3.5  Adjusting of stop ends 

 
Mechanical stop ends is possible to adjust in scale from –5 °C to 10 °C for each position dependently. 
Electric actuator is by producer adjusted to operating angle according to the specification. 
While setting, adjusting and resetting stop ends follow next steps: 

• 

loosen  the counter nut of specific stop end 

• 

set the stop end to the new 
position 

• 

lock  the  stop  end  screw 
with the counter nut 

• 

adjust  the  electric  end 
position for switch S3 or S4 
as  is  significated  in  article 
3.1. 

 

Attention! 

  

 

Operating 

angle 

adjusted  by  stop  ends  must 
be 

greater 

than 

angle 

adjusted by switches S3 and 
S4. Fixed stop ends are used 
only  for  localisation  of  a 
position 

by 

manual 

adjusting  of  the  actuator. 
Use  of  fixed  stop  ends  in 
motor-operated  operation  of 
actuator is impermissible! 

                                                                                            

 

                                                                             Pic.9: Flange of actuator from bottom. 

 
 

4.  Service and Maintenance 

4.1  Service 

 

1. 

In general it is supposed that the EA is serviced by a qualified person as required in the Chapter 1! 

2. 

After the EA is put into operation it is necessary to check whether during manipulation its surface  

 

finishing was not damaged – the damages should be eliminated to prevent the surface against 

 

deterioration caused by corrosion! 

 

The  EA  SP  and  SPR  requires  just  negligible  service.  Proper  putting  into  operation  is  a 

recondition of reliable operation. 
 

The  service  of  the  EA  leads  from  the  operation  conditions  and  usually  resides  in  information 

processing for further arranging of required functions. 
 

The  stuff  has  to  perform  prescribed  maintenance  to  prevent  the  EA  during  operation  against 

impacts of environment, which exceed the frame of allowed influences. 
 
 

At a power outage or voltage breaking off, an electric actuator will stop in a position, in which it 

had  been  before  the power  outage  occurred.  In  case  of  need  it  is  possible  to  preset  the  electric 
actuator  with  manual  operation  (if  the  electric  actuator  is  equipped  with  a  mechanism  for  a  gear 
release). 
 

Manual control: 

 

If  needed  (during  adjusting,  function  checking,  failure  etc.)  the  stuff  can  change  setting  of  the 

controlled body using the handwheel.  
 

Stop ends 

!

Содержание SP 0

Страница 1: ...74 0802 02 74 0802 02 Electric part turn actuators SP 0 SPR 0 INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS...

Страница 2: ...perating angle Transmitter Warranty period months Input operating signal Serial number of electric motor Serial number of transmitter Serial number of position controller Tests made in accordance with...

Страница 3: ...justment of position switches Fig 4 14 3 2 Adjustment of resistant transmitter Fig 5 15 3 3 Adjustment of the Electronic Position Transmitter EPV the Resistive Transmitter Potentiometer with the Conve...

Страница 4: ...components switches have to be consulted with producer 1 2 Safety instructions EA of SP and SPR types are reserved technical devices with higher rate of danger with possibility of installation in area...

Страница 5: ...rque Manual control 0096 STN ISO 7000 Protection terminal 5019 IEC 60417 1 4 Warranty conditions The supplier is responsible for completeness of the delivery and guarantees these specifications of the...

Страница 6: ...reas of industrial plants without temperature and humidity regulation protected against climate effects e g direct sunshine Installation and operation of EA is possible in any position Vertical positi...

Страница 7: ...to 150 Hz with shift amplitude of 0 15 mm for f fp and acceleration amplitude 19 6 m s2 for f fp transition frequency fp is from 57 up to 62 Hz AH 2 medium impacts shocks and vibrations AG 2 with ser...

Страница 8: ...an be optionally equipped also with the terminal board for electric motor connection 6 the terminal board for transmitter connection 7 and a resistive transmitter potentiometer 8 Plugs for cables 9 an...

