Measuring using the Superheat / Subcool mode
See section "Connecting the DIGIMON manifold".
Plug the K-Type plug of the external thermocouples (9) or the clamp
thermocouple (10) into the DIGIMON (sockets on the right (t1) and left (t2) side
of the housing).
Fix the external thermocouple (9) or the clamp thermocouple (10) with adhesive
tape to the required measuring point on the high pressure or suction pressure
side of the system.
Set the appropriate refrigerant (see section "Select refrigerant").
Switch on the temperature difference display: press SUPERHEAT/ SUBCOOL.
Maintenance work on the manifold
A visual inspection of the connections and filling hoses must be carried out
before each use, to check for mechanical damage.
Do not use aggressive cleaning agents or solvents to clean the device. Gentle
household cleaners and soapy water should be used instead.
Manifold seals are subject to mechanical and age-related wear. Therefore, the
manifold should be regularly tested by the user for leaks.
In case of leaky valves, the piston should be replaced (M4-6-04-R/4).
The special REFCO M4-6-11-T tool should be used to change the sight glass on
the manifold.
The manifold should be checked after the replacement of seals to ensure
there are no leaks.
Guarantee
Your new DIGIMON has been developed in accordance with the latest occupational
health and ergonomic requirements and reflects the latest state-of-the-art technology.
REFCO Manufacturing Ltd has been certified in accordance with DIN EN ISO 9001:
2008. Regular quality control checks as well as an accurate manufacturing process
guarantee reliable functionality and are the basis for the REFCO guarantee, in
accordance with the General Terms and Conditions of Sale and Delivery applicable on
the day of delivery. Damages arising from obvious maltreatment or wear are excluded
from the guarantee.