Commissioning 

 

 

 

Fillcontrol Auto 

 22.09.2020 - Rev. C 

 

English  

 9 

 

Terminal 
number 

Signal 

Function 

Wiring 

22 

PE (shield) 

Pressure analogue input. 

 

Display at the controller. 

 

For make-up actuation 

 

For the "Magcontrol" make-
up variant 

Factory 

23 

- Pressure 
(signal) 

24 

+ Pressure (+ 
18 V) 

29 

RS-485 interface. 

User, optional 

30 

31 

GND 

32 

+ 24 V (supply) 
E1 

Supply for E1 and E2. 

Pre-wired, 
bridged 

33 

E1 

Contact water meter (in 
"Fillset Impulse", for example) 

 

Evaluation of the make-up. 

 

Contact 32/33 closed = 
meter pulse. 

User, optional 

 
6.5.2

 

RS-485 interface 

The following options are available via the interface: 

 

Data polling by the controller. 

  

Pressure 

  

Pump operating states. 

 

Cumulated quantity of the "FQIRA+" contact water meter. 

  

All messages, see chapter 9.3 "Messages" on page 14 . 

 

All entries in the fault memory. 

 

Communication with control centres. 

 

Communication with other equipment. 

 



Note! 
If required, please request the RS-485 interface protocol from the Reflex 
Customer Service. 

 

Connection details. 

 

Accessory information and data. 

 
6.5.2.1

 

Connecting the RS-485 interface 

Connect the interface as follows: 
1. 

For connecting the interface use only a cable with these properties: 

  

LJYCY (TP), 4 × 2  × 0.8, maximum overall bus length 1000 m. 

2. 

Use a shielded cable to connect the interface to terminals 29, 30, 31 of the 
main board in the control cabinet. 

  

For connecting the interface, see chapter 6.5 "Electrical connection" 
on page 8 . 

3. 

When using the device with a control centre not supporting an RS-485 
interface (RS-232, for example), you must use a corresponding adapter. 

 

6.6

 

Installation and commissioning certificate  



Note! 
The installation and commissioning certificate can be found at the end 
of the operating manual. 

 

7

 

Commissioning 



Note! 
Confirm that installation and start-up have been carried out correctly 
using the installation and commissioning certificate. This action is a 
prerequisite for the making of warranty claims. 

  

Have the Reflex Customer Service carry out commissioning and 
the annual maintenance. 

 

 

7.1

 

Requirements for initial commissioning  

The device will be ready for initial commissioning when the tasks described in 
the "Installation" chapter have been completed. Note the following information 
on initial commissioning: 

 

The device is installed. 

 

The water connections to the system circuit are established. 

 

The device shut-off valves are closed. 

  

Shut-off valve from the "DC" make-up line to the system circuit. 

  

Shut-off valve of the "WC" make-up line to the fresh water main. 

 

"PIS" pressure monitoring is ready. 

 

The electrical connection has been created according to applicable 
national and local regulations. 

 

Establish a 230 V power supply by plugging the power plug into a corresponding 
outlet. The controller is in Stop mode. 
 

7.2

 

Determining the P

0

 minimum operating pressure for the 

controller 

The "P

0

" minimum working pressure for the device is used in system circuits with 

a diaphragm expansion vessel. 
Calculate the "P

0

" minimum working pressure for the device: 

 

 

 

 

The device is installed at the same level as the diaphragm expansion 
vessel: 

  

hst = 0, P0 = p0* 

 

The device is installed at a lower level than the diaphragm expansion 
vessel: 

  

P

0

 = p0 + h

st

/10* 

 

The device is installed at a higher level than the diaphragm expansion 
vessel: 

  

P

0

 = p0 - h

st

/10* 

 

 

*p0 in bar, h

st 

in metres 

 



Note! 
Calculate the filling pressure for system circuit make-up using fresh 
water as follows: 

Filling pressure ≥ P

0

 + 0.3 bar 

 



Note! 
When planning, note that the working range of the device must come 
within the pressurisation working range, which extends from the initial 
pressure "PA" to the final pressure "PE". 