Страница 9: ...ue value 7 Nm only Actuators with max load torque 25 Nm are self locking up to torque value 15 Nm only 2 For 24 V DC 50 30 3 Operating time as a funkcion of torque diagram No 1 4 Switching elements fo...

Страница 10: ...f output signal of EPV Z 0 2 mA O 0 1 mA b 3 wire version without built in power supply or with built in power supply Current signal 0 20 mA DC Current signal 4 20 mA DC Current signal 0 5 mA DC Power...

Страница 11: ...5A 250V AC Digital outputs 4x LED supply error adjustment opening closing with two colour LED Error status control switch 24 V 2W POR Reaction at error situation transmitter error error message LED C...

Страница 12: ...e with EN 60 654 IEC 60654 1 and 60654 3 Package is a box Products in boxes is possible to load on the pallets pallet is returnable On the outer side of the package is stated manufacturer label name a...

Страница 13: ...us waste 2 Installation and dismantling of actuator Abide by safety measures Notes Repeatedly verify whether placing of EA correspondents to part Operating conditions If actual conditions differ from...

Страница 14: ...th a tube with threads on the both ends see dimensional drawing P 0100 While mounting the lever mechanism the angle between the lever and the pull rod is to be more than 15 and less than 165 The coars...

Страница 15: ...ection protection switched off directly with the corresponding position or torque switches After electric connection it is recommended Checking of wiring Set the actuator into a mid position Check the...

Страница 16: ...on professional competence Disconnect the electrical servo drive from electrical power network Observe safety regulations The adjustment can be performed at a mechanically and electrically connected...

Страница 17: ...0 of the EA SPR terminal board Put the actuator to the position closed with the handwheel or with the local electric position control until the corresponding position switch S4 Rotate the transmitter...

Страница 18: ...ate measured on the terminals 81 82 to 0 mA or 4mA Set the actuator to the position open Turn the adjusting trimmer GAIN Fig 7 to adjust the output current signal rate measured on the terminals 81 82...

Страница 19: ...torque 5 blinks way of regulation 4 blinks wide position Notes 1 The controller at autocalibration automatically sets the feedback type resistant current 2 Parameters set in the production plant if c...

Страница 20: ...he controller with D4 diode at initialisation 4 blinks improper connection of the torque switches 5 blinks improper connection of the feedback transmitter 8 blinks bad sense of actuator s turning dire...

Страница 21: ...son as required in the Chapter 1 2 After the EA is put into operation it is necessary to check whether during manipulation its surface finishing was not damaged the damages should be eliminated to pre...

Страница 22: ...ssion bearings type KX with yellow liner and actuators gearings Changing or filling grease up during first years operation is not required If the electric actuator works only occasionally it is necess...

Страница 23: ...3 592 382 3 1 Capacitor 300 047 63 540 305 1 Micro switch CHERRY DB 6G A1LB 64 051 466 4 1 Resistant wire transmitter potentiometer RP19 1x100 64 051 812 8 1 Resistant wire transmitter potentiometer R...

Страница 24: ...22 SP 0 SPR 0 6 Accessories 6 1 Wiring diagrams Wiring diagrams for EA SP 0 Wiring diagrams for EA SP 0 24 V DC...

Страница 25: ...Z315a connection of EA SPR 24 V DC with resistant feedback and with space heater B1 remote transmitter resistive single B3 electronic position transmitter EPV S3 positional switch open S4 positional...

Страница 26: ...24 SP 0 SPR 0 6 2 Dimensional drawings The dimensions are valid for version with convertern and SPR 0 with controller...

Страница 27: ...SP 0 SPR 0 25...

Страница 28: ...26 SP 0 SPR 0...

Страница 29: ...SP 0 SPR 0 27...

Страница 30: ...28 SP 0 SPR 0...

Страница 31: ...SP 0 SPR 0 29 Shape A Shape C Position indicator VERSION FLANGE The dimensions are valid for version with converter SHAPE...

Отзывы: