Controller 

 

 

 

14 

  English  

Fillcontrol Auto 

 22.09.2020 - Rev. C 

 

 

9.2.2

 

Service menu 

The Service menu is password-protected. Only Reflex service technicians are able 
to access this menu, see chapter 12.1 "Reflex Customer Service" on page 16 . 

 

Parameter 

Setting 

Comment 

 

 

 

Make-up 

 

 

Pressure differential, "NSP" 
make-up 

0.2 bar 

Only Magcontrol 

Pressure differential, filling 
pressure PF 

 P0 

0.3 bar 

Only Magcontrol 

Water volume per contact  10 l / K 

Only if a water meter is installed. 

Maximum filling contacts  OFF 

Limits the filling volume. 
Only if a water meter is installed. 

 

9.3

 

Messages 

The display provides alarms in plain text and the ER codes shown in the list. Use 
the arrow buttons to scroll through multiple alarms displayed at the same time. 
The fault memory stores the last 20 alarms for review, see chapter 7.5 
"Parametrising the controller in the Customer menu" o
n page 10 . 
Alarm causes can be eliminated by the operator or a specialist workshop. If this is 
not possible, contact the Reflex Customer Service. 

 



Note! 
Clearing of the caus

e must be confirmed by pressing the “Ack” button on 

the operator panel. All other alarms are automatically reset as soon as 
the cause has been eliminated. 

 



Note! 
Floating contacts, setting in the Customer menu, see chapter 7.5 
"Parametrising the controller in the Customer menu" o
n page 10 . 

 

 

ER 

Code 

Alarm 

Group alarm 

Causes 

Remedy 

Alarm reset 

01 

Min. pressure 

 

Only with Magcontrol 

YES 

The set value for the "P

0

" minimum working 

pressure has been exceeded. 

 

Water loss in the system. 

 

Expansion vessel defective. 

 

Fault at the "PU" pump. 

 

Check the system for leaks. 

 

Replace the expansion vessel. 

 

Check the function in manual mode. 

  

"PU" pump 

"Quit" 

02.1 

Insufficient water  

 

No water in the system separator vessel. 

 

Ball valve in make-up line closed. 

 

Dirt trap clogged. 

 

Float valve defective. 

 

Open the ball valve in the make-up 
line. 

 

Clean the dirt trap. 

 

Replace the float valve. 

 

04.1 

Pump 

YES 

Pump does not start. 

 

"PU" pump is stuck. 

 

Pump motor defective. 

 

10 A fuse defective. 

 

Contractor (Klixon) tripped. 

 

Manually turn the pump to start. 

 

Replace the pump motor. 

 

Replace the fuse. 

 

Check the mechanical and electrical 
functions of the pump motor. 

"Quit" 

06 

Make-up time 

 

Set time for the make-up time has been 
exceeded. 

 

Severe water loss in the system. 

 

Make-up line not connected. 

 

Make-up rate insufficient. 

 

Make-up hysteresis too high. 

 

Check the system for leaks. 

 

Connect the make-up system. 

 

Check the make-up rate. 

 

Check the make-up hysteresis. 

"Quit" 

07 

Make-up cycles 

 

Set value for the make-up cycles has been 
exceeded. 

 

Leakage in the system. 

 

Check the system for leaks. 

"Quit" 

08 

Pressure measurement 

 

Only with Magcontrol 

YES 

Controller receives incorrect signal. 

 

Pressure transducer plug not plugged 
in. 

 

Broken wire from "PIS" pressure 
transducer. 

 

"PIS" pressure transducer defective. 

 

Plug in the plug. 

 

Replace the wire. 

 

Replace the "PIS" pressure 
transducer. 

"Quit" 

10 

Maximum pressure 

 

Only with Magcontrol 

 

Set value for the maximum pressure has 
been exceeded. 

 

Safety valve defective. 

 

Pipe to system has insufficient 
diameter. 

 

Check the actuating pressure of the 
safety valve. 

 

Replace the safety valve. 

 

Install new pipe to the system with 
sufficient diameter. 

