schedule 80 PVC 

Pipe

Booster Pump 

(BY OTHERS)

REGAL Ejector Assembly

#2 PVC 

Ball Valve

#1 PVC 

Ball Valve

#3 PVC 

Ball Valve

Chemical Solution 

 

Injection Point

Water Flow Meter

4-20 mA Analog Flow Input Signal

4-20 Milliamp Analog Output Signal

1) For Automatic Operation, open ball valves #1 and #2. Close Valve #3.

 

2) For Manual Operation, close ball valves #1 and #2. Open Valve #3.

Gauge for Supply

 

Pressure (Ps) 

Gauge for Back

 

Pressure (Pb) 

Isolation Valve (Typ.)

 

(BY OTHERS)

Pipe Union (Typ.)

 

(BY OTHERS)

120/240 VAC

 

50/60 Hz

REGAL SMARTVALVE™

 

Содержание Smartvalve 7001

Страница 1: ...nt is suitable for use only with the gases specified DO NOT USE THIS EQUIPMENT WITH OTHER GASES Such use can result in failures having hazardous consequences 2 This equipment is designed FOR VACUUM SE...

Страница 2: ...against material defects in components and workmanship occurring in the course of manufacture Buyer s sole remedy for breach of said warranty shall be at C I s option either repair or replacement of...

Страница 3: ...ct to open or close the valve 8 Do not reuse lead gaskets They may not seal properly thereby permitting the release of gas 9 Use only lead gaskets Other types may contract with temperature variations...

Страница 4: ...ing the Analog Output C Setting the Mechanical Zero 8 0 MAINTENANCE 9 0 SPECIFICATIONS A To Enter the Configuration Mode B Configuration Parameters C To Exit the Configuration Mode 5 0 CONFIGURATION M...

Страница 5: ...ly Circuit Board Part No 7071 Drawing No 7 Use of External Surge Suppressors Consult manufacturer of surge suppressor for installation and wiring specifics Drawing No 8 Control Valve Assembly for 10 t...

Страница 6: ...the middle third of the system s capacity maximum feed rate 2 The water flow meter and transmitter must be sized or scaled so the maximum water flow coincides with the maximum feed rate capacity of t...

Страница 7: ...ting to the vacuum fitting on the ejector assembly 5 Finally connect a length of tubing from the bottom connection of the pressure relief valve routing it outside with the end facing down and protecte...

Страница 8: ...isplay screen reads ENT ENG PW 0 Enter Engineering Password 2 Press the NEXT keypad button three times until the factory default password 0 0 0 0 appears Then press ENT enter to accept 3 The TOP LINE...

Страница 9: ...eatedly until the preferred FIRST digit is displayed Then press NEXT to accept the new value b The number 0 will appear as the second digit Once again use UP or DOWN to scroll to the preferred number...

Страница 10: ...red and designate what condition the alarm represents The selections are OFF LOW or HIGH If the SET POINT MODE setting is left in the factory default OFF position no additional parameters will be made...

Страница 11: ...ading of 0 45 V NOTE A voltage reading from 0 41 to 0 49 is acceptable IMPORTANT If for some reason the voltage reading falls outside of the acceptable range contact Chlorinators Incorporated for assi...

Страница 12: ...t the feed rate simply turn the thumbwheel while using the remote meter ball float as a guide 4 Fully Manual If it is necessary to temporarily bypass the SMARTVALVE entirely use the remote meter rate...

Страница 13: ...t Press ESC a second time and SAVE CHANGES to return to the main operating screen C SETTING MECHANICAL ZERO See Drawing No 8 for Model 7001 or No 9 for Model 7006 The mechanical zero valve plug positi...

Страница 14: ...AM 16 Bit Display 20 character 2 line Backlit LCD Relays Three 3 each 10A 250 VAC Environmental Limits 32 to 120 F 0 to 50 C Calibration Accuracy 0 25 from zero Speed of Response Variable and field se...

Страница 15: ...Union Typ BY OTHERS Gauge for Supply Pressure Ps BY OTHERS Gauge for Back Pressure Pb BY OTHERS REGAL Model CRA 5000 Residual Analyzer REGAL VAC 1000 Vacuum Monitor Static Mixer BY OTHERS Residual Sa...

Страница 16: ...Ball Valve 1 PVC Ball Valve 3 PVC Ball Valve Chemical Solution Injection Point Water Flow Meter 4 20 mA Analog Flow Input Signal 4 20 Milliamp Analog Output Signal 1 For Automatic Operation open ball...

Страница 17: ...valve tool supplied with your REGAL chlorinator system into the slot and tilt the screwdriver in the direction of the terminal number This will open the clamp and allow the wire to be inserted Remove...

Страница 18: ...RIGHT SIDE JUNCTION BOX 1 L See Note 1 2 N See Note 1 3 Ground See Note 1 4 N O Relay K1 5 Com Relay K1 6 N C Relay K1 7 N O Relay K2 8 Com Relay K2 9 N C Relay K2 10 N O Relay K3 11 Com Relay K3 NOT...

Страница 19: ...19 DRAWING NO 5 DISPLAY CIRCUIT BOARD Part Number 7070 NOTE All wiring connections to this circuit board are made at the factory prior to shipment See Drawing No 4 for Field Wiring...

Страница 20: ...20 DRAWING NO 6 POWER RELAY CIRCUIT BOARD Part Number 7071 NOTE All wiring connections to this circuit board are made at the factory prior to shipment See Drawing No 4 for Field Wiring...

Страница 21: ...h Grounding Rod External Surge Protection Device Typ BY OTHERS IMPORTANT Consult the manufacturer of the transient voltage surge suppression device for proper wiring of inputs and outputs Analog and d...

Страница 22: ...7121 1 Potentiometer 7124 3 S 405 0 Ring 7127 1 S 414 0 Ring 7128 2 Seal 7129 1 Seal 7131 4 Screw 10 24 X 2 1 2 7132 1 Screw 10 24 X 1 2 7133 4 Screw 10 32 X 1 with O Ring 7135 5 10 Lock Washer 7136...

Страница 23: ...r 7121 1 Potentiometer 7122 1 Guide Retainer 7124 1 S 405 O Ring 7125 1 S 415 O Ring 7126 1 S 407 O Ring 7127 1 S 414 O Ring 7128 1 Seal 7129 1 Seal 7130 1 Seal 7131 4 Screw 10 24 X 2 1 2 7132 1 Screw...

Страница 24: ...24 DRAWING NO 10 ENGINEERING DATA SHEET Series 7000 SMARTVALVE Dimensions DIMENSIONS INCHES mm 7500 REMOTE METER PANEL SMARTVALVE...

Страница 25: ...e Valve Plug O Ring 11 S 406 2 Meter Tube Plug O Ring 12 Z 815 4 Screw 1 4 20 x 1 Long 13 ZZ 278 1 Plug 1 2 NPT 14 See Chart 2 Tube Fitting Elbow Not Shown NOTE If system is using 1000 PPD or 2000 PPD...

Страница 26: ...Metering Tube Float Assembly 1000 PPD 20 Kg Hr 2000 PPD 40 Kg Hr Flow Meter Inlet Block Back Panel Mounting Screws For RV 810 RV 814 Base Plate for RV 814 Rate Valve Seat Plug with 2 S 803 Seals NOTES...

Страница 27: ...pad 1 At dosage settings greater than 100 proportionality is lost at some water flow rate less than the designed maximum rate If the dosage setting is increased to 200 for example proportional control...

Страница 28: ...2019 Chlorinators Incorporated Printed in U S A Pub No 0919 3 1044 SE Dixie Cutoff Road Stuart Florida 34994 USA Phone 772 288 4854 Fax 772 287 3238 www regalchlorinators com Email regal regalchlorin...

Отзывы: