Error Messages and Troubleshooting
53
Main Menu (v2.6)
REFUsol 20K...33K-2T
982079 | 05 | 2021-03
En
gl
is
h
D
eu
ts
ch
Tab. 8:
Event list
with error and information messages
ID
Event name Event description Measure
ID01 GridOVP
AC voltage in the
mains is too high.
The inverter automatically returns to normal operating status when the AC voltage is
again within the permitted limits.
ID02 GridUVP
AC voltage in the
mains is too low.
The inverter automatically returns to normal operating status when the AC voltage is
again within the permitted limits.
If the event still occurs, check the AC supply to the inverter.
ID03 GridOFP
The frequency of
the AC power grid
is too high.
The inverter automatically returns to normal operating status when the frequency is
again within the permitted limits.
ID04 GridUFP
The frequency of
the AC mains is
too low.
ID05 PVUVP
DC voltage is too
low.
Check the wiring of the connected PV modules for damage, insulation damage and
correct connection.
The inverter automatically returns to normal operating status after the cause of the
fault has been rectified.
ID09 PvOVP
DC voltage is too
high.
ID06 VLvrtlow
AC voltage is too
low.
Check the applied AC voltages; if critical voltage conditions persist, contact your pow
-
er supply company.