Disassembly
18 — English
Fillcontrol Plus Compact — 03.05.2022 - Rev. D
Cleaning the system isolator with integrated dirt trap
Clean the "BA" system isolator. The system isolator must be cleaned regularly.
Proceed as follows:
1.
Use the shut-off devices up- and downstream of the device to lock the
system and drinking water lines.
2.
Use the maintenance wrench (opening 27) to slowly unscrew the system
isolator lock.
3.
Remove the dirt trap.
–
Support body with strainer.
4.
Remove the BA cartridge.
–
The BA cartridge projects due to the spring load tension in the
system isolator.
5.
Clean all components with clear running water.
–
Strainer
–
Support body
–
BA cartridge
6.
Check the return-flow preventer in the system isolator for proper
functioning.
7.
Check the gaskets for integrity and cleanliness and replace, if necessary.
8.
Insert the cleaned BA cartridge in the system isolator.
9.
Insert the cleaned dirt trap in the system isolator.
10. Tighten the system isolator lock.
11. Slowly open the shut-off devices up- and downstream of the device.
The cleaning process is completed.
Checking the pressure reducer
Check the proper functioning of the pressure reducer.
•
Inspect the device at regular intervals and in any event at least once per
year.
Checking the maintenance battery
Check the maintenance battery.
•
Inspect the battery at regular intervals and in any event at least once per
year.
•
Replace the battery (standard 9V PP3 battery) if it is discharged.
10
Disassembly
DANGER
Risk of serious injury or death due to electric shock.
If live parts are touched, there is risk of life-threatening injuries.
•
Ensure that the system is voltage-free before installing the device.
•
Ensure that the system is secured and cannot be reactivated by other
persons.
•
Ensure that installation work for the electric connection of the device is
carried out by an electrician, and in compliance with electrical
engineering regulations.
DANGER
Risk of serious injury or death due to electric shock
Some parts of the device's circuit board may still carry 230 V voltage even
with the device physically isolated from the power supply.
•
Before you remove the covers, completely isolate the device controller
from the power supply.
•
Verify that the main circuit board is voltage-free.
CAUTION
Risk of burns
Escaping hot medium can cause burns.
•
Maintain a sufficient distance from the escaping medium.
•
Wear suitable personal protective equipment (safety gloves and
goggles).
CAUTION
Risk of burns on hot surfaces
Hot surfaces in heating systems can cause burns to the skin.
•
Wait until hot surfaces have cooled down or wear protective safety
gloves.
•
The operating authority is required to place appropriate warning signs
in the vicinity of the device.
CAUTION
Risk of injury due to pressurised liquid
If installation or maintenance work is not carried out correctly, there is a risk
of burns and other injuries at the connection points, if pressurised hot water
or steam suddenly escapes.
•
Ensure proper disassembly.
•
Ensure that the system is de-pressurised before performing the
disassembly.
Proceed as follows:
1.
Prior to dismantling, block off all "water"-side connections to the device.
2.
Disconnect the system from the power supply and secure it against
unintended reactivation.
3.
Disconnect the power cable of the device from the power supply.
4.
Disconnect and remove all cables from the terminals of the device
controller.
5.
Undo all hose and pipe connections between the device and the system
and remove them completely.
6.
Drain all water from the device.
7.
If necessary, physically remove the device from the system.
The device is removed.
11
Annex
11.1
Reflex Customer Service
Central customer service
Central telephone number: +49 (0)2382 7069 - 0
Customer Service extension: +49 (0)2382 7069 - 9505
Fax: +49 (0)2382 7069 - 9523
E-mail: [email protected]
Technical Hotline
For questions about our products
Telephone number: +49 (0)2382 7069-9546
Monday to Friday 8:00 to 16:30
11.2
Conformity and standards
Device conformity declarations are available on the Reflex homepage.
www.reflex-winkelmann.com/konformitaetserklaerungen
Alternatively, scan the QR code:
11.3
Guarantee
The respective statutory guarantee regulations apply.