Controller
14
—
English
Fillcontrol Auto
—
22.09.2020 - Rev. C
9.2.2
Service menu
The Service menu is password-protected. Only Reflex service technicians are able
to access this menu, see chapter 12.1 "Reflex Customer Service" on page 16 .
Parameter
Setting
Comment
Make-up
Pressure differential, "NSP"
make-up
0.2 bar
Only Magcontrol
Pressure differential, filling
pressure PF
–
P0
0.3 bar
Only Magcontrol
Water volume per contact 10 l / K
Only if a water meter is installed.
Maximum filling contacts OFF
Limits the filling volume.
Only if a water meter is installed.
9.3
Messages
The display provides alarms in plain text and the ER codes shown in the list. Use
the arrow buttons to scroll through multiple alarms displayed at the same time.
The fault memory stores the last 20 alarms for review, see chapter 7.5
"Parametrising the controller in the Customer menu" on page 10 .
Alarm causes can be eliminated by the operator or a specialist workshop. If this is
not possible, contact the Reflex Customer Service.
Note!
Clearing of the caus
e must be confirmed by pressing the “Ack” button on
the operator panel. All other alarms are automatically reset as soon as
the cause has been eliminated.
Note!
Floating contacts, setting in the Customer menu, see chapter 7.5
"Parametrising the controller in the Customer menu" on page 10 .
ER
Code
Alarm
Group alarm
Causes
Remedy
Alarm reset
01
Min. pressure
•
Only with Magcontrol
YES
The set value for the "P
0
" minimum working
pressure has been exceeded.
•
Water loss in the system.
•
Expansion vessel defective.
•
Fault at the "PU" pump.
•
Check the system for leaks.
•
Replace the expansion vessel.
•
Check the function in manual mode.
–
"PU" pump
"Quit"
02.1
Insufficient water
No water in the system separator vessel.
•
Ball valve in make-up line closed.
•
Dirt trap clogged.
•
Float valve defective.
•
Open the ball valve in the make-up
line.
•
Clean the dirt trap.
•
Replace the float valve.
04.1
Pump
YES
Pump does not start.
•
"PU" pump is stuck.
•
Pump motor defective.
•
10 A fuse defective.
•
Contractor (Klixon) tripped.
•
Manually turn the pump to start.
•
Replace the pump motor.
•
Replace the fuse.
•
Check the mechanical and electrical
functions of the pump motor.
"Quit"
06
Make-up time
Set time for the make-up time has been
exceeded.
•
Severe water loss in the system.
•
Make-up line not connected.
•
Make-up rate insufficient.
•
Make-up hysteresis too high.
•
Check the system for leaks.
•
Connect the make-up system.
•
Check the make-up rate.
•
Check the make-up hysteresis.
"Quit"
07
Make-up cycles
Set value for the make-up cycles has been
exceeded.
•
Leakage in the system.
•
Check the system for leaks.
"Quit"
08
Pressure measurement
•
Only with Magcontrol
YES
Controller receives incorrect signal.
•
Pressure transducer plug not plugged
in.
•
Broken wire from "PIS" pressure
transducer.
•
"PIS" pressure transducer defective.
•
Plug in the plug.
•
Replace the wire.
•
Replace the "PIS" pressure
transducer.
"Quit"
10
Maximum pressure
•
Only with Magcontrol
Set value for the maximum pressure has
been exceeded.
•
Safety valve defective.
•
Pipe to system has insufficient
diameter.
•
Check the actuating pressure of the
safety valve.
•
Replace the safety valve.
•
Install new pipe to the system with
sufficient diameter.
"Quit"
11
Make-up volume
•
Only if "With water
meter" is activated in the
Customer menu.
Set value of the water meter has been
exceeded.
•
Leakage in the system.
•
Water volume per contact incorrectly
set in the Service menu.
•
Check the system for leaks.
•
Check the set value.
"Quit"
12
Filling time
•
Only with Magcontrol
Set value for the maximum filling time has
been exceeded.
•
System volume too large
(≤
3000Liter).
•
Restart the filling process
"Quit"
13
Filling volume
•
Only with Magcontrol
and contact water meter
•
System volume too large
(≤
3000Liter).
•
Water volume per contact incorrectly
set in the Service menu.
•
If necessary, restart the filling process
•
Set the water quantity per contact in
the Service menu.
"Quit"
16
Power failure
No power.
Check power supply.
–