1.5.1 Lifetime of actuators
The lifetime of an electric actuator (EA) is at least 6 years.
EA used for closing mode (closing valves) comply with the requirements for at least
15,000 working cycles
(cycle C – O – C: for part-turn EA)
EA used for regulating/modulating operation (control valves) comply with the below stated numbers of
operating
hours
at the total number of 1 million start-ups:
Switching frequency
max. 1,200 [h
-1
]
1,000 [h
-1
]
500 [h
-1
]
250 [h
-1
]
125 [h
-1
]
Minimal lifetime expectancy – number of operating hours
850
1,000
2,000
4,000
8,000
Time of
net operation
is min. 200 hours, max. 2,000 hours.
Lifetime at operating hours
depends on loading and switching frequency.
Note : High switching frequency does not ensure better regulation. Setting of regulation parameters should be
therefore made with the inevitably necessary switching frequency needed for the process in question.
1.6 Operation conditions
1.6.1 Product location and operation position
EA may be installed and operated in enclosed locations of industrial facilities with no temperature and
moisture regulation, protected from direct climatic effects (such as direct sunlight). Moreover, special “marine”
versions may be used in waste water treatment applications, water management, selected chemical
applications, tropical environments and coastal areas.
Warning:
When the EA is installed in open air,
it must be
sheltered lightly to protect is against direct
effects of atmosphere.
When installed in the areas with relative humidity more than 80%, in open air under a shelter is
needed to connect the space heater directly – without a thermal switch.
Installation and operation of EA is possible in
any position.
Vertical position of output part axis and
with the control part above the valve is usual.
1.6.2 Working enviroment
According to valid standard IEC 60 721-2-1, there are delivered these versions of electric actuators:
1) Version
„standard“
for type climate temperate
2) Version
„tropical wet“
for type climate tropical wet
3) Version
„cold“ -
for type climate cold
4) Version
„tropical dry and dry“
for type climate tropical dry and dry
5) Version
„marine“
for type climate marine
6) Version
„arctic“
for type climate arctic.
In accordance with IEC 60 364-1, IEC 60 364-5-51 and IEC 60 364-5-55 within valid edition the EA have to
resist external effects and operate reliably:
In the conditions of the following types of environment:
•
warm mild to very hot dry with temperatures -25°C to +55°C ............................................................ AA 7*
•
cold, warm mild to hot dry with temperatures -50°C to +40°C............................................................ AA 8*
•
cold, hot dry to slightly hot dry with temperatures -50
°
C to +55
°
C.................................................. AA 8*+AA 7*
•
cold to mild hot dry with temperatures in range -60
°
C až +40
°
C.............................................AA 1*+AA 5*
•
with relative humidity 10÷100%, including condensation with maximum content 0,029kg of water
in 1kg of dry air , with temperatures stated above............................................................................. AB 7*
•
with relative humidity 15÷100%, including condensation with maximum content 0,036kg of water in 1kg
of dry air , with temperatures stated above ....................................................................................... AB 8*
•
with relative humidity 10÷100%, including condensation with maximum content 0,036 kg of water
in 1kg of dry air, with temperatures stated above ......................................................................... AB 8*+AB 7*
!
Содержание UP 0
Страница 10: ...8 UP 0 UP 1 UP 2 UP 2 4 UP 2 5 5 9 Fig 1a Fig 1b ...
Страница 11: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 9 Fig 1c UP 2 5 with controller ...
Страница 42: ...40 UP 0 UP 1 UP 2 UP 2 4 UP 2 5 7 Enclosures 7 1 Wiring diagrams UP 1 UP 2 UP 2 4 UP 2 5 ...
Страница 43: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 41 ...
Страница 44: ...42 UP 0 UP 1 UP 2 UP 2 4 UP 2 5 Wiring diagrams UP 0 ...
Страница 47: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 45 7 4 Dimensional drawings Electric part turn actuators Unimact UP 0 UP 1 UP 2 ...
Страница 48: ...46 UP 0 UP 1 UP 2 UP 2 4 UP 2 5 Electric part turn actuators Unimact UP 0 UP 1 UP version stand and lever ...
Страница 49: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 47 Electric part turn actuators Unimact UP 1 UP 2 version with local control ...
Страница 51: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 49 Electric part turn actuators Unimact UP 2 4 UP 2 5 ...
Страница 52: ...50 UP 0 UP 1 UP 2 UP 2 4 UP 2 5 Electric part turn actuators Unimact UP 2 4 UP 2 5 version stand and lever ...
Страница 53: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 51 Electric part turn actuators Unimact UP 2 4 UP 2 5 version with local control ...