background image

English                                                    Instruction Manual DIGIMON-SE / DIGIMON4 

12 

Connecting the manifold  

a)  with DIGIMON-SE

 

  Connect blue hose (1)      

 

to suction pressure side of system  

  Connect red hose (2)           

 

to high pressure side of system  

  Connect yellow hose (3)           

to vacuum pump  

  Close both valves (5+6) 

 

b)  with DIGIMON4

 

 

Connect blue hose (1)      

     

to suction pressure side of system  

 

Connect red hose (2)           

 

to high pressure side of system  

 

Connect yellow hose 3/8“ (3)         

to vacuum pump 

 

Connect yellow hose 1/4“ (4)          

to  refrigerant cylinder 

 

Close both valves (5+6) 

 

Evacuating the system  

  Switch on the manifold 

  Press the 

 button 

  Connect the hoses 

  Switch on vacuum pump 

  Open all valves 

  Check vacuum display  

  When the ultimate vacuum is achieved, close all valves. 

  Press the 

 button to exit vacuum mode.  

Evacuation time varies depending on the size of the system. A small to 

medium-sized system requires a minimum evacuation time of 20 minutes.  

 

 
 
 

 

 
 

LP/HP 

VAC  

Содержание DIGIMON-SE

Страница 1: ...DIGIMON SE DIGIMON4 Installation and operating guide Digital Manifold...

Страница 2: ...anchor SAE 2 High pressure anchor SAE 3 Vacuum anchor SAE or 3 8 4 Refrigerants anchor SAE 5 Low pressure valve blue 6 High pressure valve red 7 Vacuum valve yellow 8 Refrigerants valve black 9 2 ext...

Страница 3: ...icator 6 Application 7 Connecting the manifold 12 Evacuating the system 12 Filling the system 13 Measuring using the Superheat Subcool modes 14 Maintenance work on the manifold 14 Guarantee 14 Environ...

Страница 4: ...6MPa Under no circumstances should the manifold be used as a pressure regulator especially not when using nitrogen N2 The manifold must not be used with the refrigerant ammonia NH3 R717 The manifold s...

Страница 5: ...o the central T piece when not in use This serves to protect the thread from contamination and damage Technical description The DIGIMON can be used with the following refrigerants R11 R113 R114 R12 R1...

Страница 6: ...olution 0 1 C 0 1 F Optional clamp thermocouple K type Temperature range 40 C to 125 C 40 F to 257 F For pipe diameters of 6mm to 38mm to 1 Plug K type Accuracy of measurement 1 K Resolution 0 1 C 0 1...

Страница 7: ...pressure display function Switch vacuum display function Switch LCD light on off switches off automatically after 1 minute Select refrigerant search forwards select pressure unit Select refrigerant s...

Страница 8: ...cator Illuminating the display Press the button to switch the display light on or off The light switches off automatically after 1 minute Automatic shut off The DIGIMON switches off automatically appr...

Страница 9: ...to select the desired refrigerant from the list During selection you will see a flashing R on the display Press the button to confirm selection of the desired refrigerant The R no longer flashes on th...

Страница 10: ...ice will save the last pressure and temperature units selected Memory function of the analogue pressure display Save value current measurement value press the and buttons at the same time Retrieve mem...

Страница 11: ...e vacuum display Vacuum display values When evacuating the device a maximum of 10 bars will be displayed When the display remains stable the ultimate vacuum has been reached and the evacuation time be...

Страница 12: ...lect pressure unit Hold down the button Use the button to select the desired unit Release both buttons Save value current measurement value press the and buttons at the same time Retrieve memory value...

Страница 13: ...red hose 2 to high pressure side of system Connect yellow hose 3 8 3 to vacuum pump Connect yellow hose 1 4 4 to refrigerant cylinder Close both valves 5 6 Evacuating the system Switch on the manifol...

Страница 14: ...ure and temperature Remove the hoses from the system Open valves 5 6 b with DIGIMON4 manifold Disconnect the yellow hose 3 8 from the vacuum pump and the DIGIMON4 3 and screw the caps onto the 3 8 SAE...

Страница 15: ...sehold cleaners and soapy water should be used instead Manifold seals are subject to mechanical and age related wear Therefore the manifold should be regularly tested by the user for leaks In case of...

Страница 16: ...evice users should observe the disposal regulations applicable in their country Replacement parts and accessories Description Identifier P N Control knob set M4 7 SET B N R Y 4687094 Complete valve se...

Страница 17: ...er a vacuum Factory settings Set the DIGIMON to the Digital display screen Press the and buttons at the same time for 5 seconds Display shows Press the button to exit Resetting the external vacuum sen...

Страница 18: ...y For a correct calibration there should be no pressure or vacuum in the DIGIMON 6 Press the button to select the low pressure side s calibration pressure 400psi 7 Press the button to exit 8 Wait 3 5...

Страница 19: ...he button once Continue holding down the Light button until the display shows Password 000 4 Press the buttons to scroll to code 018 5 Press the button once Display shows T call 6 Press the button onc...

Страница 20: ...cables must be straight unwound 3 While holding down the button continuously switch on the device by pressing the button once Continue holding down the Light button until the display shows Password 0...

Страница 21: ...cool button Read T1 and T2 temperature readings with sensors in the same ice bath They should be within 1 0 C of 0 0 C ON OFF R SET LP End 011xx 24 4 C Take your time use lots of ice and stir water of...

Страница 22: ...REFCO Manufacturing Ltd Industriestrasse 11 6285 Hitzkirch Switzerland Telefon 41 41 919 72 82 Telefax 41 41 919 72 83 info refco ch www refco ch 4686731 0916...

Отзывы: