GmbH
27
4.12 PV- Generator DC Connection
CAUTION
Before connecting the PV strings, connect the inverter to the power sup-
ply network and to the ground bolt to ensure that the device is safely
connected to the protective conductor.
Connect the PV strings to the inverter only in the de-energized state, op-
timally in the dark because that is when the PV strings are inactive.
The protective conductor must be connected to the housing separately
from and in addition to the power supply connection.
WARNING
Live PV strings can be under lethal voltages.
Before connecting the PV strings, verify that the open circuit voltage
does not exceed 50 V.
The DC connection is effected with MC4-plugs and sockets. Ensure that you use DC
connectors which are suitable for the particular cable diameter. If you use connectors
which are not suitable for the particular cable diameter, the protection class of the de-
vice may fall below IP65.
Whenever it is switched on, the inverter
automatically checks the insulation of the PV
generator. If the insulation is defective, the inverter
switches off automatically. In this
case, it is absolutely mandatory that the insulation fault of the PV generator be repaired
before the PV generator is connected to the inverter.
Be absolutely sure to verify proper polarity when connecting the PV strings. Any inap-
propriate connection of individual strings may damage the module strings. The inverter
is protected by an integrated polarity reversal protection diode. Protect the connectors
such that they cannot be pulled off inadvertently.
Close unused connectors with plugs. If you fail to do this, the protection class of the
device may fall below IP65.
The connection has to be strictly done according to chapter
Fehler! Verweisquelle
konnte nicht gefunden werden.
of the operating instructions. By non-observance the
dc-disconnector can be destroyed.
4.13 DC Connecting Line
Please note the following information (plug type, cross section) regarding the DC power cable.
Denomination
Type
Item No.
MultiContact
Diameter wire insulation
in mm
Cable cross section in
mm²
Connector plug
PV-KST4/6I-UR
32.0015P0001
3 -6
4 - 6
Connector plug
PV-KST4/6II-UR 32.0017P0001
5,5 - 9
4 - 6
Connector socket
PV-KBT4/6I-UR
32.0014P0001
3 - 6
4 - 6
Connector socket
PV-KBT4/6II-UR 32.0016P0001
5,5 - 9
4 - 6
To attach the crimp contacts on the site, you might acquire the pliers, type PV-CZM -19100 by Mul-
tiContact.