3.5.1  Setting of controller 

 

The controller's microprocessor unit is in the production plant programmed to parameters given 

in 

Table 2

 (Note 2). 

 

Setting of the controller is performed using buttons and LED diodes. 

 

Adjust  the  position  and  thrust  switches  and  the  position  transmitter  before  adjustment  of  the 

controller. 
Laying of adjusters and signalling elements on the board of the REGADA controller is shown on Fig. 9: 

 

 

   

 

Fig. 9 

 

 
Table 2: 

D3 (yellow) diode 

number of blinking 

Adjust menu 

D4 (red) diode 

number of blinking 

Adjusted parameter 

1 blink 

0-20mA 

2 blinks 

4-20 mA (*) (**) 

1 blink 

control signal 

3 blinks 

0-10V DC 

1 blink 

EA opens receiving signal SYS 

2 blinks 

EA closes receiving signal SYS 

2 blinks 

response for signal 

SYS-TEST 

3 blinks 

EA stops receiving signal SYS (*) 

1 blink 

EA CLOSING at increasing of control 

signal 

3 blinks 

mirroring 

(ascending/descending 

characteristics) 

2 blinks 

EA OPENING at increasing of control 

signal (*) 

4 blinks 

insensitiveness of 

controller 

1 to 10 blinks 

insensitiveness of controller of 1-10%  

(3% set by the producer) (*) 

CONTINUE >>> 

 

D3 (yellow) diode 

number of blinking 

Adjust menu 

D4 (red) diode 

number of blinking 

Adjusted parameter 

1 blink 

narrow thrust 

2 blinks 

narrow position (*) 

3 blinks 

wide thrust 

5 blinks 

way of regulation 

4 blinks 

wide position 

Notes:  
1.  The controller at autocalibration automatically sets the feedback type - resistant/current 
2.  (*)  Parameters set in the production plant, if customer has not stated else. 
3.  (**) Input signal  

  4 mA - position "closed" 

 

   

 

20 mA - position "open" 

 

 

Standard setting of controller (programmed RESET of controller) - 

in case of any problems with 

setting of the parameters it is possible with pressing both 

SW1 and SW2 

at the same time and then 

switching power on to set the standard parameters. 
 

SW1 button

 

starts  an  initialisation  routine  an  allows 
listing in the adjust menus 

SW2 button

 

setting of parameters in the chosen menu 

D1 diode

 

power on indication 

D2 diode

 

motion  to  the  direction  "opening"  indication 
(green) - "closing" (red) indication 

D3 diode

 

(yellow  light)  number  of  blinking  codes 
indicates chosen adjust menu 

D4 diode

 

(red  light)  number  of  blinking  codes 
indicates 

adjusted 

parameter 

of 

the 

controller from the chosen menu 

Содержание ST 0

Страница 1: ...74 0813 02 INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS Electric linear actuators ST 0 STR 0...

Страница 2: ...min Operating stroke mm Input operation signal Warranty period months Transmitter potentiometer Serial number of electric motor Serial number of transmitter Serial number of position controller Tests...

Страница 3: ...5 3 1 Gear unit adjustment 16 3 2 Position unit adjustment Fig 6 16 3 3 Adjustment of resistant transmitter 16 3 4 Adjustment of the Electronic Position Transmitter EPV the Resistive Transmitter Poten...

Страница 4: ...th producer It is forbidden to use EA as a lifting mechanism 1 2 Safety instructions 1 2 1 Characteristics of the Product Regarding Its Exposure Rate EA of ST and STR types are reserved technical devi...

Страница 5: ...with EN ISO 7010 ISO 7000 and IEC 60417 within valid edition Dangerous voltage EN ISO 7010 W012 Stroke of the electric linear actuator Switching off thrust Manual control 0096 ISO 7000 Protection term...

Страница 6: ...max 2 000 hours Lifetime at operating hours depends on loading and switching frequency Note High switching frequency does not ensure better regulation Setting of regulation parameters should be there...

Страница 7: ...50 but at most 1000 mg sq m per day protection enclosure IP 6x AE6 with atmospheric occurrence of corrosive and pollution media AF2 with possibility of effects of medium sinusoid vibrations with frequ...

Страница 8: ...fed and controlled through two thrust switches 2 The thrust switches are switched with a finger 5 The position switches are switched with motion of the cams 4 The actuators are controlled with connect...

Страница 9: ...power Nom speed Men current Capacitor capacity mm min mm mm N N N kg V 10 W 1 min A F V 1 2 3 4 5 6 7 8 9 10 11 12 13 14 3 200 4 000 4 500 2 560 3 200 3 800 1 280 1 600 1 900 5 640 800 950 3 200 4 00...

Страница 10: ...rsion without built in power supply with built in power supply Output signal for 2 wire version 4 20 mA DC Output signal for 3 wire version 0 5 mA DC 0 20 mA DC 4 20 mA DC 0 10 V DC Power supply volta...

