![Regada ST 0 Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/regada/st-0/st-0_installation-service-and-maintenance-instructions_1433061015.webp)
ST 0, STR 0
13
Mechanical connection for pillar version - Fig. 3
Connection procedure:
•
The valve (B) is put to the position „closed“ and the
actuator (A) to a mid-position.
•
Loosen the nuts (4) on the pillars (6).
•
Screw the pillars (6) with the cross system into the valve
flange (13).
•
Tighten the pillars (6) nuts.
•
Unscrew the coupling (3) screws (7) to dismantle the
coupling into parts.
•
Screw the coupling (3) nut onto the valve shaft (10) to
reach the connecting size H in accordance with the table
and the actuator nameplate.
•
Unscrew the coupling (3) nut by one revolution and lock it
by a nut (12).
•
Use the hand wheel (2) to put the actuator output shaft
next to the valve (10), and screw the coupling parts
together
.
A ............ electric actuator
1 ............. disengagement button
2 ............. hand wheel
3 ............. coupling nut
4 ............. pillar nut
6 ............. pillar
7 ............. coupling screw
B ............ valve
10 ........... valve shaft
12 ........... locking nut
13 ........... valve flange
Mechanical connection for versions with flange (Fig. 4)
Connection procedure:
•
Set the actuator (A) and the valve (B) to the position
„closed“.
•
Place the actuator (A) onto the valve (B).
•
Tighten the central nut (11) to connect flanges (13) and
(5).
•
Unscrew the coupling (3) screws to dismantle the coupling
into parts.
•
Screw the coupling (3) nut onto the valve shaft (10) to
reach the connecting size H in accordance with the table
and the actuator nameplate.
•
Unscrew the coupling (3) nut by one revolution and lock it
by a nut (12) to create the prestress onto the valve seat.
•
Use the hand wheel (2) to put the actuator output shaft
near the valve (10), and screw the coupling parts together.
A ............ electric actuator
1 ............. disengagement button
2 ............. hand wheel
3 ............. coupling nut
4 ............. pillar nut
5 ............. actuator flange
6 ............. pillar
B ............ valve
10 ........... valve shaft
11 ........... central nut
12 ........... locking nut
13 ........... valve flange
Fig. 3
Fig.4
Содержание ST 0
Страница 1: ...74 0813 02 INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS Electric linear actuators ST 0 STR 0...
Страница 26: ...24 ST 0 STR 0 6 Enclosures 6 1 Wiring diagrams Wiring diagrams for EA ST...
Страница 29: ...ST 0 STR 0 27 Flange DIN 3358...
Страница 30: ...28 ST 0 STR 0 Pillars...
Страница 31: ...ST 0 STR 0 29 Flange...
Страница 32: ...30 ST 0 STR 0 Flange...
Страница 33: ...ST 0 STR 0 31 Flange...
Страница 34: ...32 ST 0 STR 0 Pillars...
Страница 35: ...ST 0 STR 0 33 Flange...
Страница 36: ...34 ST 0 STR 0 Pillars...
Страница 37: ...ST 0 STR 0 35 Flange...
Страница 38: ...36 ST 0 STR 0 Flange...
Страница 39: ...ST 0 STR 0 37...
Страница 40: ...38 ST 0 STR 0...