VISION VXL
12
8540615 • 19/12/2014 • Rev.8
EXAMPLE OF CONNECTION WITH AD SR0 WITH START/RESTART INTERLOCK ACTIVATED
CONFIGURATION AND OPERATION MODES
The VISION VXL operation mode is selected realizing appropriate connections on the M12
8 poles of the Receiver (Table 3 and Table 4).
AUTOMATIC MODE
The VISION VXL light curtain does not dispose of a start/restart interlock circuit in
automatic mode. In most applications this safety function is necessary. Please
consider the risk-analysis of your application about this matter.
In AUTOMATIC functioning, the two static outputs OSSD1 and OSSD2 follow the status of
the guarded opening.
with the area guarded clear, the outputs will 24VDC
with the area occupied they will supply 0VDC.
CONNECTION
OPERATION MODE
SEL_A (PIN 5)
connected to :
OSSD1 (PIN 1)
SEL_B (PIN 6)
connected to :
OSSD2 (PIN 3)
K1_K2 (PIN 4)
connected to :
0VDC
AUTOMATIC without
K1-K2 feedback
control
SEL_A (PIN 5)
connected to :
OSSD2 (PIN 3)
SEL_B (PIN 6)
connected to :
OSSD1 (PIN 1)
K1_K2 (PIN 4)
connected to :
24VDC
(through series of
contatcts N.C. of
external relays)
AUTOMATIC with
K1-K2 feedback
control
Table 3