Страница 11: ...ng in direction opening frequency of relay switching in direction closing Supply voltage terminal 61 L1 1 N 230 V AC 10 Frequency 50 60 Hz 2 Input control signals analogue 0 20 mA 4 20 mA 0 10 V Input...

Страница 12: ...acking Surfaces without surface treatment are treated by conservation preparation MOGUL LV 2 3 before packaging Conservation is not necessary if the following storage conditions are complied with Stor...

Страница 13: ...nto operation Assembled EA but not put into operation is necessary to protect by the equivalent method as during storage for example suitable protective cover After assembly to the armature in free an...

Страница 14: ...nnection dimensions according to DIN Standards Fig 2 Connection procedure Set the actuator A and the valve B to the position closed Put the actuator A onto the valve B Screw the actuator shaft 8 into...

Страница 15: ...g nut 4 pillar nut 6 pillar 7 coupling screw B valve 10 valve shaft 12 locking nut 13 valve flange Mechanical connection for versions with flange Fig 4 Connection procedure Set the actuator A and the...

Страница 16: ...ing nut 5 actuator flange 6 pillar B valve 10 valve shaft 11 connecting nut 12 locking nut 13 valve flange 2 1 2 Electric connection and checking of function 1 Follow instructions in the part Requirem...

Страница 17: ...ng The procedure is as follows Press the button SW1 for about 2 sec i e till the D3 diode is got on to set the controller to the autocalibration mode During this process the controller checks the feed...

Страница 18: ...eps Put the actuator to the position where the switch S5 should indicate the position open Turn the cam switching the switch S5 clockwisely until the switch S3 14 switches Put the actuator to the posi...

Страница 19: ...the procedure if needed Note The output signal of 4 20mA can be adjusted at the range from 75 up to 100 of the rated stroke stated on the actuator s nameplate At values less than 75 the value 20mA is...

Страница 20: ...resp 0V Set the actuator to the position open Turn the adjusting trimmer GAIN resp B to adjust the output current signal rate measured on the terminals 81 82 to 20mA resp 5 mA resp 10V Check the outp...

Страница 21: ...insensitiveness of controller of 1 10 3 set by the producer CONTINUE D3 yellow diode number of blinking Adjust menu D4 red diode number of blinking Adjusted parameter 1 blink narrow thrust 2 blinks na...

Страница 22: ...e D4 diode reports about the type of the error Else after finishing the initialisation process the controller is put into the regulation mode Error messages of the controller with D4 diode at initiali...

Страница 23: ...face occurred it is to be removed to prevent actuator against corrosion The EA ST STR requires just negligible service Proper putting into operation is a recondition of reliable operation The service...

Страница 24: ...s operation the replacement of cover seals and oil filling seals must be done The grease in the supplied actuators is designed for the lifetime of the product It is not necessary to change the grease...

Страница 25: ...mA 250V fuse e g Siba or MSF 250 Note If the EA requires dismantling follow the chapter Dismantling Taking the EA to pieces for repair purposes is allowed only by professionally qualified persons trai...

Страница 26: ...24 ST 0 STR 0 6 Enclosures 6 1 Wiring diagrams Wiring diagrams for EA ST...

Страница 27: ...ent converter 3 wire version with power supply Z269 wiring diagram of resistive transmitter with current converter or capacitive transmitter 2 wire version with power supply B1 remote transmitter resi...

Страница 28: ...26 ST 0 STR 0 6 2 Dimensional drawings EA ST STR The dimensions are valid also for the following dimensional drawings where only mechanical connection types are shown...

Страница 29: ...ST 0 STR 0 27 Flange DIN 3358...

Страница 30: ...28 ST 0 STR 0 Pillars...

Страница 31: ...ST 0 STR 0 29 Flange...

Страница 32: ...30 ST 0 STR 0 Flange...

Страница 33: ...ST 0 STR 0 31 Flange...

Страница 34: ...32 ST 0 STR 0 Pillars...

Страница 35: ...ST 0 STR 0 33 Flange...

Страница 36: ...34 ST 0 STR 0 Pillars...

Страница 37: ...ST 0 STR 0 35 Flange...

Страница 38: ...36 ST 0 STR 0 Flange...

Страница 39: ...ST 0 STR 0 37...

Страница 40: ...38 ST 0 STR 0...

Страница 41: ...heck report Service center Date of repair Guarantee repair no User of actuator Claim applied by Actuator type number Actuator production number Product claim fault Detected product fault Used spare pa...

Страница 42: ...uarantee service check report Service center Date of repair User of actuator Actuator operating place Actuator type number Actuator production number Detected product fault Used spare parts Remarks Is...

Страница 43: ...n cka 7 080 01 Pre ov Tel 421 0 51 7480 460 Fax 421 0 51 7732 096 E mail regada regada sk Czech Republic Exclusive representation Regada s r o Ltd for sale of electric actuators Regada esk s r o N m 5...

Отзывы: