Regada SP 0 Скачать руководство пользователя страница 17

SP 0, SPR 0 

 

15

 

3.2  Adjustment of resistant transmitter (Fig.5) 

 

The 

resistant transmitter 

is in the EA 

SP 

used to function as a remote position indicator; in the 

EA 

SPR 

to  function  as  a  feedback  in  the  position  controller  and  if  needed  also  in  the  position  of  a 

remote resistant position indicator. 
 

Before the resistant transmitter adjustment the position switches have to be adjusted.  

 

Resistant  transmitter  does  not  need  adjustment,  because  of  self-adjustment  by  adjusting 

actuator  to  both  end  positions.  Transmitter  is  not  possible  set  up  to  other  operating  angle,  than  is 
shown on name-plate of actuator. 
 

Adjustment consists in setting of the resistance in the defined limit position of the EA. 

Notes: 
1.  In case that the EA is not used in the whole stroke range given on the nameplate, the resistance in 

the limit position "open" is proportionally reduced. 

2.  In the EA 

SPR 

2000

 resistant transmitters are used. In the other cases if the resistant branch is 

lead  to  the  terminal  board  the  resistance  of  the  transmitters  is  according  to  the  customer's 
specification. 

To adjust the transmitter follow these steps: 

• 

Loosen the fixing screws (9)  of the transmitter holder and push the transmitter out of mesh. 

• 

Connect a meter for resistance measuring to the terminals 71 and 73 of the EA 

SP 

terminal board, 

or to the terminals 7 and 10 of the EA 

SPR 

terminal board. 

• 

Put  the actuator  to  the  position  “closed“  (with  the  handwheel, or 
with  the  local  electric  position  control  until  the  corresponding 
position switch S4). 

• 

Rotate the transmitter shaft until resistance of 

5% of the nominal 

transmitter resistance can be read on the meter in case of EA 

SP

and 3 up to 7 % of the nominal transmitter resistance in case of 
EA 

SPR, 

i.e.  with  the  resistant  transmitter  with  the  converter 

PTK1. 

• 

In  the  position  put  the  transmitter  to  mesh  with  the  drive  wheel 
and fix the fixing screws on the transmitter holder. 

• 

Disconnect the meter from the terminal board. 

 

 

3.3  Adjustment of the Electronic Position Transmitter (EPV) - the Resistive 

Transmitter (Potentiometer) with the Converter PTK 1 

EPV – the 2-wire version (Fig. 6) 

 

The  position  transmitter  with  the  converter  PTK1  is  in  the  plant  adjusted  to  have  the  output 

current signal on the terminals 81-82 as follows:  

• 

in the position “open“ .............................. 20 mA 

• 

in the position “closed“ ..............................4 mA 

If the transmitter requires a new adjustment follow these 
steps: 

• 

Put  the  actuator  to  the  position  “closed“  and  switch 
the power supply off. 

• 

Adjust  the  resistive  transmitter  according  to  the 
previous chapter. The resistance is to be metered on 
the  terminals  X-Y  (Fig.  6).  The  used  transmitter 
resistance is

 

100 

• 

Switch the converter

s power supply on. 

• 

Turn  the  adjusting  trimmer  ZERO  (Fig.  6)  to  adjust 
the  output  current  signal  rate  measured  on  the 
terminals 81-82 to  4mA. 

• 

Set the actuator to the position “open“. 

• 

Turn the adjusting trimmer GAIN (Fig. 6) to adjust the 

Fig.5 

Fig.6 

Содержание SP 0

Страница 1: ...74 0802 02 74 0802 02 Electric part turn actuators SP 0 SPR 0 INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS...

Страница 2: ...perating angle Transmitter Warranty period months Input operating signal Serial number of electric motor Serial number of transmitter Serial number of position controller Tests made in accordance with...

Страница 3: ...justment of position switches Fig 4 14 3 2 Adjustment of resistant transmitter Fig 5 15 3 3 Adjustment of the Electronic Position Transmitter EPV the Resistive Transmitter Potentiometer with the Conve...

Страница 4: ...components switches have to be consulted with producer 1 2 Safety instructions EA of SP and SPR types are reserved technical devices with higher rate of danger with possibility of installation in area...

Страница 5: ...rque Manual control 0096 STN ISO 7000 Protection terminal 5019 IEC 60417 1 4 Warranty conditions The supplier is responsible for completeness of the delivery and guarantees these specifications of the...

