Installation
Fillcontrol Auto
—
22.09.2020 - Rev. C
English
—
7
Installation with user-supplied system separator tank
1
Pump "PU"
3
"BT" system separator vessel
2
"PIS" pressure transducer
4
"ST" dirt trap
During installation, observe the following points:
•
Ambient temperatures up to 35 °C
•
Pipe length (see table)
•
"WC" make-up connection at must be least 100 mm above the "PU" pump
intake connection.
•
Minimum diameter of the intake line and the pressure line (see table).
•
Adherence to EN 1717
•
Recommended nominal volume of the system separator tank o
f ≤ 200 l
•
Overflow with sufficient dimensions to match the maximum possible water
supply is installed.
•
A shut-off valve is installed in the supply to the system separator tank.
Nominal diameters of the intake and pressure lines depending on the required
make-up pressure
Make-up pressure
> 3.7 bar
≤
3.7 bar
Pressure line
≤
10 m
DN 32
DN 40
Pressure line
≤
2 m
DN 32
DN 40
Note!
For installation at the same level, open the Customer menu to set the
"P
0
" minimum operating pressure to the "p
0
" initial pressure of the
"MAG" diaphragm expansion vessel, otherwise, you must correct with
"hst", see chapter 7.2 "Determining the P
for the controller" on page 9 .
6.3.2
Hydraulic connection
6.3.2.1
Connection to the facility system
Note!
Starting up of the pump causes vibration in the device. This transfers
loud noises into the system pipes.
–
Connect the pipes to the device using flexible connections.
Connection to the system circuit with a system separator tank for the make-up
with mains water.
1
Pump "PU"
WC Make-up lines for mains water
•
Intake line to pump
•
Pressure line to the
system circuit
2
"Fillsoft" softening system
3
Contact water meter
4
"BT" system separator vessel
5
"ST" dirt trap
Comply with the following requisites for the installation and connection of an
open system separator tank.
•
Make-up temperatures up to 70° C
•
Pipeline lengths, see chapter 6.3.1 "Floor mounting" on page 6 .
•
Outlet from the system separator tank at least 100 mm above the intake
connection of the "PU" pump.
–
"WC" intake line to "PU" pump with constant incline to the system
separator tank.
Note!
At make-up temperatures > 70 °C and the use in system circuits
without system separator tanks, you must plan according to the local
conditions, see chapter 12.1 "Reflex Customer Service" on page 16 .
6.4
Switching and make-up variants
Example diagram for a pressure-dependent make-up with water in a solar
installation with diaphragm expansion vessel.
1
Pump "PU"
WC Make-up lines
•
Intake line to "PU"
pump
•
Pressure line to the
system circuit
2
"BT" system separator vessel
3
"ST" dirt trap
DN Nominal diameter of the
make-up lines
In system circuits with a diaphragm expansion vessel, the "PIS" pressure
transducer in the device monitors the make-up with mains water. When the
required filling pressure for water make-up drops below the minimum value, the
pressure transducer sends a signal to the device controller. The controller
activates the pump. Mains water from the system separator tank is added to the
system circuit.
Proceed as follows:
1.
In the Customer menu, set the device to "Magcontrol", see chapter 9.2.1
"Customer menu" on page 13 .
2.
Connect the pressure line near the connection to the diaphragm expansion
vessel.
–
This ensures that the "PIS" pressure transducer detects the filling
pressure required for the make-up with mains water.
–
For calculating the filling pressure, see chapter 7.2 "Determining the
P
minimum operating pressure for the controller" on page 9 .
3.
Do not use nominal diameters below the specified diameters for the
"WC"make-up lines, see chapter 6.3.1 "Floor mounting" on page 6 .
–
You will avoid an undesired cycling of the make-up.
4.
In solar plants, use the "BT" system separator tank to prepare the
water/glycol mixture.
–
Size the system separator tank with at least 1.5 times the system
volume.