BA_REFUSOL 008K-020K_V08.1_EN
54
Copyright REFU
sol
GmbH
Error
code
Error message
Description
Action
0A011B
Activation PS 2
DC link voltage drop during acti-
vation
0A011C
Activation PS 3
Target value for balancing is
invalid.
0A011D
Activation PS 4
Balancing has failed
Please contact Service.
0A011E
Activation PS 5
Uploading of DC links has failed.
0A011F
Parameter error PS
5
Faulty reading or writing process
in power section memory
1.) Switch off device with DC dis-
connector.
2.) Wait until the display has
turned off completely.
3.) Switch on device with DC dis-
connector.
If this does not rectify the error,
contact Service.
0A0120 Communication
PS
Communication malfunction be-
tween power section and control
and regulation unit
Do nothing. The inverter will ac-
knowledge the error automatically.
If problem occurs repeatedly, con-
tact Service.
0A0130 PS
elements
Faulty configuration of elements
for the power section
Please contact Service.
0A0131
Combine relay
Switching the combine relay has
failed.
0A200D
Overtemperature 6
Device temperature too high
Do nothing. The inverter will ac-
knowledge the error automatically.
If problem occurs repeatedly, con-
tact Service
0B0001
System 1
Error in error management sys-
tem
Please contact Service.
0B0002
System 2
Error memory is full.
0B0003
System 3
Error memory is full
0D0001 System
error
A connection to the power sec-
tion could not be established
during the firmware update.
1.) Switch off device with DC dis-
connector.
2.) Wait until the display has
turned off completely.
3.) Switch on device with DC dis-
connector.
If this does not rectify the error,
contact Service.