Страница 6: ...reas of industrial plants without temperature and humidity regulation protected against climate effects e g direct sunshine Installation and operation of EA is possible in any position Vertical positi...

Страница 7: ...to 150 Hz with shift amplitude of 0 15 mm for f fp and acceleration amplitude 19 6 m s2 for f fp transition frequency fp is from 57 up to 62 Hz AH 2 medium impacts shocks and vibrations AG 2 with ser...

Страница 8: ...an be optionally equipped also with the terminal board for electric motor connection 6 the terminal board for transmitter connection 7 and a resistive transmitter potentiometer 8 Plugs for cables 9 an...

Страница 9: ...ue value 7 Nm only Actuators with max load torque 25 Nm are self locking up to torque value 15 Nm only 2 For 24 V DC 50 30 3 Operating time as a funkcion of torque diagram No 1 4 Switching elements fo...

Страница 10: ...f output signal of EPV Z 0 2 mA O 0 1 mA b 3 wire version without built in power supply or with built in power supply Current signal 0 20 mA DC Current signal 4 20 mA DC Current signal 0 5 mA DC Power...

Страница 11: ...5A 250V AC Digital outputs 4x LED supply error adjustment opening closing with two colour LED Error status control switch 24 V 2W POR Reaction at error situation transmitter error error message LED C...

Страница 12: ...e with EN 60 654 IEC 60654 1 and 60654 3 Package is a box Products in boxes is possible to load on the pallets pallet is returnable On the outer side of the package is stated manufacturer label name a...

Страница 13: ...us waste 2 Installation and dismantling of actuator Abide by safety measures Notes Repeatedly verify whether placing of EA correspondents to part Operating conditions If actual conditions differ from...

Страница 14: ...th a tube with threads on the both ends see dimensional drawing P 0100 While mounting the lever mechanism the angle between the lever and the pull rod is to be more than 15 and less than 165 The coars...

Страница 15: ...ection protection switched off directly with the corresponding position or torque switches After electric connection it is recommended Checking of wiring Set the actuator into a mid position Check the...

Страница 16: ...on professional competence Disconnect the electrical servo drive from electrical power network Observe safety regulations The adjustment can be performed at a mechanically and electrically connected...

Страница 17: ...0 of the EA SPR terminal board Put the actuator to the position closed with the handwheel or with the local electric position control until the corresponding position switch S4 Rotate the transmitter...

Страница 18: ...ate measured on the terminals 81 82 to 0 mA or 4mA Set the actuator to the position open Turn the adjusting trimmer GAIN Fig 7 to adjust the output current signal rate measured on the terminals 81 82...

Страница 19: ...torque 5 blinks way of regulation 4 blinks wide position Notes 1 The controller at autocalibration automatically sets the feedback type resistant current 2 Parameters set in the production plant if c...

Страница 20: ...he controller with D4 diode at initialisation 4 blinks improper connection of the torque switches 5 blinks improper connection of the feedback transmitter 8 blinks bad sense of actuator s turning dire...

Страница 21: ...son as required in the Chapter 1 2 After the EA is put into operation it is necessary to check whether during manipulation its surface finishing was not damaged the damages should be eliminated to pre...

Страница 22: ...ssion bearings type KX with yellow liner and actuators gearings Changing or filling grease up during first years operation is not required If the electric actuator works only occasionally it is necess...

Страница 23: ...3 592 382 3 1 Capacitor 300 047 63 540 305 1 Micro switch CHERRY DB 6G A1LB 64 051 466 4 1 Resistant wire transmitter potentiometer RP19 1x100 64 051 812 8 1 Resistant wire transmitter potentiometer R...

Страница 24: ...22 SP 0 SPR 0 6 Accessories 6 1 Wiring diagrams Wiring diagrams for EA SP 0 Wiring diagrams for EA SP 0 24 V DC...

Страница 25: ...Z315a connection of EA SPR 24 V DC with resistant feedback and with space heater B1 remote transmitter resistive single B3 electronic position transmitter EPV S3 positional switch open S4 positional...

Страница 26: ...24 SP 0 SPR 0 6 2 Dimensional drawings The dimensions are valid for version with convertern and SPR 0 with controller...

Страница 27: ...SP 0 SPR 0 25...

Страница 28: ...26 SP 0 SPR 0...

Страница 29: ...SP 0 SPR 0 27...

Страница 30: ...28 SP 0 SPR 0...

Страница 31: ...SP 0 SPR 0 29 Shape A Shape C Position indicator VERSION FLANGE The dimensions are valid for version with converter SHAPE...

Отзывы: