© 2006
GE ECM
by Regal-Beloit
- 76 -
Indoor Blower Motors
v0.2
X13 Connections and Communications
There is one connection block on the X13 motor with two rows of terminals and two
different size terminals used.
The Power Inputs (High Voltage)
to the motor connect through the 3/16” terminals
on the following terminals:
C L G N
1 2 3 4 5
High Voltage
Connections
3/16"
Low Voltage Connections
1/4”
(L) – Line 1
(G) - Ground
(N) - Neutral or Line 2
The power connected to these terminals is
live whenever they system is powered
regardless of a demand call to power the
internal electronics.
There are two discrete models per voltage,
one for 115vac applications and one for
230vac applications.
The allowable voltage range on these motors
is:
98-132vac on the 115vac model
196-264vac on the 230vac model