 

7.3

 

Filling the device with water 

 CAUTION 

 

Risk of injury due to pump start-up 
Hand injuries may occur when the pump starts up if you turn the pump 
motor at the impeller using a screwdriver. 

 

Switch the pump to a zero-volts state before turning the pump at the 
fan wheel with a screwdriver. 

 

ATTENTION 

 

Device damage due to pump start-up 
Pump damage may occur when the pump starts up if you turn the pump 
motor at the impeller using a screwdriver. 

 

Switch the pump to a zero-volts state before turning the pump at the 
fan wheel with a screwdriver. 

 

Содержание Fillcontrol Auto

Страница 1: ...Fillcontrol Auto 22 09 2020 Rev C GB Operating manual Original operating manual...

Страница 2: ...cal connection 8 6 5 1 Terminal diagram 8 6 5 2 RS 485 interface 9 6 6 Installation and commissioning certificate 9 7 Commissioning 9 7 1 Requirements for initial commissioning 9 7 2 Determining the P...

Страница 3: ...ult in death or severe irreversible injuries WARNING Serious damage to health The sign in combination with the signal word Warning indicates imminent danger failure to observe the safety information c...

Страница 4: ...stems Solar circuits The device is used in combination with a user supplied open system separator tank Note An application without system separator tank is possible For customised design and adjustmen...

Страница 5: ...For calculating the filling pressure into the system circuit see chapter 7 2 Determining the P0 minimum operating pressure for the controller on page 9 Adding water to system circuits with a pressuris...

Страница 6: ...possible transport damage 2 Document any damage 3 Contact the forwarding agent to register your complaint 6 2 Preparatory work Preparing the device installation Frost free well ventilated room Room te...

Страница 7: ...n open system separator tank Make up temperatures up to 70 C Pipeline lengths see chapter 6 3 1 Floor mounting on page 6 Outlet from the system separator tank at least 100 mm above the intake connecti...

Страница 8: ...electric shock Some parts of the device s circuit board may still carry 230 V voltage even with the device physically isolated from the power supply Before you remove the covers completely isolate the...

Страница 9: ...ng and the annual maintenance 7 1 Requirements for initial commissioning The device will be ready for initial commissioning when the tasks described in the Installation chapter have been completed Not...

Страница 10: ...h Magcontrol make up variant Calculation of the minimum operating pressure see chapter 7 2 Determining the P0 minimum operating pressure for the controller on page 9 Safety valve pressure Enter the va...

Страница 11: ...operation can be started after initial commissioning The following prerequisites must be met for automatic operation P0 minimum working pressure is entered in the controller The device is filled with...

Страница 12: ...sioning the factory settings must first be adjusted for the system specific conditions Note For a description of the operation see chapter 9 1 Operator panel on page 12 All grey marked menu items must...

Страница 13: ...ble soft water capacity Replacement 18 months This value is only displayed if YES has been set in the With softening menu option Manufacturer specification for the replacement interval of the softenin...

Страница 14: ...an the dirt trap Replace the float valve 04 1 Pump YES Pump does not start PU pump is stuck Pump motor defective 10 A fuse defective Contractor Klixon tripped Manually turn the pump to start Replace t...

Страница 15: ...ons Ensure that installation work for the electric connection of the device is carried out by an electrician and in compliance with electrical engineering regulations CAUTION Risk of injury due to pre...

Страница 16: ...ore you remove the covers completely isolate the device controller from the power supply Verify that the main circuit board is voltage free CAUTION Risk of burns Escaping hot medium can cause burns Ma...

Страница 17: ...Installation and commissioning certificate This device has been installed and commissioned in accordance with the instructions provided in the operating manual The settings in the controller match th...

Страница 18: ...SI1415enC 11 20 Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com...

Отзывы: