Technical data
Fillcontrol Auto
—
22.09.2020 - Rev. C
English
—
5
Information on the type plate
Meaning
at site
Set minimum operating pressure
max. pressure saftey valve
factory - aline
Factory set actuating pressure of the
safety valve
at site
Set actuating pressure of the safety
valve
4.3.2
Type code
No.
Type code (example)
1
Device designation
2
Auto
Fillcontrol Auto A 5,5
3
Maximum working pressure (in bar)
1
2 3
4.4
Function
1
Pump "PU"
2
"Fillsoft" softening system
3
"FQIRA+" contact water meter
4
"BT" system separator vessel
5
"ST" dirt trap
WC
Make-up lines
•
From the system separator tank to the pump (intake line)
•
From the pump to the system circuit (pressure line)
Levelcontrol External signal line for the Levelcontrol make-up variant
Magcontrol Internal signal line for the Magcontrol make-up variant
•
From the "PIS" pressure transducer to the controller
The device controller uses the pump to regulate the make-up with mains water
for the system circuit.
The controller monitors the following parameters:
•
Make-up time
•
Make-up cycles
•
Make-up quantity, if an optional contact water meter is installed
The controller will detect small leaks in the system. When a leak is detected, the
controller interrupts the make-up with as soon as the make-up time or the make-
up cycles are exceeded. An integrated insufficient water protection sensor
deactivates the pump to prevent it from running dry.
You can set two make-up variants in the device, "Magcontrol" or "Levelcontrol".
These variants depend on the system circuit.
•
Adding water to system circuits with a diaphragm expansion vessel
(Magcontrol).
The pressure transducer sends a signal to the controller if the pressure
drops below the minimum working pressure of the system circuit. The
controller activates the pump. mains water is added to the system circuit
from the system separator vessel. For calculating the filling pressure into
the system circuit, see chapter 7.2 "Determining the P
pressure for the controller" on page 9 .
•
Adding water to system circuits with a pressurisation unit
(
Levelcontrol).
A pressurisation unit monitors the filling level in the expansion vessel.
When the filling level falls below the minimum level, the pressurisation
unit sends a signal to the device controller. The controller activates the
pump. mains water is added to the system circuit from the system
separator vessel.
The make-up variant is set in the Customer menu, see chapter 9.2.1 "Customer
menu" on page 13 .
The controller may monitor additional function, if you combine various
accessories.
The following components are available as optional accessories:
•
"Reflex Fillsoft" water softening system
•
"FQIRA+" contact water meter
Note!
For optional accessories, see chapter 4.6 "Optional equipment and
accessories" on page 5 .
4.5
Scope of delivery
The scope of delivery is described in the shipping document and the content is
shown on the packaging.
Proceed as follows:
1.
Immediately after receipt of the goods, please check the shipment for
completeness and damage.
2.
Please notify us immediately of any transport damage.
Basic make-up equipment:
•
The pre-wired device.
•
Operating manual.
4.6
Optional equipment and accessories
The following optional equipment and accessories are available for this device:
•
"FQIRA+" contact water meter.
•
Expansions for Reflex Basic controllers.
–
Bus modules
•
Profibus DP
•
Ethernet
Note!
Separate operating instructions are supplied with accessories.
5
Technical data
Permissible ambient temperature
0
–
35 °C
Degree of protection
IP 54
Noise level
55 dB
Electric output
750 W
Power supply
230 V / 50 Hz
Fusing
4 A
Number of RS-485 interfaces
2
Weight
18.6 kg
Height
690 mm
Width
470 mm
Depth
440 mm
Inlet connection
G 1 ¼"
Outlet (return) connection
G 1"
Delivery rate
4.2 m³/h
Max. supply pressure
10 bar
Max. working pressure
5.5 bar
Permissible gauge operating pressure
10 bar
Permissible operating temperature
70 °C