"Quit" 

11 

Make-up volume 

 

Only if "With water 
meter" is activated in the 
Customer menu. 

 

Set value of the water meter has been 
exceeded. 

 

Leakage in the system. 

 

Water volume per contact incorrectly 
set in the Service menu. 

 

Check the system for leaks. 

 

Check the set value. 

"Quit" 

12 

Filling time 

 

Only with Magcontrol 

 

Set value for the maximum filling time has 
been exceeded. 

 

System volume too large 

(≤

 3000Liter). 

 

Restart the filling process 

"Quit" 

13 

Filling volume 

 

Only with Magcontrol 
and contact water meter 

 

 

System volume too large 

(≤

 3000Liter). 

 

Water volume per contact incorrectly 
set in the Service menu. 

 

If necessary, restart the filling process 

 

Set the water quantity per contact in 
the Service menu. 

"Quit" 

16 

Power failure 

 

No power. 

Check power supply. 

 

Содержание Fillcontrol Auto

Страница 1: ...Fillcontrol Auto 22 09 2020 Rev C GB Operating manual Original operating manual...

Страница 2: ...cal connection 8 6 5 1 Terminal diagram 8 6 5 2 RS 485 interface 9 6 6 Installation and commissioning certificate 9 7 Commissioning 9 7 1 Requirements for initial commissioning 9 7 2 Determining the P...

Страница 3: ...ult in death or severe irreversible injuries WARNING Serious damage to health The sign in combination with the signal word Warning indicates imminent danger failure to observe the safety information c...

Страница 4: ...stems Solar circuits The device is used in combination with a user supplied open system separator tank Note An application without system separator tank is possible For customised design and adjustmen...

Страница 5: ...For calculating the filling pressure into the system circuit see chapter 7 2 Determining the P0 minimum operating pressure for the controller on page 9 Adding water to system circuits with a pressuris...

Страница 6: ...possible transport damage 2 Document any damage 3 Contact the forwarding agent to register your complaint 6 2 Preparatory work Preparing the device installation Frost free well ventilated room Room te...

Страница 7: ...n open system separator tank Make up temperatures up to 70 C Pipeline lengths see chapter 6 3 1 Floor mounting on page 6 Outlet from the system separator tank at least 100 mm above the intake connecti...

Страница 8: ...electric shock Some parts of the device s circuit board may still carry 230 V voltage even with the device physically isolated from the power supply Before you remove the covers completely isolate the...

Страница 9: ...ng and the annual maintenance 7 1 Requirements for initial commissioning The device will be ready for initial commissioning when the tasks described in the Installation chapter have been completed Not...

Страница 10: ...h Magcontrol make up variant Calculation of the minimum operating pressure see chapter 7 2 Determining the P0 minimum operating pressure for the controller on page 9 Safety valve pressure Enter the va...

Страница 11: ...operation can be started after initial commissioning The following prerequisites must be met for automatic operation P0 minimum working pressure is entered in the controller The device is filled with...

Страница 12: ...sioning the factory settings must first be adjusted for the system specific conditions Note For a description of the operation see chapter 9 1 Operator panel on page 12 All grey marked menu items must...

Страница 13: ...ble soft water capacity Replacement 18 months This value is only displayed if YES has been set in the With softening menu option Manufacturer specification for the replacement interval of the softenin...

Страница 14: ...an the dirt trap Replace the float valve 04 1 Pump YES Pump does not start PU pump is stuck Pump motor defective 10 A fuse defective Contractor Klixon tripped Manually turn the pump to start Replace t...

Страница 15: ...ons Ensure that installation work for the electric connection of the device is carried out by an electrician and in compliance with electrical engineering regulations CAUTION Risk of injury due to pre...

Страница 16: ...ore you remove the covers completely isolate the device controller from the power supply Verify that the main circuit board is voltage free CAUTION Risk of burns Escaping hot medium can cause burns Ma...

Страница 17: ...Installation and commissioning certificate This device has been installed and commissioned in accordance with the instructions provided in the operating manual The settings in the controller match th...

Страница 18: ...SI1415enC 11 20 Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com...

Отзывы: